User Manual

List of Parameters
Parameters
1-385
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Sets the reference quantity for the unit of the parameters of the free technology controller 1.
When changing over using changeover parameter p11126 to absolute units, all of the parameters involved refer to
the reference quantity.
Dependency: Refer to: p11126
Description: Sets the sampling time for the free technology controller 1.
Value: 0: Reserved
1: 128 ms
2: 256 ms
3: 512 ms
4: 1024 ms
Description: Displays the status word of the free technology controller 1.
Description: Sets the signal source for the setpoint of the free technology controller 1.
p11127 Free tec_ctrl 1 unit reference quantity / Ftec1 unit ref
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0.01 340.28235E36 1.00
p11128 Free tec_ctrl 1 sampling time / Ftec1 t_samp
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 4 2
r11149.0...11 CO/BO: Free tec_ctrl 1 status word / Ftec1 stat_word
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 De-activated Yes No -
01 Limited Yes No -
08 Actual value at the minimum Yes No -
09 Actual value at the maximum Yes No -
10 Output at the minimum Yes No -
11 Output at the maximum Yes No -
p11153 CI: Free tec_ctrl 1 setpoint signal source / Ftec1 setp s_s
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0