SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 06/2011
Description: Displays the torque constant of the synchronous motor used.
Dependency: IEC drives (p0100 = 0): unit Nm / A
NEMA drives (p0100 = 1): unit lbf ft / A
Note: This parameter is not used for induction motors (p0300 = 1xx).
For synchronous motors, parameter r0334 is calculated from p0305, p0307 and p0311.
Description: Sets the motor cooling system used.
Value: 0: Non-ventilated
1: Forced cooling
2: Liquid cooling
128: No fan
Dependency: For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: The parameter influences the thermal 3-mass motor model.
1LA7 motors, frame size 56 are operated without fan.
Description: Displays the rated EMF of the motor.
Note: EMF: Electromagnetic force
r0334[0...n] Actual motor-torque constant / Mot kT act
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: MDS
Units group: 28_1 Unit selection: p0100
Min Max Factory setting
- [Nm/A] - [Nm/A] - [Nm/A]
p0335[0...n] Motor cooling type / Motor cooling type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1, 3), T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
0 128 0
r0337[0...n] Rated motor EMF / Mot EMF_rated
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]