Instruction Manual July 2009 multiranger 100/200
Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed. Qualified Personnel: This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
Table of Contents Specifications ...............................................................................................................................................3 Installation ......................................................................................................................................................8 Mounting ...................................................................................................................................................
Table of Contents mmmmm Hand Programmer .......................................................................................................................27 Programmer Keys ........................................................................................................................28 Dolphin Plus ............................................................................................................................................29 Dolphin Plus Toolbar Buttons ........................
mA I/O ..............................................................................................................................................................49 Readings ..................................................................................................................................................51 Tank Shape and Dimensions ..............................................................................................................51 Characterization Chart [MR 200] ..............
Table of Contents mmmmm Setting the Common Parameters ............................................................................................70 Set Relay 1 (Operate Rake) .......................................................................................................70 Set Relays 2 to 4 (Level Alarms) ..............................................................................................70 External Totalizers and Flow Samplers [MR 200] ..................................................
Communications Installation .............................................................................................................92 Word Order (R40,062) ..........................................................................................................................98 Map ID (R40,063) ....................................................................................................................................98 Product ID (R40,064) ....................................................
Table of Contents mmmmm Error Handling ......................................................................................................................................111 Communication Troubleshooting ...................................................................................................113 Generally ...............................................................................................................................................113 Specifically .............................
Index types ........................................................................................................................................... 223 Appendix B: Technical Reference ................................................................................................ 224 Transmit Pulse ..................................................................................................................................... 224 Echo Processing .....................................................
Table of Contents mmmmm Obstructions in the Sound Beam ......................................................................................... 235 Nozzle Mountings .................................................................................................................... 235 Set the MultiRanger to Ignore the Bad Echo .................................................................... 236 Wrong Reading .............................................................................................
The MultiRanger 100 and 200 The MultiRanger is available in two models, MultiRanger 100 and MultiRanger 200, and is designed for a variety of applications: • • • water and wastewater storage tanks, for measuring liquids, slurries, and solids hoppers, ore bunkers, flotation cells MultiRanger 100 The MultiRanger 200 is a single or dual-point, three or six relay device that offers both level and volume measurement.
If you have any questions, comments, or suggestions about the manual contents, please email us at techpubs.smpi@siemens.com. For the complete library of Siemens Milltronics manuals, go to www.siemens.com/processautomation. Manual Symbols Please note their use carefully.
Specifications Power AC version • 100-230 V AC ± 15%, 50 / 60 Hz, 36 VA (17W)1 • fuse: F3: 2 AG, Slow Blow, 0.375A, 250V DC version • 12-30 V DC, 20W1 • fuse: F3: 2 AG, Slow Blow, 2A, 250V Transmitter fuse • F1: Belling Lee, L754, 4000A HRC, ceramic type, 100mA, 250V Temperature Sensor fuse • F2: Belling Lee, L754, 4000A HRC, ceramic type, 50mA, 250V Mounting • indoor / outdoor Altitude • 2000 m max.
Range • 0.3 m (1 ft) to 15 m (50 ft), dependent on transducer Accuracy • 0.25% of maximum range or 6 mm (0.24”), whichever is greater Resolution • 0.1% of program range1 or 2 mm (0.
Fixed • 0.17 % per °C deviation from programmed value Outputs Transducer drive • 315 V peak mA Analog MultiRanger 100/200: Single or Dual point versions include two mA outputs • • • • • 0-20 mA 4-20 mA 750 ohm maximum Resolution of 0.
Inputs mA (analog) (1) [MR 200 only] • 0-20 or 4-20 mA, from alternate device, scalable Discrete (2) • • • • 10-50 V DC switching level logical 0 = < 0.5 V DC logical 1 = 10 to 50 V DC 3 mA maximum draw Enclosure Wall Mount • 240 mm (9.5") x 175 mm (6.9"). Width dimension includes hinges. • Type 4X / NEMA 4X / IP 651 • Polycarbonate Specifications mmmmm Panel Mount • 278 mm (10.93") x 198 mm (7.8") Width dimension includes flange. • Type 3 / Nema 3 / IP54 • Polycarbonate Weight • Wall mount: 1.
Cable • Do not use coaxial cable for transducer (see General Appendix F: Upgrading on page 246 for more information) • transducer and mA output signal to be 2 copper conductors, twisted with shield/drain wire, 300 Vrms, 0.324 - 0.823 mm2 (22 - 18 AWG), nominal capacitance between adjacent conductors @ 1kHz = 62.3 pF/m (19 pF/ft). Nominal capacitance between conductor and shield @ 1kHz = 108.
Installation Notes: • • Installation must only be performed by qualified personnel, and in accordance with local governing regulations. This product is susceptible to electrostatic shock. Follow proper grounding procedures. All field wiring must have insulation suitable for at least 250 V. Hazardous voltage present on transducer terminals during operation. DC terminals shall be supplied from an SELV source in accordance with IEC 1010-1 Annex H.
Mounting Instructions The wall mount and panel mount units install differently. Please follow the specific instructions for your unit. Note: When routing cable through a conduit, please follow the Cable Routing instructions on page 10 before mounting the MultiRanger. Wall Mount Enclosure Dimensions 14.9 mm (0.58") 15.2 mm (0.6") 160.3 mm (6.325") 130 mm (5.125") 4.3 mm dia. (0.17") four mounting holes lid screws (6) 91 mm (3.58") 6.6 mm (0.26") 240 mm (9.45") 227 mm (8.93") 3.
Cable routed through a conduit: 1. 2. Remove the four mounting screws holding the motherboard to the enclosure. Be careful not to damage the electronics with static electricity. Remove the motherboard from the enclosure by pulling the board straight out. Drill the required cable entry holes. Make sure conduit holes do not interfere with the lower areas on the terminal block, circuit board, or SmartLinx card.
Panel Mount Installing the panel mount unit requires making a cutout in the panel. The dimensions for the cutout are provided in the illustration below. A full size cutout template is provided with your unit or may be downloaded from www.siemens.com/processautomation. Cutout Dimensions 1. 2. 3. 4. Select a place for the unit and fasten the template onto the panel (use tape or tacks). Drill the four fastener holes. Make the cutout using the appropriate tools.
Panel Mount Dimensions 198 mm (7.80") 97 mm (3.82") 36 mm (1.40") 278 mm (10.93") Mounting the Enclosure Once cutout is complete and mounting holes are drilled, follow these steps: Installation mmmmm 1. 2. 3. 4. 5. 6. 7. 8. Remove lid from unit by undoing the six lid screws and lifting it off its hinges. Remove the four screws holding the motherboard to the enclosure. Be careful not to damage the electronics with static electricity.
MultiRanger Board Battery RS-232 RJ-11 Connector Power Supply TB1 TB2 L2/N L1 2 Female Connector for SmartLinx Card TB3 SYNC 1 mA INPUT SHIELD RELAY 1 RELAY 2 SmartLinx Card 1 4 - 20 mA OUTPUTS 2 Terminals RELAY 3 TS-3 SHIELD 1 RELAY 4 DISCRETE INPUTS 2 RELAY 5 RS-485 Connections COM RELAY 6 RS485 A B Installing the Battery The battery (Rayovac BR2032) has a ten-year life expectancy. Please note the life expectancy may be reduced by ambient temperature.
Installing SmartLinx Card SmartLinx cards are generally pre-installed. If unit does not have a SmartLinx card, follow these steps to install one. 1. Installation mmmmm 2. 3. Align card with the two mounting posts and then press-fit with the female connector. Use the screws supplied with the card to attach it to the mounting posts. Wire in the SmartLinx card according to SmartLinx Manual.
Wiring Please note: • • • Verify that all system components are installed in accordance with instructions. Connect all cable shields to the MultiRanger Shield Terminals. Avoid differential ground potentials by not connecting cable shields to ground (earth) anywhere. Keep exposed conductors on shielded cables as short as possible to reduce noise on the line caused by stray transmissions and noise pickup.
Terminal Board The terminal board on the MultiRanger allows all inputs and outputs to be connected simultaneously. Note: Recommended torque on terminal clamping screws. • 0.56 - 0.79 Nm • 5 - 7 in.lbs Please do not overtighten the screws.
Transducers Warning: Hazardous voltage present on transducer terminals during operation. Run the transducer cable in a grounded metal conduit, separate from other wiring (except TS-3 temperature sensor wiring, if applicable).
Temperature Sensor Accurate temperature readings are critical to accurate level measurements because the speed of sound changes, depending on air temperature, and all Siemens Milltronics Echomax and ST-H transducers have an internal temperature sensor.
Level System Synchronization Note: The MultiRanger 100/200 CANNOT be synchronized with the MultiRanger Plus or the HydroRanger. When using multiple ultrasonic level monitors, be sure to run the transducer cables in separate grounded metal conduits. When separate conduits are not possible, synchronize the level monitors so that no unit transmits while another is waiting for echo reception.
Note: Make sure unit is connected to a reliable ground. Ground GND L1 L2/N Digital Communications Wiring the MultiRanger for communications allows it to be integrated into a full SCADA system or an industrial LAN. The MultiRanger can also be directly connected to a computer running Dolphin Plus.
Discrete Inputs Discrete inputs have a positive and negative terminal. Requires an external power supply. Discrete Input (post.) 1 Discrete Input (pos.) 2 Common (neg.
Operation mmmmm Operating the MultiRanger The MultiRanger has two modes of operation: RUN and PROGRAM. RUN Mode In RUN mode, the MultiRanger detects material level and provides control functions. The MultiRanger automatically starts in RUN mode when power is applied. System status is shown on the unit’s LCD, or on a remote communications terminal.
Icons indicating index type (Item 1) edited in PROGRAM mode: Icon Index Type relay secondary index mA input or output Readings in RUN Mode Change the displayed values with the keys on the hand programmer. All readings are shown in the Auxiliary field, except for the totalizer and P920. Key Function + + [MR 200 only] [MR200 only] [MR 200 only] + ### P P P# Toggle Readings between percent and units: • Level: 0 – 100% • Space or Distance:1 100% – 0 Accumulated pump running hours2 for numbered pump.
Operation mmmmm Status Parameters Status parameters give the operating status of the MultiRanger. You can access parameters with the hand programmer (see page 32) or with Dolphin Plus (see page 27). Remote SCADA system access is also possible.
Controlling the Display Adjusting the primary reading for four-digit LCD readout: Parameter P060 P061 P062 Action Decimal Position Convert Reading Offset Reading Sets maximum number of decimals Scales the reading to fit Shifts the reading up or down by a fixed amount Example To reference the displayed level to sea level, enter the distance in Units (P005), between Empty (P006) and sea level. (Enter a negative value if Empty is below sea level.
Setting the Default Auxiliary Reading Operation mmmmm To maintain a constant variable display in the auxiliary reading area, set the default. Example: To leave the level reading on the screen and view the echo confidence in the auxiliary reading field, set the following parameter: Parameter Index Value Description P730 G 805 Auxiliary field defaults to P805 Setting a Specific Auxiliary Reading To display a second auxiliary reading, press Example: To set P P in RUN mode.
PROGRAM Mode The MultiRanger’s primary programming is by the hand programmer. Other access is available through Dolphin Plus software (purchased separately). Notes • • • To activate PROGRAM from RUN mode, press PROGRAM and then DISPLAY The display briefly reads ---- while the measurement reading is verified. Reading level and other data is displayed and programmed relays are operated. Placing a programmed unit that is in normal operation into PROGRAM mode de-energizes all control relay outputs.
Operation mmmmm Programmer Keys Keys Programming Mode Run Mode 1 8-digit Totalizer (toggle) [MR 200 only] Pump Running Time 2 3 5 Head [MR 200 only] Flow based on Head [MR 200] mA Output 6 Temperature 7 Rate of Change 8 Failsafe Time Left 9 9 N/A 0 0 N/A Decimal Point (TVT left) Parameter Value Negative Value (TVT right) Material Level (P731) Fire Transducer Distance Run Mode Program Mode (Key 1) Units or % Next Display Field Units or % (Program Mode) (Key 2) Pause Display Tog
Dolphin Plus (compatible with product software versions 1.06 and earlier)1 After configuration, you can edit parameters, upload and download parameter sets to and from disk, and use parameter sets saved from other instruments. You can also work with echo profiles for fine tuning without the need for special instruments. Built-in Quick Start features and Help files guide you through the entire process. Note: Dolphin Plus is ordered separately from Siemens Milltronics. 1. 2.
Dolphin Plus Toolbar Buttons Operation mmmmm The toolbar buttons provide quick access to Dolphin Plus features.
SIMATIC Process Device Manager (PDM) (compatible with product software versions 1.07 and later)1 • • • • • • • display, set, change, compare, check the plausibility of, manage, and simulate process device data. More information about SIMATIC PDM is available at www.siemens.com/processinstrumentation: go to Products & Solutions > Products & Systems > Communication and Software > Process Device Manager. Please consult the operating instructions or online help for details on using SIMATIC PDM.
Operation mmmmm Activating the MultiRanger All the instructions in the following procedures apply to the hand programmer and assume that the MultiRanger is activated. 1. Power the MultiRanger. 2. 3. Point the programmer at the unit and press PROGRAM Press DISPLAY . .
Security P000 (1954) is a fixed value password. Therefore, you should use other means to secure the MultiRanger if security is a concern. Simulation P000 Lock also controls how simulations affect control relays. By default, control relays are unaffected by simulation levels. But if P000 is set to –1, they react to the simulated level. See Parameters P925–P927 on page 220 for running a simulation.
Default Values Operation mmmmm Parameter default values are indicated with an * in the parameter tables. P000 Lock Primary Index Global 1954 -1 Value other * OFF: programming permitted Simulation Controls (relays energize based on simulated level) ON: Lock activated and programming not permitted via the handheld programmer The asterix identifies 1954 as the default value. Parameter Reset Returning a parameter to factory default. 1. 2. 3. Display the appropriate parameter number.
Changing Parameters(Dolphin Plus) 7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 35 mmmmm Most examples in this manual use the icons from the hand programmer but nearly all functions are also available through Dolphin Plus. Operation The other method for changing parameter values is with Dolphin Plus software. It lets you access the MultiRanger from a PC or on site with a laptop and change MultiRanger parameters.
Operation mmmmm Parameter Indexing Parameters are indexed when they apply to more than one input or output. The index value defines the input/output for that parameter. Indexed parameters contain a value for each index, even if that index is not used. MultiRanger Display The index number and the index values are displayed above the parameter indicator on the LCD. Index Value Index Number 1 2 3 4 5 6 Notes • • • • Transducers are always indexed when the dual point option is enabled.
Primary and Secondary Indexes Primary Index Example Setting: P111[3] = 52 P111 1 2 3 4 5 6 52 • • P111 sets the Relay Control Function P111(3) = 52 sets Relay #3 to a value of 52. Secondary Index Parameters with a secondary index permit multiple values for a primary index (point). For example, a volume calculation based on vessel characterization breakpoints requires a distinct set of breakpoints for each measured point.
Operation mmmmm Example [MR 200 only] P054 provides up to 32 breakpoint levels used with P055 (Volume Breakpoint) for universal volume calculation. The illustration indicates how you can set secondary indexes to specific functions. A B P054 [1,6] = 2m P054 [2,6] = 8m C P054 [1,3] = 1.5m P054 [1,1] = .75m P054 [2,3] = 5.5m P054 [2,1] = 2.75m P054 1 2 [6 = 2m] A [3 = 1.5m] B A [6 = 8m] B [3 = 5.5m] C [1 = 0.75m] [1 = 2.75m] C P054 [1,1] = .75m sets breakpoint 1 on transducer 1 to .75m.
Average or Differential [MR 200 only] relay is configured Dot indicates relay is energized/deenergized Index 2 3 Description indexed by Transducer One or Two indexed by level measurement 1 = Transducer One 2 = Transducer Two 3 = Calculated Level (average or difference) Dual Point Models The MultiRanger starts in an OFF state and does not take level measurements.
Operation mmmmm Average or Differential [MR 200 only] For differential or average operation dual-point MultiRanger, set P001 to 4 (differential) or 5 (average) and connect two transducers of the same type.
Relays Relays are the primary controls of external devices such as pumps or alarms. The MultiRanger comes with extensive control and alarm functions. General Introduction Depending on the model, up to six onboard multi-purpose relays are provided on the MultiRanger. Each relay may be independently assigned to one function and has a corresponding status icon on the LCD.
Temperature [MR 200] In high alarm, the function goes on when the temperature rises to the ON setpoint and goes off when the temperature lowers to the OFF setpoint. In low alarm, the function goes on when the temperature lowers to the ON setpoint and goes off when the temperature rises to the OFF setpoint. Loss of Echo The function goes on when the fail-safe timer expires. The function goes OFF when a valid echo is received (fail-safe timer is reset).
Relay Status – Non Run Modes When the fail-safe timer expires, pump control relays respond as previously described. However, alarm relays will respond in the following manner: Fail-Safe Mode Fail-Safe High Fail-Safe Low Fail- Safe Hold Relay Status High Alarm ON OFF HOLD Low Alarm OFF ON HOLD Upon entering the program mode, all pump control relays will be turned OFF. Alarm relays will hold their prior status.
P111–Control Functions The control function energizes the relay coils. When the instrument is at rest (no controls operating) the relay coils are de- energized. P112–Relay ON Setpoint Sets the process point at which the relay is tripped. P113–Relay OFF Setpoint Sets the process point at which the relay is reset. Relays mmmmm P118–Relay Output Logic Affects relay reaction. Reverses the logic (normally-open to normally-closed or vice versa).
[MR 100]: Functions affected by setpoint are configured by parameters that determine the application requirements such as timing. P111 Pump and Control functions (see page 134) sets the functions requirements. [MR 200]: Functions affected by setpoint are configured by parameters that determine the application requirements such as timing. P111 Pump and Control functions (see page 134 sets the function requirements.
Preset Applications Preset applications set up the relay parameters to predetermined values shown below: Value Off Wet Well 1 # Parameters Affected 0 All relays set to OFF Pump down with the following settings: Relay # 1 2 3 4 5 6 P111 52 52 1(H) 1(L) 0 0 P112 70% 80% 90% 10% – – P113 20% 20% 85% 15% – – Pump down with the following level and rate settings: Relay # Parameter 1 2 3 4 5 6 P111 52 52 1(H) 1(L) 0 0 P112 70% 80% 90% 10% – – P113 20% 20% 85% 15% – – P121 1 P121 sets the pump relays to accept co
Backup Level Override Backup level override provides the option of overriding the ultrasonic input with another contacting point level device, for example, the Pointek CLS200. The ultrasonic reading is fixed at the programmed switch level until the discrete input is released and the ultrasonic device makes its decisions based on the override value. Backup Level Override Parameters P064: Reading Override Enable Sets the discrete input as the source of a level reading override.
Discrete Inputs Wiring the Discrete Inputs Normal state is standard operation, with the MultiRanger sensing the material level and controlling the pumps. The discrete input contacts are either normally-open or normally-closed when the system state is normal. Example: Normal state for a backup high level switch is open, and the contacts on the discrete input are wired as normally-open. See Discrete Inputs on page 21 for complete details on wiring the discrete inputs.
mA I/O To integrate the MultiRanger with other equipment, use the mA input and outputs. Note: When a mA input parameter is accessed, a mA symbol appears in the upper left corner of the LCD display. The mA input can be used as a level measurement or can be passed on to a SCADA system.
Calibrating 4 mA Output 1. 2. 3. 4. 5. Connect the mA receiving device to the MultiRanger. Put the MultiRanger into PROGRAM mode. Set P911–mA Output Value to 4.0. View the mA level on the receiving device. If there is a discrepancy, a.Attach ammeter to MultiRanger mA output. b.Access P214, Index 1 (for mA output 1) or 2 (for mA output 2). Press CLEAR and ENTER . The ammeter should show a value near 4 mA. c.Enter the exact value displayed on the ammeter into P214 (Index 1 or 2). d.
Volume [MR 200] Calculate and display volume instead of level. For programming all setpoint parameters in terms of volume units rather than level units. Calculate pumped volume to accomplish the following: • Totalize the volume of material that is pumped out of the wet well • Set an alarm on pump efficiency 2. If you require this functionality, please contact your local Siemens Milltronics representative at www.siemens.com/processautomation .
If you cannot use a pre-defined tank, then use one of the universal tank shapes and program the characterization curve. 1. Plot a volume to height chart. Usually a tank supplier will provide this chart. However, if you have a custom-built wet well then you will need access to complete drawings of the well or accurate measurements. Enter the curve values from this chart into P054 and P055. Ensure extra points are added around sharp transitions in the wet well volume (e.g: as steps in the well wall). 2. 3.
MultiRanger 200 only Parameter Transducer Index Value Description 7ML19981FB06 1 Determines the Level breakpoints at which the volumes are known. Determines the volumes which correspond to the level breakpoints. The universal calculations interpret between the breakpoints to produce an accurate model of the volume at all level readings.
Alarms Level The level alarm is the most common. Use this alarm to warn you when your process is in danger of being upset due to high or low levels. Generally, the four alarms used are Hi, Hi Hi, Lo, and Lo Lo. Alarms mmmmm Set the Common Parameters P006 hi hi hi P007 lo lo lo Prerequisite: You must know the details of your application and substitute the values for the sample values provided. If you are bench testing the unit, then set your test values to be the same as the sample values.
Setting Simple Level Alarms To set Relay Five to a standard level alarm (Hi Hi, Hi, Lo, Lo Lo) do the following: Parameter Index Value Description P110 5 1 • P111 5 1 • • Press UNIT symbol. • Press ARROW keys as required to scroll to the alarm designation (L, LL, H, or HH). Press ENTER to enter the value.
In Bounds/ Out of Bounds Range [MR 200] Use the bounded range alarms to detect when the level is inside or outside of the range. By using a bounded range alarm, you can effectively put two level alarms (high and low) on one relay. Alarms mmmmm Setting an Out of Bounds Alarm Parameter Index Value P111 P112 P113 P116 5 5 5 5 3 1.3 0.3 0.05 Results: • • Trips alarm above 1.35 m and below 0.25m Resets alarm below 1.25 m and above 0.
With P112 and P113, you can set a high alarm (P112 > P113) or a low alarm (P112 < P113). This shows a high alarm: Parameter Index Value P111 P112 P113 P110 5 5 5 5 5 45 43 1 Description Alarm on temperature ON setpoint at 45 °C OFF setpoint at 43 °C Take the temperature reading from Transducer One The temperature source can be the temperature sensor built into the transducer or an external TS-3, as set by P660. Parameter Index Value P110 P111 P070 5 5 G 1 6 0.
Pump Control Setting a Pump Down Group Example: Sewage Wet Well Setting a group of three pumps to pump down a wet well. MultiRanger P006 Outflow Pump Control mmmmm Inflow P007 Set the Common Parameters Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values. Parameter Index1 P001 P002 P003 P004 P005 P006 P007 G G G G G G G 1.
Set Relays to ALTERNATE DUTY ASSIST Parameter Index P111 P111 P111 1 2 3 Value Description 52 52 52 Sets the pump relays (index 1, 2, and 3) to ALTERNATE DUTY ASSIST. Set the ON Setpoints Parameter Index P112 P112 P112 1 2 3 Value Description 1.0m 1.1m 1.2m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps. Set the OFF Setpoints Parameter Index Value P113 0 0.
Set the Common Parameters Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values. Parameter Index1 P001 P002 P003 P004 P005 P006 P007 G G G G G G G 1. Value Description 1 1 2 102 1 1.8 1.4 Operation = level Material = liquid Maximum Process Speed = medium Transducer = XPS-10 Units = meters Empty = 1.8m Span = 1.4m Example assumes a single measurement unit.
Other Pump Control Algorithms Set Relays to ALTERNATE DUTY BACKUP [MR 200] Parameter Index P111 P111 P111 1 2 3 Value Description 53 53 53 Sets the pump relays (index 1, 2, and 3) to ALTERNATE DUTY BACKUP. Set the Relay ON Setpoints [MR 200] Parameter Index P112 P112 P112 1 2 3 Value Description 0.4m 0.3m 0.2m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps.
Set Relays to FIXED DUTY BACKUP [MR 200] Parameter Index P111 P111 P111 1 2 3 Value Description 51 51 51 Sets the pump relays (index 1, 2, and 3) to FIXED DUTY BACKUP. Only one pump will ever run at one time. Set the Relay ON Setpoints [MR 200] Parameter Index P112 P112 P112 1 2 3 Value Description 0.4m 0.3m 0.2m Sets the three setpoints for the pump relays. The setpoints remain attached to the pump relays. Set the Relay OFF Setpoints [MR 200] Parameter Index Value P113 0 1.
Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200] Parameter Index P111 P111 P111 1 2 3 Value Description 56 56 56 Sets the pump relays (index 1, 2, and 3) to FIFO DUTY ASSIST. Set the Relay ON Setpoints [MR 200] Parameter Index P112 P112 P112 1 2 3 Value Description 0.4m 0.3m 0.2m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps.
When the first ON setpoint is reached, the pumps will start, one by one, until the material level rate of change is set at the same value or greater than the value in: • • P703 – Emptying Indicator (pump down applications) P702 – Filling Indicator (pump up applications) Set delay between pump starts using P132 – Pump Start Delay. Single and Dual Point [MR 200] • • Single Point Mode: one pump by rate control available that affects all pumps.
Totalizing Pumped Volume [MR 200] Prerequisite: the volume of the vessel must be known. Parameter Index P001 P002 P003 P004 P005 P006 P007 P050 P051 G G G G G G G G G Value Description 7 1 2 102 1 1.8 1.4 1 17.6 P111 P111 P111 P112 P112 P112 P113 1 2 3 1 2 3 0 52 52 52 1.0 1.2 1.4 0.2 Operation = pumped volume These parameters are as shown above. Tank shape is Flat Bottom. Max volume is 17.6m3 or 17,600 liters. Sets relays 1, 2, and 3 as a pump group using ALTERNATE DUTY ASSIST CONTROL.
Setting a Pump to Run On [MR 200] When you need to pump below the normal OFF setpoint, use P130 (Pump Run-On Interval) and P131 (Pump Run-On Duration) to control this event. Example: The pump connected to Relay Three is set to pump for an extra 60 seconds every 5 hours. Parameter Index P130 P131 3 3 Value Description 5 60 Time in hours of run-on interval. Run-on for 60 seconds. Note: P130 counts when the indexed relay is tripped, not the number of pump cycles.
Example [MR 200]: A range of 0.5 meters is used to vary the setpoint. The randomly-selected setpoints are always inside the ON and OFF setpoints. Level Setpoint ON Random Setpoint Range Wall Cling Value Level Setpoint OFF Grouping Pumps [MR 200] Example: Pumps One and Two can operate as a group and Pumps Three and Four can operate as another group.
Example: The flush valve connects to Relay Four and the watched pump is on Relay One. Parameter Index P170 P171 P172 P173 G G G G Value Description 1 3 10 120 Watch Relay One to count pump cycles. Open the flush valve for 3 cycles. Use the flush value every 10 cycles. Open the flush valve for 120 seconds. Relay Controlled by Communications A relay can be controlled directly by a remote system through communications. No other control schemes can then be used with a relay configured this way.
Rake (Screen) Control [MR 200] This feature is only available on the MultiRanger 200. Screens or rakes are mounted on the inflow channel of the wastewater treatment plant to prevent debris from clogging the equipment. When material builds up on the screen, a level differential is created, and the water level is higher in front of the screen than behind it.
Setting the Common Parameters Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values. Parameter Index P001 P002 P003 P004 P005 P006 G G 1,2 1,2 G 1 2 1 2 3 P007 Value Description 4 1 2 102 1 1.8 2.2 1.4 1.4 1.4 Operation Material Max. Process Speed Transducer Units Empty Empty Span Span Max Differential = Differential = liquid = medium = XPS-10 = meters = 1.8m = 2.
External Totalizers and Flow Samplers [MR 200] This feature is only available on the MultiRanger 200. External totalizers are simple counters which count the number of relay clicks produced by the MultiRanger. This is generally used to keep track of OCM or pumped volume totals. Note that both of these values are also stored in the MultiRanger and are available through communications. Flow samplers are devices which take a sample of liquid when triggered by a relay click.
The source of units depends on the operation: Operation OCM (P001=6) Pumped Volume (P001=7) Units Source Parameter P604–Maximum Flow, or P608–Flowrate Units P051–Max Volume Flow Sampler Based on Volume and Time To trigger a flow sampler relay based on flow, use P111[r]=41 and set the other parameters: Counter Formula 1 Contact per P641 x 10P642 units Operation Units Source Parameter OCM (P001=6) P604 – Maximum Flow, or P608 – Flowrate Units By using a mantissa (P641) and an exponent (P642), the rela
1. Dimensional (P600 = 2,3,6,7) For some common weir and flume types. PMD dimensions (P602) are entered directly. • • • • BS-3680 / ISO 1438/1 Thin plate V notch weir on page 75 BS-3680 / ISO 4359 Rectangular Flume on page 76 Palmer Bowlus Flume on page 77 H Flume on page 78 2. Exponential (P600 = 1) For most other weir and flume types. PMD exponents provided by the manufacturer are entered. Flow is calculated using the exponent (P601) and the maximum values (P603 and P604).
Many PMDs start flowing higher than the traditional empty distance of the application. You can account for the flow in one of two ways: 1. Use P605 (Zero Head) to have OCM calculations ignore levels below that value. Possible head = P007 minus P605. Note: P603 (Max. Head) is preset to P007 and is not updated when P605 is used. Make sure you set P603 to the correct value when using P605. P006 P603 P007 2.
To display the totalized volume on the LCD use the following parameters: Index P737 G Value Description 2 Show the eight digit totalizer in the primary display Applications Supported by MultiRanger 200 BS-3680 / ISO 1438/1 Thin plate V notch weir Front View Side View Transducer notch angle P006 P603 P007 P602 P801 4 to 5 x hmax (hmax = P007) Plan View Parameter Index P600 P602 (view only) P603 P801 P608 G 1 2 G G G 7ML19981FB06 Value 7–ISO 1438/1 V Notch Weir Notch angle Discharge coeffici
mmmm m Open Channel Monitoring MR 200 BS-3680 / ISO 4359 Rectangular Flume h Plan View Diagonal View 4 to 5 x hmax (hmax = P007) L Flow Front View Side View Transducer P006 h Flow P605 (p) Parameter Index P600 P602 G 1 2 3 4 5 6 7 G G (view only) (view only) (view only) P605 P608 Page 76 Value 6–ISO 4359 Rectangular Flume Approach width (B) Throat width (b) Hump Height (p) Throat length (L) Velocity coefficient (Cv) Discharge coefficient (Cd) Cross sectional area Zero Head Flowrate Units
Plan View Flow Front View D/2, point of measurement Transducer Side View P006 P007 P603 P605 Parameter Index P600 P602 P603 P604 P605 P606 G 1 G G G G Value 2–Palmer Bowlus Flume Flume width (D) Maximum Head (preset = P007) Maximum Flow Zero Head Time Units Application Information • • • • • Sized by pipe diameter D Flume relief is trapezoidal Designed to install directly into pipelines and manholes Head is referenced to bottom of the throat, not bottom of the pipe For rated flows under free flo
Transducer mmmm m Open Channel Monitoring MR 200 H Flume Flow Point of Measurement Plan View P006 P007 D Front View • • • • Parameter Index P600 P602 P603 P604 P606 G 1 G G G 0.5 0.75 1.0 1.5 2.0 2.5 3.0 4.
Standard Weirs Transducer 3 to 4 hmax h Weir Profile Applicable Weir Profiles V-notch or triangular suppressed rectangular Parameter Index P600 P601 G G P603 P604 P606 P801 G G G G 1. cipolleti or trapezoidal sutro or proportional Value 1 - Exponential Function Weir Type V-notch Suppressed rectangular Cipolletti or trapezoidal Sutro or proportional Maximum Head Maximum Flow Time Units Range Extension Value1 2.50 1.50 1.50 1.00 Values are samples only.
mmmm m Open Channel Monitoring MR 200 Non-Applicable Weir Profiles contracted rectangular compound Poebing approximate exponential Flows through these weirs can be measured using the Universal Flow Calculation P600 = 4 or 5. See Universal Calculation Support on page 83. Parshall Flume Note: C = Converging Dimension.
Plan View Throat Front View Converging Diverging Transducer Point of Measurement Side View 0 Head Parameter Index P600 P601 P603 P604 P605 P606 G G G G G G Value 1–Leopold Lagco Flume 1.
Open Channel Monitoring MR 200 Flume Size (pipe diameter in inches) Point of Measurement cm inches mmmm m 4-12 15 18 21 24 30 42 48 54 60 66 72 2.5 3.2 4.4 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.2 1 1¼ 1¾ 2 2½ 3 3½ 4 4½ 5 5½ 6 Cut Throat Flume Plan View Application Information • • Page 82 Similar to Parshall flume except that the floor is flat bottomed and throat has no virtual length. Refer to manufacturer’s specifications for flow equation and point of head measurement.
Two curve types are supported: • • P600 = 4–linear (piece wise linear) P600 = 5–curved (cubic spline) Both are shown in the following chart. Typical Flow Characterization Flow (P611) Maximums (P603, P604) Linear Curved Head (P610) Characterization is achieved by entering the head (P610) and corresponding flow (P611), either from empirical measurement or from the manufacturer's specification. Increasing the number of defined breakpoints will increase the accuracy of the flow measurement.
mmmm m Open Channel Monitoring MR 200 Example Flumes These example flumes would both require a universal calculation. Trapezoidal Dual Range (nested) Parshall Example Weirs These weirs could require universal calculation.
Testing the Configuration After programming the unit, you must test the device to ensure that it performs to your specifications. This test can be run in simulation mode or by varying the level in the application. The latter is preferred as it more accurately represents running conditions. However, if it is not possible to do a physical test, a simulation will ensure that control programming is correct. In simulation mode, the LCD display reacts to the simulated level changes.
3. Press the ARROW or to adjust the simulated rate of rise or fall, based on the chart on page 86. The maximum rate is 4% of Span / second. The effect of the ARROW key is determined by the state (rate of rise or fall) immediately before the key is pressed. Testing the Configuration mmmmm Action Press Press State (prior to pressing key) Effect Stop Rise at 1% of Span / second Rise at 1% of Span / second Rise at 4% of Span / second (max.) Rise at 4% of Span / second (max.
5. 6. Change parameters P610 and P611, as required. Repeat steps 2 to 5 until the flow curve is verified. I/O Checkout After the unit is installed, test to verify the wiring. Relays Discrete Inputs Use P270 to force the input value and verify that the results are as expected.
Monitor system performance carefully, under all anticipated operating conditions. 1. When the MultiRanger performs exactly as required, programming is complete. 2. If alternate Reading units, Failsafe action, or relay operation is desired, update the parameters for the new functionality. 3. If the system performance experiences problems, see General Appendix C: Troubleshooting, on page 231.
MultiRanger Communications MultiRanger Communication Systems The MultiRanger is an integrated level controller capable of communicating process information to a Supervisory Control and Data Acquisition (SCADA) system, via a serial device such as a radio modem, leased line, or dial-up modem. MultiRanger The standard MultiRanger supports the following two communication protocols: Modbus Modbus is an industry standard protocol used by SCADA and HMI systems.
Communication Systems The MultiRanger is capable of communicating with most SCADA systems, PLCs, and PCs. The supported protocols are: • Modbus RTU/ASCII – base unit on RS-232 or RS-485 transport • PROFIBUS DP – optional SmartLinx® module • Allen-Bradley®1 Remote I/O – optional SmartLinx module • DeviceNet® – optional SmartLinx module Communication Ports The MultiRanger comes with two communication ports on the base unit.
Parameter P770 P771 P772 P773 P774 P775 P778 P782 Index Value 2 3 2 1 2 9.6 2 0 2 8 2 1 2 0 2 0 Description Modbus RTU slave Network address, only used for RS-485 Data rate of 9600 baud No parity, common setting 8 data bits, common setting 1 stop bit, common setting No modem connected Index parameter values globally SmartLinx Other protocols are available through optional SmartLinx communications modules.
Communications Installation Wiring Guidelines • • • • the RJ-11 cable maximum length is 3 meters RS-485 maximum length is 1,200 meters (4,000 feet) use 24 AWG (minimum) use good quality communication grade (shielded twisted pairs) cable that is recommended for RS-485 for port 2 (Belden 9842) run the communication cable separately from power and control cables (do not tie wrap your RS-232 or RS-485 cable to the power cable or have them in the same conduit) use shielded cable and connect to ground at one end
Port 1: RS-232 RJ-11 Jack To connect the unit to a PC using an RS-232 jack, use the cable as shown: Computer DB-9 (male) RJ-11 to DB 9 converter 6 1 2 Tx 3 Rx 4 SG RJ-11 on MultiRanger 6 4 6 7 8 RJ-11 jack 1 6 1 1 2 3 4 5 5 4 3 2 6 1 1 6 Rx 2 Tx 3 SG 5 6 6 1 Modular cable with RJ-11 plug Note: Jumper pins 4-6 and 7-8 at the DB-9.
MultiRanger Terminal Block (Shield to be grounded at one end) C A B O M To connect the unit to a modem using an RS-485 port: RS-485 Modem COM MultiRanger Terminal Block A B Configuring Communication Ports (Parameters) The 11 parameters listed are indexed to the two communication ports, unless otherwise noted: An asterisk (*) identifies the preset value.
For devices connected with the Siemens Milltronics protocol, this parameter is ignored. For devices connected with a serial Modbus slave protocol, this parameter is a number from 1-247. The network administrator must ensure that all devices on the network have unique addresses. Do not use the value 0 for Modbus communications as this is the broadcast address and is inappropriate for a slave device. P772 Baud Rate The communication rate with the master device. Primary Index Values Communications Port 4.
P778 Modem Available Sets the MultiRanger to use an external modem. Primary Index Values Communications Port 0 * No modem connected 1 Answer only P779 Modem Inactivity Timeout Sets the time that the unit will keep the modem connected with no activity. Primary Index Values Communications Port Range: 0-9999 seconds 0 * No timeout To use this parameter, ensure that P778 (Modem Available) =1.
Modbus Register Map Features affecting volume, mA input, and Average or Difference readings apply to the MultiRanger 200 only. They are clearly marked. The memory map of the MultiRanger occupies the Modbus holding registers (R40,001 and up). This map is used when the protocol is Modbus RTU slave or Modbus ASCII slave. Register Map for Most Common Data Legend Type Start Data Type Description #R Read/Write Type The type of data held in the group of registers. The first register to hold the referenced data.
Type Point Data I/O Pump Control Description #R 1 Temperature (2) Totalizer for points 1 and 2 [MR 200] Discrete Inputs (2) Relay Outputs (3 or 6) mA Input (1) [MR 200] mA Output (2) 41,030 41,040 2 41,070 41,080 1 Pump on Setpoint (3 or 6) Pump off Setpoint (3 or 6) Pumped Volume (2) [MR 200] Pump Hours (3 or 6) Pump Starts (3 or 6) 41,420 Parameter Access 1.
Product ID (R40,064) This value identifies the Siemens device type: Device Type Value MultiRanger 100 MultiRanger 200 6 4 Point Data (R41,010 – R41,031) Measurement point data contain the current instrument readings. These are the values shown for the reading measurement for each measurement point. The reading is based on the setting for P001 (operation). P001 can be set to level, distance, OCM flow, or volume. See Parameter Reference section on page 117 for details.
Discrete Inputs (R41,070) This table shows the current status of the discrete inputs. Only register 41,070 is used. Discrete Input 1 2 Data Address 41,070, bit 1 41,070, bit 2 Relay Outputs (R41,080) This table shows the current status of the relays. A reading of 0 means that the relay function is not asserted and a 1 means that it is asserted. For example, a 1 for a pump relay means that the pump is running.
Pump OFF Setpoint (R41,430 – R41,435) The OFF setpoint level (P113) for the referenced pump relay. The setpoint is scaled from 0 to 10,000 (0 to 100% of span multiplied by 100). So 54.02% is shown in the register as 5402. Pumped Volume (R41,440 – R41,443) [MR 200] The pumped volume registers hold the current total for all of the pumps associated with a level point. These registers are available only if operation is set to pumped volume (P001 = 7). These volumes can become very large.
Parameter Access (R43,998 – R46,999) Parameter values are given as integers in the range of registers from R44,000 to R44,999. The last three numbers of the register correspond to the parameter number. Parameter Register # Format Register # Parameter # 44,000 44,001 44,002 … 44,999 46,000 46,001 46002 … 46,999 P000 P001 P002 … P999 Usually, the parameters are all read / write. Note: • • • Parameters P000 and P999 are read only.
Reading Parameters To read parameter values, follow the steps listed in either the Global or the Parameter Specific Index Method that follow. You must be able to program your HMI or SCADA system before completing these methods. Global Index Method (P782 = 0) Global format method sets index values for all parameters simultaneously. Use this method to read multiple values set to the same index values. 1. Write the primary index value into R43,999.
• from Transducer One Send the integer value 01008 to register 46,921. 2. Read the value from the appropriate parameter register (the example uses 44,921). Types of values are: • Numeric Values on page 107 • Bit Values on page 107 • Split Values on page 108 • Text Messages on page 109 • Relay Function Codes (P111 Only) on page 110 A value of 22,222 indicates that an error occurred. Specify a different format type and try again.
Format Words (R46,000 to R46,999) Format words are unsigned integers that contain up to three values (described below). The number of values used in the format words depends on the Parameter Index Location (P782) that is used. Parameter P782 Parameter Index Location, described on page 96, determines which of two methods is used to access the format words: Global Index Method or Parameter Specific Index Method.
The decimal offset indicates how the remote system must interpret the integer value that is stored in the parameter access register. The following table shows how different parameter values can be shown based on a register value (integer) of 1234. Decimal Offset 0 1 2 3 4 5 6 7 8 9 0 –1 –2 –3 –4 –5 +1 +2 +3 Percent Example 1,234 12,340 123,400 1,234,000 12,340,000 123,400,000 123.4 12.34 1.234 12.
Data Types Numeric parameter values are the most common. For example, parameter P920 (Reading) returns a number that represents the current reading (either level or volume, depending on the MultiRanger configuration). Numeric values are requested or set in units or percent of span, and may be specified with a number of decimal places. Numeric values must be in the range –20,000 to +20,000 to be valid.
For example, if R41,442 is read as a UINT32, the 32 bits would look like this: Data Types mmmmm R41,442 16 MSW 32 R41,443 1 16 LSW 32-bit integer value (UINT32) 1 1 The two registers are read as a 32-bit integer. The most significant word (MSW) and least significant word (LSW) can be reversed to accommodate some Modbus drivers. See Word Order (R40,062) on page 98 for details. The position of the decimal place is dependent on the register. For more details see the description of the register.
Text Messages 22222 30000 30001 30002 30003 30004 30005 30006 30007 30008 30009 30010 30011 30012 30013 30014 30015 -32768 32767 7ML19981FB06 Text Message as displayed on LCD Invalid value Off On ≡≡≡≡ (parameter does not exist) Err Err1 Open Short Pass Fail Hold Lo Hi De En ---- (parameter has not been set) Value is less than –20,000 Value is greater than 20,000 MultiRanger 100/200 – INSTRUCTION MANUAL Page 109 mmmmm Number Data Types If a device parameter returns a text message, that message is co
Relay Function Codes (P111 Only) Data Types mmmmm Please note that the MultiRanger 200 offers more function codes. If a device parameter returns a relay function code, that message is converted to a number and is then provided in the register.
Error Handling Modbus Responses When polled by a Modbus Master, a slave device will do one of the following: Not reply. This means that something went wrong with the transmission of the message. 2. Echo back the command with the correct response (see the Modbus specification for more details). This is the normal response. 3. Return an Exception Code. This reflects an error in the message.
If the host attempts to write one or more registers that are out of range, an exception response code 2 or 3 is generated, depending if the start address is valid. • If the host used an unsupported function code, an exception response code of 01 should be generated. However, this is not guaranteed and there may be no response.
Communication Troubleshooting Generally 1. Check the following: • • • There is power at the unit The LCD is showing the relevant data The device can be programmed using the hand programmer 2. Check the wiring pin outs and verify that the connection is correct. 3. Verify that values in the set-up parameters (P770 to P779) match the settings in the computer used to communicate with the unit. 4. Check that the port on the computer is correct.
Communication Appendix A: Single Parameter Access (SPA) This Appendix is intended to provide someone with advanced communications knowledge the ability to access any parameter value in any available format. Built into MultiRanger is an advanced handshaking area that can be used to read and write single registers to the MultiRanger. This section performs a similar function to the Parameter access section. The differences are: 1. Advanced section is more powerful and harder to program. 2.
Writing Parameters To set parameters through Modbus do the following steps: 1. Send the parameter, its primary index, and its secondary index (usually 0) to registers 40,090, 40,091, and 40,092. 2. Write the value to registers 40,096 and 40,097. 3. Write the desired format word to register 40,093 to enable the MultiRanger to interpret the value correctly.
Error Codes The error codes returned in the format area are 8-bit integers found in the lowest eight bits of the format word. This allows for 256 potential error codes. Currently the MultiRanger has two error codes available.
Parameter Reference The MultiRanger is configured through its parameters, and the application determines the parameter values which are entered into the unit. Please check your value entries carefully before operating the MultiRanger to ensure optimum performance. MultiRanger 100 and MultiRanger 200 All MultiRanger 100 and MultiRanger 200 parameters are listed in this section. MultiRanger 200 parameters are identified separately.
Index types Name # of indexes Global This parameter applies to the entire unit n/a View only This parameter can not be set, only viewed n/a Breakpoint Indexed by breakpoint Parameter dependent Dimension Indexed by PMD dimension up to 7 Discrete Input Indexed by discrete input 2 Echo Profile Indexed by stored echo profile 10 Level1 Indexed by level point 1, 2 or 3 Indexed by mA input 1 mA output1 Indexed by mA output 0 or 2 Comm.
P000 Lock Notes: • • This lock only applies to the handheld programmer: it does not lock access through communications. A remote master can change configuration if P799 is set to allow this. Secures the MultiRanger from changes via the handheld programmer.
For DPD and DPA Programming [MR 200] Please note that this feature is only available on the MultiRanger 200. Single Point Model Use For Dual Point Difference (DPD) or Dual Point Average (DPA), the unit requires either two transducers of the same type, or one transducer and one mA input. If two transducers are used, all transducer parameters become indexed, and a third level point is calculated. • • DPD (difference) = Point 1 - Point 2 DPA (average) = (Point 1 + Point 2) / 2.
P003 Maximum Process Speed Determines level change reaction. Primary Index Transducer 1 Values Slow (0.
Related (chart cont’d from previous page) • • • • • • • • • • • • P203 mA Output Value/Transducer mA Input (P250 to P260) (related only to Value 250) P800 Near Blanking P823 Reform Echo P832 TVT Shaper Adjust P840 Short Shot Number P841 Long Shot Number P842 Short Shot Frequency P843 Long Shot Frequency P844 Short Shot Width P845 Long Shot Width P852 Short Shot Range P005 Units Specifies measurement units used for dimensional values.
P007 Span Sets the range levels to be measured. Level Primary Index Range: 0.000 to 99.000 m (or equivalent depending on units) Values Preset: based on Empty (P006) Alters • • • P605 Zero Head P112 Relay ON Setpoint P113 Relay OFF Setpoint Altered By • • P005 Units P006 Empty Related • • • • • Volume (P050 to P055) P800 Near Blanking P921 Material Measurement P922 Space Measurement P926 Head Measurement Span is preset for a value close to the maximum available.
P050 Tank Shape [MR 200] Enter the Tank Shape value matching the monitored vessel or wet well. When Operation is LEVEL (P001 = 1), liquid (material) volume is calculated. Alternatively, when Operation is SPACE (P001 = 2), remaining vessel capacity is calculated. In RUN mode, readings are displayed in percent of maximum volume. To convert readings to volumetric units, see Maximum Volume (P051).
Values 8 Sphere 9 Universal Linear 10 Universal Curved • • • • • Alters P001 Operation P051 Maximum Volume Pump Efficiency (P180-P186) Pumped Volume Totalizer (P622-P623) P920 Reading Measurement P051 Maximum Volume [MR 200] For Readings in volumetric units (rather than percent), enter the equivalent vessel volume for Span (P007). Primary Index Level Range: 0.000 to 99999 Values Preset: 100.
P052 Tank Dimension A [MR 200] Dimension A as used in P050 Tank Shape. Level Primary Index Range: 0.0 to 99.00 m (or equivalent depending on units) Values Preset: 0.000 • Related P050 Tank Shape Enter one of the following: • height of the tank bottom if P050 = 2,3,4, or 5 OR • length of one end section of the tank if P050 = 7, in Units (P005) P053 Tank Dimension L [MR 200] Dimension L as used in P050 Tank Shape. Level Primary Index Range: 0.0 to 99.
P055 Volume Breakpoints and Characterization (Universal Volume Calculation) [MR 200] Each segment defined by the level breakpoints (P055) requires a volume so that the MultiRanger can make the level-to-volume calculations. Primary Index Level Secondary Index Breakpoint Values Range: 0.0 to 99999 Related • P054 Breakpoints Levels (Universal Volume Calculation) Typical volume calculations Cone Cylinder V = (1/3)πr2h V = πr2h Entering a Volume Breakpoint 1. 2. 3. Go to Parameter P055.
Alters • P607 Flowrate Decimal Altered by • P051 Maximum volume Related • P920 Reading Measurement In RUN mode, the decimal position adjusts to prevent the number of digits from exceeding the display capabilities. To keep the decimal place from shifting, reduce the number of decimal places to that shown at 100%. Example: If 100% is 15m, use two decimal places for sample readings of 15.00 or 12.15.
Backup Level Override Use this feature to override the ultrasonic reading by a discrete input such as a contacting point device. The ultrasonic reading will be fixed at the programmed switch level until the discrete input is released. The ultrasonic device makes decisions based on the override values. P064 Reading Override Enable Sets the discrete input to act as the source for a level reading override. Primary Index Values Related Transducer 0 1-2 • • * OFF: No override.
Please note the following: • • enter value in current units (as selected in P005) valid for level, space, and distance • volume is calculated based on the Backup level Example: Transducer One is configured for a level measurement. Digital Input 2 is connected to a Hi Level Backup switch located a level of 4.3m. Parameter Index P064 Value 1 2 P065 1 4.3 When the level rises to 4.3m, and the switch is activated, the reading is forced to 4.3m. The reading stays at 4.
Failsafe (P070 to P072) P070 Failsafe Timer The time for invalid measurements to elapse before Failsafe State activates. Primary Index Values Single Point Model Dual Point Model Global Transducer Range: 0 to 15 minutes Preset 10.00 minutes Altered by • P003 Maximum Process Speed Related • P129 Relay Failsafe Once activated, the Failsafe State initiates the following: 1. 2. The material level is reported based on P071 Failsafe Material Level.
Selecting HI, LO, or HOLd 1. Press FUNCTION 2. Press ARROWS 3. Press ENTER to display the Auxiliary Function symbol. to scroll to the desired option. to set the value. Entering a Measurement To enter a specific Failsafe Material Level within -50 to 150% of Span (P007), in Units (P005). Relay reaction The way in which relay programming reacts to the failsafe level depends on P129 Relay Failsafe (page 140). By default: • • Alarm relays have P129 = OFF and so react to the Failsafe Material Level.
Control Functions (P111) Each relay can be configured independently to take advantage of the MultiRanger’s advanced features and flexibility. Start with a preset application and then change the required parameters to make the task more efficient. Setpoints (P112, P113) Each relay is triggered by one or more setpoints. The setpoints can be based on absolute level (P112, P113) or rate of change (P702, P703). Each control function specifies which setpoints are required.
P110 Level Source Sets the level source on which the indexed relay is assigned to a measurement point. Please note that Difference and Average settings are MultiRanger 200 features.
MultiRanger 100 Values For P111 Control Type General OFF Level Loss of Echo (LOE) Cable Fault Pump Fixed Duty Assist Alternate Duty Assist Communication 1. #1 Relay Control 0* 1 6 7 Relay set off, no action (preset) Based on level setpoints ON and OFF When echo is lost When the circuit to a transducer is opened At fixed ON and OFF setpoints and allows multiple 50 pumps to run At rotating ON and OFF setpoints and allows multiple 52 pumps to run Based on input from external communications.
Values For P111 Control #1 Type Fixed Duty Assist 50 Fixed Duty Backup 51 Alternate Duty Assist Alternate Duty Backup Service Ratio Duty Assist Service Ratio Duty Backup First In First Out (FIFO) Pump 52 53 54 55 56 Flush Valve 64 Communication 65 Control 1.
P113 Relay OFF Setpoint Sets the process point at which the relay returns to its NORMAL state. Primary Index Values Relay Range: -999 to 9999 Preset: ---- Altered by • P007 Span Related • • • P100 Preset Applications P111 Relay Control Function P112 Relay ON Setpoint For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OFBOUNDS alarms, it is the low point in the specified range.
For IN-BOUNDS and OUT-OF-BOUNDS Relay Functions (P111 = 2 and 3 respectively), a dead band prevents relay chatter due to material level fluctuations at both the upper and lower setpoints. Actual ON or OFF setpoint Enter the dead band in either percent of span or units of measure (P005). The dead band value is applied both above and below the upper and lower bound setpoints as shown in the figure.
Positive Logic In software, all relays are programmed the same way, with ON setpoints indicating when to change the relay contact state (open or closed). This parameter allows the reversal of the operation so that relay contacts can be NORMALLY CLOSED or NORMALLY OPEN. P118 is preset to 2 which is positive logic. Negative Logic When P118 = 3 (negative logic), the operation for the indexed relay is reversed from normal.
The delay between pump starts is set by P132 Pump Start Delay. This only applies to any relays set to pump control (P111 = 50 to 56). Notes: • • All pump control relay ON and OFF setpoints must be the same value If the level is within 5% of Span (P007) of the OFF setpoint, the next pump is not started P122 Pump Service Ratio [MR 200] Selects pump usage based on the RUN time ratio rather than last used. Primary Index Values Related Relay Range: 0.000 to 9999 Preset: 20.
Relay Failsafe is only available for the following relay functions (P111) and is not used for any other relay control function. Relay Function (P111) Preset (P129) 1 – level alarm 2 – in bounds alarm 3 – out of bounds alarm OFF 4 – rate of change alarm 5 – temperature alarm 50 to 56 – all pump controls dE To select an independent Relay Failsafe value: 1. Press FUNCTION 2. 3. Press ARROWS to scroll through the failsafe options. Select option and press ENTER .
P131 Pump Run-On Duration [MR 200] Sets the number of seconds that the pump runs on. Primary Index Relay Range: 0.0 to 9999 Values Preset: 0.000 • Related Advanced Pump Control Modifiers (P130 to P136) Your pump capacity determines the amount of material that can be removed. Choose a value long enough to clean out the vessel bottom, yet short enough not to run the pump dry. Also be sure that this value does not overlap with P130 (Interval).
P136 Wall Cling Reduction [MR 200] Varies the upper and lower setpoints to reduce material buildup on the walls. Single Point Model Dual Point Model Primary Index Global Transducer Range: 0.000 to 9999 Values Preset: 0.000 This value is the range in which the setpoints are allowed to deviate in percent or units. The Relay Setpoints ON and OFF values are randomly varied inside the range to ensure that the material level does not consistently stop at the same point.
Flush Systems (P170 to P173) [MR 200] Please note that these parameters apply to the MultiRanger 200 only. Use this feature to control an electrically operated flush valve on a pump to divert some pump output back into the wet well to stir up sediment. Notes: • • If any of the following parameters are set to 0, this feature will not work. In Dual Point mode, a flush valve can be set up for each of the three available level inputs (P001 = 4 or 5).
P171 Flush Cycles [MR 200] Sets the number of pump cycles requiring flush control. Single Point Model Dual Point Model Primary Index Global Relay Range: 0 to 9999 Values Preset: 0 • Related P111 = 64, Flush Valve If three flush cycles are required after every ten pump cycles then: P172 (Flush Interval) = 10 P171 (Flush Cycles) = 3 P172 Flush Interval [MR 200] Sets the number of pump cycles before flush control is enabled.
mA Output (P200 to P219) P200 mA Output Range Determines the mA output range. Primary Index mA output 0 off 1 0 to 20 mA 2 Values 4 to 20 mA 3 20 to 0 mA 4 20 to 4 mA • Related * P911 mA Output Value If either 1 or 2 is selected, the mA output is directly proportional to the mA Function. If either 3 or 4 is selected, then the output is inversely proportional.
MultiRanger 200 Primary Index Values mA output value mA function Operation (P001) 0 OFF 1 level level, differential, or average 2 space space 3 distance distance 4 volume level or space 5 flow OCM 6 head 7 volume rate 8 mA input 9 comms input Related • • P202 mA Output Allocation P911 mA Output Value Altered By • P001 Operation P202 mA Output Allocation Sets the input source from which the mA output is calculated.
Enter the Point Number the mA output is based on. This value depends on whether mA function (P201) is set as transducer or mA input. For a single point device, if P201 uses a transducer, parameter P202 can only be altered if P001 (Operation) is set for DPD or DPA. P202 can be set to a particular point or range of points. When set to a range of points, the mA output will be the average of the readings from all in service transducers in the range. Out of service transducers will be ignored.
Independent mA Setpoints (P210 and P211) Use these features to reference the minimum and/or maximum mA output to any point in the measurement range. P201—mA Function Settings Action Level, Space, or Distance Enter the material level in Units (P005) or percent of Span (P007) as referenced to Empty (P006). Volume [MR 200] Enter the volume in Max Volume (P051) units or as a percent of Max Volume. Flow [MR 200] Enter the flowrate in OCM Max Flow (P604) units or as a percent of OCM Max Flow.
P212 mA Output Min Limit Sets the minimum mA output value (in mA) to be produced. Primary Index mA output Range: 0.000 to 22.00 Values Preset: 3.8 • • Related P200 mA Output Range P213 mA Output Max Limit P213 mA Output Max Limit Sets the maximum mA output value (in mA) to be produced. Primary Index mA output Range: 0.000 to 22.00 Values Preset: 20.
P215 20 mA Output Trim Calibrates the 20 mA output. Primary Index mA output Values Preset: 20.00 Related • P214 4mA Output Trim Adjust this value so the device indicates 20.00 mA when P215 is accessed. mA Output Failsafe (P219) [MR 200] Please note that this parameter applies to the MultiRanger 200 only. P219 mA Output Failsafe [MR 200] Use for failsafe operation, independent of the Failsafe Material Level (P071). Primary Index mA output Range: 0.000 to 22.
P250 mA Input Range [MR 200] Shows the mA input range of the connected mA device. Primary Index Global 1 Values 2 0 to 20 mA * 4 to 20 mA Ensure this range corresponds to the output range of the external device. All level measurements will equate % of Span with the % of the mA range. P251 0 or 4 mA Input Level [MR 200] Shows the process level corresponding to the 0 or 4 mA value.
P253 Input Filter Time Constant [MR 200] Shows the time constant used in the mA input filter to dampen signal fluctuations. Primary Index Global Range: 0 to 9999 Values Preset: 1 This number in seconds is used in the damping calculations. Larger values damp more than smaller values and 0 disables the signal filter. P254 Scaled mA Input Value [MR 200] Shows the resulting level value after scaling.
P270 Discrete Input Function Sets how discrete signals are interpreted by the MultiRanger. Primary Index Values Discrete input 0 Forced OFF 1 Forced ON 2 3 • Related * Normally Open – 0 (DI open), 1 (DI closed) Normally Closed – 0 (DI closed), 1 (DI open) Pump Control section P275 Scaled Discrete Input Value Shows the current value of the discrete input after any scaling is applied.
P300 Temperature, Transducer Maximum Shows the highest temperature encountered, as measured by the temperature sensor in the transducer (if applicable). Primary Index Transducer Range: - 50 to 150°C (view only) Values Preset: - 50°C • Related Press CLEAR P301 Temperature, Transducer Min keys to reset the log after a short circuit on the transducer wiring.
P303 Temperature, Sensor Minimum Shows the lowest temperature encountered, as measured by the TS-3 Temperature Sensor (if applicable). Global Primary Index Range: - 50 to 150°C (view only) Values Preset: 150°C • Related Press CLEAR P302 Temperature, Sensor Max keys to reset the log after an open circuit on the transducer wiring. Record Readings (P304 and P305) This identifies the occurrence of the record high and low level readings.
P309 Pump RUN Time Displays the amount of time in minutes since a relay was last activated. Primary Index Relay Values Range: 0 to 9999 minutes (view only) Related • Relay Function (P111) set for any pump control feature Parameter measures the length of time since a relay was asserted, most often to determine how long a pump has been running. Alternatively, it can monitor a relay to show how long it has been in a state of alarm. It resets every time the relay is activated.
Flow Records (P320 and P321) [MR 200] Please note that these parameters apply to the MultiRanger 200 only. These features are enabled if Operation is set for OCM (P001 = 6), or an OCM device is defined (P600 ≠ 0). Use them to identify the occurrence of the record high and low flow rates as displayed in OCM Max Flow (P604) units, or as a percent of OCM Max Flow. Press CLEAR keys to reset values once the installation is working correctly.
Totalizer units are dependent upon programming. Enter zero 0 (if required) to reset the totalizer to zero. Alternatively, enter any other (applicable) value, to preset the totalizer to the necessary value. Note: A second point is available only if the Dual Point Feature is enabled. P322 LCD Total Low [MR 200] View and/or alter the four least significant digits of the totalizer value. Single Point Model Dual Point Model Primary Index Global Values Range: 0.
P330 Profile Record Records profiles for later viewing.
P331 Auto Record Enable Use to enable/disable the Auto Profile Record function. Primary Index Global Range: 0 to 1 0 Values * Off 1 On P332 Auto Record Transducer Specifies the Transducer Point Number for which Auto Profile Records are saved. Please note that Differential and Average operation is a MultiRanger 200 feature.
Auto Record ON and OFF Setpoints (P334 to P337) Use Auto Record ON Setpoint (P334) and Auto Record OFF Setpoint (P335) to define the boundaries within which the level must be, for the resultant Echo Profile to be considered for an Auto Profile Record. If ---- is displayed for either P334 or P335, Auto Profile Records are saved regardless of current level (subject to all other restrictions). Enter the level value in Units (P005) or percent of Span (P007) as referenced to Empty (P006).
P336 Auto Record Filling / Emptying Use this feature to restrict Auto Profile Records from being saved unless the level is rising, falling or either.
Installation Records (P340 to P342) P340 Date of Manufacture View the date of manufacture of this MultiRanger unit. Primary Index Global Values Format: YY:MM:DD (view only) Related • • P340 Date of Manufacture P342 Start Ups P341 RUN Time View the number of days this MultiRanger has been in operation. Primary Index Global Values Range: 0.000 to 9999 (view only) Related • • P340 Date of Manufacture P342 Start Ups The RUN Time value is updated once a day, and cannot be reset.
Open Channel Monitoring (P600 to P621) [MR 200] Open Channel Monitoring (OCM) operation is a MultiRanger 200 feature only. If the MultiRanger is used to monitor open channel flow, alter the following parameters as required and run a calibration as described in P621. Note: See Open Channel Monitoring (OCM) on page 73 for application examples involving common weirs and flumes. The MultiRanger measures head as referenced to Empty (P006) or OCM Zero Offset (P605), when Operation is set for OCM (P001 = 6).
The MultiRanger is pre-programmed for common PMD flow calculations. If your PMD is not listed, select the appropriate Universal Flow Calculation. Associated parameters Max Head (P603), Max Flow (P604), and Min Head (P605) may be scroll accessed. If Operation is not set for OCM (P001 = 6), this value is preset to 0. If Operation is set for OCM, it is preset to 1. P601 Flow Exponent [MR 200] The Exponent for the flow calculation formula.
Example Exponents PMD Type Exponent (sample only) Suppressed Rectangular Weir 1.50 Cipolletti Weir 1.50 Venturi Flume 1.50 Parshall Flume 1.22 to 1.607 Leopold Lagco 1.547 V-Notch Weir 2.50 P602 Primary Measuring Device Dimensions [MR 200] The dimensions of the Primary Measuring Device (PMD).
P603 Maximum Head [MR 200] The level value associated with Maximum Flow, in Units (P005). Single Point Model Dual Point Model Primary Index Global Transducer Range: -999 to 9999 Values Preset: Span (P007) value Altered By • • P005 Units P600 Primary Measuring Device Related • • P604 Maximum Flow P605 Zero Head This represents the highest head level supported by the PMD and works in conjunction with Maximum Flow (P604) to define the highest point in the exponential curve.
Example Conditions Enter • • • • Flowrate display: millions of gallons/day, Maximum flowrate is 376,500,000 gallons/ day 376.5 for Maximum Flow (P604) and 4 for Time Units (P606). P605 Zero Head [MR 200] The distance above Empty (P006) in Units (P005) representing zero head (and zero flow). Single Point Model Dual Point Model Primary Index Global Transducer Range: -999 to 9999 Values Preset: 0.
P606 Time Units [MR 200] Determines the units used to display current flow and logging flow values. Single Point Model Primary Index Dual Point Model Global Values Transducer 1 seconds 2 minutes 3 hours 4 Alters • Altered By • * days P608 Flowrate Units This is used when the Primary Measuring Device is Ratiometric (P608=0). Example Conditions • • Enter Flowrate display: millions of gallons/day, • Maximum flowrate is 376,500,000 gallons/day • 376.
P608 Flowrate Units [MR 200] The volume units used to display total flow. Note: Set this parameter only when using BS-3680/ISO 4359 Rectangular Flume or BS-3680/ISO 1438/1 Thin Plate V-Notch Weir (P600 = 6 or 7). Use the default value of 0 for P608 when P600 = 1 to 5.
P610 Head Breakpoints [MR 200] The head breakpoints for which flowrate is known. See “Accessing a Secondary Index” on page 117 for more information.. Single Point Model Dual Point Model Primary Index Global Transducer Secondary Index Breakpoint Values Range: 0.000 to 9999 Related • P611 Breakpoint Flowrates The values in the Span for which flowrates are known. See Universal Calculation Support on page 83 for how to specify universal flows.
P620 Low Flow Cutoff [MR 200] Eliminates totalizer activity for flows at or below the cutoff value. Single Point Model Dual Point Model Primary Index Global Transducer Range: 0.000 to 9999 Values Preset = 5.000 %, or equivalent units Altered By • P005 Units Related • P007 Span Use this to enter the minimum head in units (P005) or as a percent of span. P621 Auto Zero Head [MR 200] Calibrates Zero Head (P605) based on actual head measurements.
Pumped Volume Totalizer (P622) [MR 200] The Pumped Volume Totalizer is a MultiRanger 200 feature only. If the eight-digit totalizer display or a remote totalizer contact closure are desired, alter the following parameters. P622 Inflow / Discharge Adjust [MR 200] The method used to calculate the volume pumped, for pumped total Operation (P001 = 7).
Totalizer (P630 to P645) [MR 200] The Totalizer features apply to MultiRanger 200 only. P630 LCD Totalized Multiplier [MR 200] Use this feature if the LCD Total increments by too large (or too small) an amount. Single Point Model Dual Point Model Primary Index Global Values Values Related Transducer -3 .001 -2 .01 -1 .
P633 LCD Totalized Decimal Position [MR 200] Enter the maximum number of decimal places to be displayed. Primary Index Single Point Model Global Transducer 0 Values no digits after the decimal point 1 1 digit after the decimal point 2 * 3 Related • Dual Point Model 2 digits after the decimal point 3 digits after the decimal point LCD Totalizer (P322 and P323) Note: Set the decimal position during initial commissioning of the MultiRanger 200.
Enter the factor (powers of 10 only) by which actual volume is divided, prior to Remote Totalizer count increment. Example: For a Remote Totalizer update by 1000s of volume units, enter 3. P641 Flow Sampler Mantissa [MR 200] Use this feature in conjunction with Flow Sampler Exponent (P642) to establish the number of flow units required to increment the Flow Sampler (device connected to the MultiRanger relay set for the flow sampler operation Relay Function, P111 = 41).
This parameter is relevant only if Operation is set to OCM (P001 = 6). Enter the exponent (Z) for the mantissa (Y) in the formula: Flow Sampler Increment = Y x 10Z Flow units. P645 Relay Duration [MR 200] Use this feature (if desired) to adjust the minimum contact closure duration of a relay set as a totalizer, flow sampler, time (control), or aeration (P111 = 40, 41, 60 or 62) Primary Index Global Range: 0.1 to 1024 Values Preset = 0.
P650 Offset Calibration Calibrates Empty (P006) if the reported level is consistently high or low by a fixed amount.
Using Sound Velocity Calibration Ensure a steady level at some low value (P653 and P654 adjusted accordingly) 1. Allow sufficient time for the vapor concentration to stabilize. 2. Press TRANSDUCER to display the calculated reading. 3. Repeat Step Two at least five times to verify repeatability. 4. Measure the actual reading (e.g. with a tape measure). 5. Enter the actual value.
P654 Velocity at 20°C This value is used to automatically calculate Sound Velocity (P653). Single Point Model Dual Point Model Primary Index Global Transducer Values Range: 50.0 to 2000.0 m/s (164 to 6562 ft/s) Related • • • P005 Units P651 Sound Velocity Calibration P653 Velocity After performing a Sound Velocity Calibration, check this value to verify the acoustic beam atmosphere is air (344.1 m/s or 1129 ft/s).
In gasses other than air, the temperature variation may not correspond with the speed of sound variation. In these cases turn off the temperature sensor and use a fixed temperature. P661 Temp Fixed Use this feature if a temperature sensing device is not used.
P664 Temperature View the transducer temperature in °C. Primary Index Transducer Values Range: -50 to 150 (view only) Altered By • P660 Temp Source Related • • • • P651 Sound Velocity Calibration P653 Velocity P654 Velocity at 20°C P661 Temp Fixed is pressed in RUN mode (see Readings in Run Mode on Value is displayed when page 23). If Temp Source (P660) is set to any value other than Fixed Temp, the value displayed is the temperature measured.
P701 Max Empty Rate Adjusts the MultiRanger response to decreases in the actual material level (or advance to a lower Failsafe Material Level, P071). Single Point Model Dual Point Model Primary Index Global Transducer Values Range: 0.000 to 99.00 m (or equivalent depending on units) Altered by • P003 Maximum Process Speed Related • • • P005 Units P007 Span P071 Failsafe Material Level Enter a value slightly greater than the maximum vessel emptying rate.
P703 Emptying Indicator The empty rate required to activate the LCD Emptying indicator ( ). Single Point Model Dual Point Model Primary Index Global Transducer Values Range: 0.000 to 99.00 m (or equivalent depending on units) Altered by • P003 Maximum Process Speed Related • • • P005 Units P007 Span P701 Max Empty Rate This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of the Max Empty Rate (P701). P704 Rate Filter Damps Rate Value (P707) fluctuations.
P705 Rate Update Time The time period (in seconds) over which the material level rate of change is averaged before Rate Value update. Single Point Model Dual Point Model Primary Index Global Values Range: 0.000 to 9999 Related • Transducer P707 Rate Value P706 Rate Update Distance The material level change (in metres) to initiate a Rate Value update. Single Point Model Dual Point Model Primary Index Global Values Range: 0.
P708 Volume Rate Display [MR 200] The rate of change of volume in percent of maximum volume per minute. Please note that this feature applies to the MultiRanger 200 only. Single Point Model Dual Point Model Primary Index Global Values Range: -999 to 9999 (view only) Related • Transducer P622 Inflow / Discharge Adjust This value is used internally to calculate inflow in pumped volume applications (P622=3). Press READING to toggle between percent and volume.
P711 Echo Lock Use this feature to select the measurement verification process. Single Point Model Dual Point Model Primary Index Global Values 0 Off 1 Maximum verification 2 3 Related Transducer • • • • • * Material agitator Total lock P700 Max Fill Rate P701 Max Empty Rate P712 Echo Lock Sampling P713 Echo Lock Window P820 Algorithm If a material agitator (mixer) is used in the vessel monitored, set Echo Lock for maximum verification or material agitator to avoid agitator blade detection.
P712 Echo Lock Sampling The sampling criterion sets the number of consecutive echoes appearing above or below the echo currently locked onto, that must occur before the measurements are validated as the new reading (for Echo Lock P711 values: 1 or 2).
The Echo Lock Window is a distance window (units P005) centred on the echo and used to derive the Reading. When a new measurement is in the window, it is re-centred and the new Reading calculated. Otherwise, the new measurement is verified by Echo Lock (P711) before the reading is updated. When 0 is entered the window is automatically calculated after each measurement. For slower P003 Maximum Process Speed values the window is narrow, for faster P003 values the window becomes wider.
P728 Shot Delay The delay, in seconds, between transducer shots. Primary Index Transducer Range: 0.1 to 4.0 Values Preset: 0.5 Use this if transient acoustic noise within the vessel is causing measurement difficulties due to echoes from one shot being received on the next. If more than one ultrasonic unit is installed for redundancy, this value should be 0. P729 Scan Time View the elapsed time (in seconds) since the point displayed was last scanned. Primary Index Level Values Range: 0.
If necessary, enter the Parameter Number to default in the Auxiliary Reading display. That value will show in the auxiliary reading area by default. Other values are available but will reset to the parameter defined here. P731 Auxiliary Reading Key Enter the Parameter Number whose value is to be displayed in the Auxiliary Reading field Primary Index Global Range: 000 to 999 Values Preset: Material Reading, P921 P is pressed in the RUN mode.
P735 Backlight Controls the LCD backlighting. Primary Index Global 0 1 Values Off * 2 On Keypad activated The backlight can be forced on or off, or be controlled by a programmer, in which case it will turn OFF 30 seconds after the last key is pressed. P737 Primary Reading [MR 200] The reading shown on the primary reading display when in RUN mode.
SmartLinx Reserved (P750 to P769) These parameters are reserved for optional SmartLinx communications cards and vary by card. Refer to the SmartLinx documentation to determine if any of them are used. Communications (P770 to P782) The MultiRanger communication ports are configured by a series of parameters that are indexed by port. See the Communications section on page 89 for a complete description of communications set-up.
P772 Baud Rate The communication rate with the master device. Communications Port Primary Index Values 4.8 4800 baud 9.6 9600 baud 19.2 * 19,200 baud (preset for port 2) 115.2 * 115,200 baud (preset for port 1) This specifies the rate of communication in Kbaud. Any value may be entered but only the values shown above are supported. The baud rate should reflect the speed of the connected hardware and protocol used. P773 Parity The serial port parity.
P775 Stop Bits The number of bits between the data bits. Primary Index Communications Port Range: 1 or 2 Values 1 * Preset: P778 Modem Available Sets the MultiRanger to use an external modem.. Primary Index Communications Port 0 Values * 1 No modem connected Answer only P779 Modem Inactivity Timeout Sets the time that the unit will keep the modem connected with no activity.
P782 Parameter Index Location Determines where index information is stored for the parameter access area.
P791 Hardware Error Code Indicates the precise cause of Fail or ERR1 condition from P790. Primary Index Global 0 Values No error 8 No SmartLinx card installed Any other value Error code; provide this code to your Siemens Milltronics representative for troubleshooting • Related * P790 Hardware Error P792 Hardware Error Count A count that increments by 1 each time Fail is reported in P790 (Hardware Error).
P799 Communications Control Enables the read/write access to parameters via remote communications. Primary Index Protocol (Index 1 controls the Modbus Master (RS-485 or RS-232); Index 2 controls the Fieldbus Master (PROFIBUS DP, DeviceNet, or Allen Bradley Remote I/O) 0 Read Only 1 Values * Read/Write Restricted Access – read only except for P799 which is read/write 2 Notes: • • P799 controls the lock access via communications. P000 controls the lock access via the Siemens handheld programmer.
P801 Range Extension Allows the material level to fall below the Empty setting without reporting LOE. Single Point Model Dual Point Model Primary Index Global Transducer Range: 0.000 to 99.00 m, or max.
P803 Shot / Pulse Mode Determines what type of ultrasonic shots are fired. Single Point Model Dual Point Model Primary Index Global Transducer 1 Values Short 2 • • • • Related * Short and long P006 Empty P805 Echo Confidence P804 Confidence Threshold P852 Short Shot Range Increases MultiRanger response when the monitored surface is close to the transducer face.
P805 Echo Confidence Displays the echo confidence of the measurement echo from the last shot. Primary Index Transducer Format: x:y (view only) x = short (0 to 99) Values y = long (0 to 99) • • Related P804 Confidence Threshold P830 TVT Type Use this feature to monitor the effect of transducer aiming, location, and mechanical transducer / mounting isolation. Both short and long shot Echo Confidence is displayed.
Advanced Echo Processing (P815 to P825) The following parameters are for authorized Siemens Milltronics Service personnel or technicians familiar with Siemens Milltronics echo processing techniques. P815 Echo Time Filtered The time (in ms) from the transmission of the pulse, to when it is processed. Primary Index Transducer Values Range: 0.0 to 9999 (view only) Related • P816 Echo Time Raw P816 Echo Time Raw The time (in ms) from the transmit pulse to the processed echo.
P820 Algorithm Chooses the algorithm to generate the measured value from the profile.
P821 Spike Filter Dampens spikes in the echo profile to reduce false readings. Single Point Model Dual Point Model Primary Index Global Transducer 0 Off Values 1 • • • • Related * On P820 Algorithm P822 Narrow Echo Filter P823 Reform Echo P825 Echo Marker Trigger Use P821 if interference spikes are on the long shot Echo Profile display. P822 Narrow Echo Filter Filters out echoes of a specific width.
P823 Reform Echo Smoothes jagged peaks in the echo profile. Single Point Model Dual Point Model Primary Index Global Transducer 0 = OFF (preset) Values greater = wider, nearest acceptable value returned • • • • • Related P002 Material P820 Algorithm P821 Spike Filter P822 Narrow Echo Filter P825 Echo Marker Trigger Use this feature, when monitoring solids (P002 = 2), if the reported level fluctuates slightly, though the monitored surface is still.
Advanced TVT Adjustment (P830 to P835) The following parameters are for authorized Siemens Milltronics Service personnel or technicians familiar with Siemens Milltronics echo processing techniques. Advanced TVT control applies to long shots only. P830 TVT Type Selects the TVT Curve used.
P832 TVT Shaper Adjust Allows manual adjustment of the TVT curve. Use this parameter in conjunction with Dolphin Plus PC Software. Single Point Model Dual Point Model Primary Index Breakpoint Transducer and Breakpoint Range: -50 to 50 Values Preset: 0 • Related P831 TVT Shaper Use this feature to bias the shape of the TVT curve to avoid selecting false echoes from fixed objects. Adjustment to this parameter is best done while viewing the echo profile with Dolphin Plus.
P834 TVT Start Duration Use this feature in conjunction with TVT Start Min (P833) to ignore false echoes (or pick up true echoes) near the start of the Echo Profile. Single Point Model Dual Point Model Primary Index Global Transducer Range: 0 to 9999 Values Preset: 30 • • Related P833 TVT Start Min P835 TVT Slope Min Enter the time (in ms) for the TVT Curve to decrease from the TVT Start Min (P833) point to the TVT Curve baseline.
P837 Auto False-Echo Suppression Use P837 and P838 together, to set MultiRanger 100/200 to ignore false echoes. Use P838 to set the Auto TVT distance first. Notes: • • • This function works best when the vessel is empty or nearly empty: use it only if there is a minimum distance of 2 meters from the transducer face to the material. Set P837 and P838 during start up, if possible. If the vessel contains an agitator, the agitator should be running.
P838 Auto False-Echo Suppression Distance Defines the range of Auto False-Echo Suppression (P837) to use for ignoring false echoes. (Units are defined in P005.) Values Range (depends on model) Maximum range: 0.000 to 15 m (50 ft) Default 1.000 m (3.28 ft) Determine the actual distance from the transducer face to the material surface. Subtract 0.5 m from this distance, and enter the result. Set Up: 1. Perform this function when the vessel is empty or nearly empty. 2.
Advanced Shot Adjustment (P840 to P852) These parameters are for Siemens Milltronics service personnel only. P840 Short Shot Number The number of short shots to be fired (and results averaged) per transmit pulse.
P842 Short Shot Frequency Adjust the short shot transmit pulse frequency (in kHz). Single Point Model Dual Point Model Primary Index Global Transducer Values Range: 41 to 46 kHz, nearest acceptable value is returned Altered By • P004 Transducer Related • • • • • P840 Short Shot Number P844 Short Shot Width P850 Short Shot Bias P851 Short Shot Floor P852 Short Shot Range This feature is automatically altered when Transducer (P004) is altered.
P845 Long Shot Width Adjust the width (in ms) of the long shot transmit pulse. Single Point Model Dual Point Model Primary Index Global Values Range: 0.000 to 5.000 Altered By • P004 Transducer Related • • • P841 Long Shot Number P844 Short Shot Width P843 Long Shot Frequency Transducer This feature is automatically altered when Transducer (P004) is altered.
P852 Short Shot Range Enter the maximum distance in Units (P005) to be measured using short shot echoes. Single Point Model Dual Point Model Primary Index Global Transducer Values Range: 0 to 10 m, or equivalent depending on units Altered By • P004 Transducer Related • • • • • P840 Short Shot Number P842 Short Shot Frequency P844 Short Shot Width P850 Short Shot Bias P851 Short Shot Floor This feature is automatically altered when Transducer (P004) is altered.
P902 Watchdog Press ENTER to put the CPU into an infinite loop to test the watchdog timer. On successful completion (10 seconds) the RUN mode is entered and the MultiRanger is reset. Programming is kept and the unit responds as if there had been a power failure. P903 Display Press ENTER to activate the display test. All LCD segments and symbols are temporarily displayed.
P908 Scanner Press ENTER to cycle the scanner relay while firing the transmitter. Use this parameter to ensure that both transducers are being stimulated. P910 Toggle Relays Used to energize and de-energize relays directly. Primary Index Global Values 0 to 6 Related • P119 mA Relay Logic Test Enter the relay number and then toggle between energized and de-energized, as required. Enter 0 to toggle all relays at once. Applies only to relays with P119 = 0 (algorithm control).
P913 Sensor Temperature Access this parameter to display the temperature in °C (as monitored by the TS-3). Primary Index Global Values Range: -50 to 150 OPEn is displayed if a TS-3 is not connected. P914 mA Input [MR 200] Use this feature to display the mA input value (in mA). Primary Index mA input Values Range: 0.000 to 24.00 Measurement (P920 to P927) All of these parameters are available in RUN mode and used to verify programming. See Readings in RUN Mode on page 23.
Reading Measurements by Operation P001 P050 = 0 P050 ≠ 0 0 – OFF ---- ---- 1 – Level P921 P924 2 – Space P922 100% - P924 3 – Distance P927 P927 4 – Difference [MR 200] P921 (indexed) P921 (indexed) 5 – Average [MR 200] P921 (indexed) P921 (indexed) 6 – OCM [MR 200] P925 P925 7 – Pump Totalizer [MR 200] P924 P924 P921 Material Measurement The distance in Units (P005) or % of Span (P007) between Empty (P006) and the monitored surface.
P924 Volume Measurement [MR 200] The calculated vessel capacity in Max Volume (P051) or % of Max Volume. Please note that Volume Measurement is a MultiRanger 200 feature only. Primary Index Level Values Range: 0.000 to 9999 (view only) Related • P051 Maximum Volume P925 Flow Measurement [MR 200] The calculated flowrate in Max Flow (P604) units or % of Max Flow. Please note that Flow Measurement is a MultiRanger 200 feature only.
P927 Distance Measurement The distance between the surface and the transducer face (displays only as % of Empty). Primary Index Transducer Values Range: 0.000 to 9999% (Displays as % of Empty) (view only) Related • • P005 Units P006 Empty Use P923 unless the distance information is required in percent. Master Reset (P999) This feature resets all parameters to original values. Single Point Model Dual Point Model Primary Index Global Transducer See below.
Parameters mmmmm Notes: Page 222 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
Global View only Name Description This parameter applies to the entire unit This parameter can not be set, only viewed Breakpoint Indexed by breakpoint Dimension Discrete Input Echo Profile Level Point1 mA input1 mA output1 Comm.
Appendix B: Technical Reference Appendix B: Tech Reference mmmmm Transmit Pulse The transmit pulse consists of one or more electrical “shot” pulses, which are supplied to the transducer connected to the MultiRanger terminals. The transducer fires an acoustic “shot” for each electrical pulse supplied. After each shot is fired, sufficient time is provided for echo (shot reflection) reception before the next (if applicable) shot is fired.
TVT (Time Varying Threshold) curves A TVT curve describes a threshold below which any echoes will be ignored. The default TVT curve is used, until P837 and P838 are used to create a new ’learned TVT curve’. Auto False-Echo Suppression False echoes can be caused by an obstruction in the beam path (pipes, ladders, chains, and such). Such false echoes may rise above the default TVT curve.
Distance Calculation To calculate the transducer to material level (object) distance, the transmission medium (atmosphere) sound velocity (P653) is multiplied by the acoustic transmission to reception time period. This result is divided by 2 to calculate the one way distance.
Scanning MultiRanger 100/200 When echo processing is complete (if more than 1 vessel is monitored) the scanning relay changes state to supply the transmit pulse to the other transducer after the Scan Delay (P727). MultiRanger 200 Volume Calculation [MR 200] Please note that the Volume Calculation feature is only available on the MultiRanger 200. The unit provides a variety of volume calculation features (P050 to P055).
Universal, Curved [MR 200] Please note that the Universal, Curved feature is only available on the MultiRanger 200. Set P050 = 10 Appendix B: Tech Reference mmmmm This calculation creates a cubic spline approximation of the level/volume curve, providing best results if the curve is non-linear, and there are no sharp angles.
Universal, Linear [MR 200] Please note that the Universal, Linear feature is only available on the MultiRanger 200. Set P600 = 4. This flow calculation creates a piece-wise linear approximation of the head/flow curve. This option provides best results if the curve has sharp angles joining relatively linear sections. Universal, Curved [MR 200] Please note that the Universal, Curved feature is only available on the MultiRanger 200.
For combination curves, enter at least 2 breakpoints immediately before and after any sharp angle (as well as 1 breakpoint exactly at the angle) on the curve. For more information, go to Typical Flow Characterization on page 83. Maximum Process Speed Appendix B: Tech Reference mmmmm The MultiRanger’s ability to respond to material level changes is designed to exceed even the most demanding installation requirements.
Appendix C: Troubleshooting Note: Many of the parameters and techniques described here require extensive knowledge of ultrasonic technologies and Siemens Milltronics echo processing software. Use this information with caution. If the setup becomes too confusing use P999 to reset and start again. Common Problems Chart Symptom Display blank, transducer No power. not pulsing. Cause No response to program- Obstructed infrared interface, mer. defective programmer.
Noise Problems Incorrect readings can be the result of noise problems, either acoustic or electrical, in the application. The noise present at the input to the ultrasonic receiver can be determined by viewing parameter P807. The display reads ##:##, where the first number is the average noise and the second is the peak noise. In general, the most useful value is the average noise. With no transducer attached the noise is under 5 dB. This is often called the noise floor.
Non-Transducer Noise Sources Remove all input and output cables from the MultiRanger individually while monitoring the noise. If removing a cable reduces the noise, that cable may be picking up noise from adjacent electrical equipment. Check that low voltage cables are not being run adjacent to high voltage cables or near to electrical noise generators such as variable speed drives. Filtering cables is an option but is not recommended unless all other options have been exhausted.
Measurement Difficulties If the Failsafe Timer (P070) expires due to a measurement difficulty, LOE flashes alternately with the last known Reading. In rare cases, the MultiRanger may lock on to a false echo and report a fixed or wrong reading. Flashing LOE Display The loss of echo (LOE) display appears when the echo confidence is below the threshold value set in P805 Echo Confidence. LOE occurs when: • • The echo is lost and no echo is shown above the ambient noise.
To display Echo Confidence in the RUN mode Press and hold for four seconds (Failsafe Time Left changes to the Short:Long Confidence display). To display Echo Confidence in the program mode, access the Echo Confidence (P805) parameter. To update the value displayed after each aiming adjustment.. Press (five times or more to verify stability and overcome any echo lock P711).
larger diameter or shorter length nozzle, bevel the inside of the bottom end, or cut the open end of the nozzle at a 45° angle. See the transducer manual for complete mounting instructions. For ST-series and XPS-10 transducers use the plastic conduit / flange adapter supplied with the unit. If the mounting hardware is over tightened, loosen it. Over tightening changes the resonance characteristics of the transducer and can cause problems.
If multiple echoes appear on the Echo Profile, typical of a flat material profile (especially if the vessel top is domed), use the “first” Algorithm. If the Echo Profile repeatedly switches from short to long, adjust the Short Shot Range (P852) to stabilize the “shot” mode used for the echo evaluation. Also, adjust the Short Shot Bias to increase (or decrease the amount of preference given to short shot echoes over long shot echoes.
Ring down times that extend past the near blanking area can be interpreted by the MultiRanger as the material level and are characterized by a steady high level being reported. Unit Repair and Excluded Liability All changes and repairs must be done by qualified personnel and applicable safety regulations must be followed. Please note the following: • • Appendix C: Troubleshooting mmmmm • • The user is responsible for all changes and repairs made to the device.
Appendix D: Pump Control Reference Please note that some pump control features apply to the MultiRanger 200 only. The MultiRanger has the pump control strategies to solve nearly any water / wastewater application. This section details these strategies for engineers requiring in-depth knowledge of the system and how it operates.
All of these algorithms can be used to start multiple pumps (assist) or one pump at a time (backup). The MultiRanger 100 and MultiRanger 200 have three main methods of pump control: Fixed Starts pumps based on individual setpoints and always starts the same pumps in the same sequence. Alternate Starts pumps based on the duty schedule and always leads with a new pump. Service Ratio Starts pumps based on user-defined ratio of running time.
The following table shows relay status when each setpoint is reached. Setpoints Relays Index On 3 On 2 On 1 Off 0 1 Off Off On Off 2 Off On Off Off 3 On Off Off Off Alternate Duty Assist (P111 = 52) Alternates the lead pump each time the material level cycles and runs all pumps together. Relay Operation (for P118 = 2) The setpoints associated with the relays are grouped so that they can be rotated. Setpoint one does not relate directly to relay one.
Relay Table Setpoints Cycle 1 Relays 1 Off Off On Off On 3 On 2 On 1 0ff 0 Setpoints Cycle 2 3 On Off Off Off Relays 1 On 3 On 2 On 1 Off 0 Cycle 3 Setpoints 2 Off On Off Off On Off Off Off 1 Off On Off Off On 3 On 2 On 1 Off 0 2 Off Off On Off Relays 2 On Off Off Off 3 Off On Off Off 3 Off Off On Off Service Ratio Duty Assist (P111 = 54) [MR 200] Selects the lead pump based on number of hours each pump has run and the specified ratios that each pump requires.
Service Ratio Duty Backup (P111 = 55) [MR 200] Selects the lead pump based on number of hours each pump has RUN and the specified ratios that each pump requires. Only one pump can RUN at a time. Please note that this feature applies to the MultiRanger 200 only. This algorithm is the same as Service Ratio Duty Assist except that it will only RUN one pump at a time. When the next pump in the sequence starts, the previous pump stops.
Flush Device (P170 to P173) Appendix D: Pump Control mmmmm Operates a flush valve or special flush device based on the number of pump starts, usually to aerate wet well wastewater.
Appendix E: Updating Software Updating Software To update the software in the MultiRanger, please contact your Siemens Milltronics representative to obtain the software. For a complete list of representatives, go to www.siemens.com/processautomation. WARNINGS: 1. All parameter values will be lost during software upgrade. Record your current parameters manually or using Dolphin Plus or SIMATIC PDM before upgrade. 2.
Appendix F: Upgrading mmmmm Appendix F: Upgrading The following procedure will assist you if you are upgrading from a MultiRanger Plus to a MultiRanger 100 or MultiRanger 200. If the application is unchanged, copy down the parameters in the MultiRanger Plus before de-commissioning the unit. Mounting a MultiRanger 100/200 Please read the MultiRanger Installation section on page 8 before mounting the new MultiRanger 100/200. Make sure the power is OFF to the unit before following these steps: 1. 2.
Connecting a transducer with RG62 coaxial extension cable RG62 coaxial cable has been used to make the extension. The level controller might be a MultiRanger Plus, HydroRanger, HydroRanger Plus or one of our other level controllers. Transducer MultiRanger 100/200 Installation (for retrofitting MultiRanger Plus Installations) Connect with a 0.1µF (100v or greater) capacitor (included with MultiRanger) between the shield and negative terminals.
Appendix F: Upgrading mmmmm MultiRanger Plus to MultiRanger 100/200 Parameters The MultiRanger 100/200 uses the current Siemens Milltronics standard parameter set which is different than the parameter numbers used in the MultiRanger Plus. The MultiRanger Plus parameters numbers are sequential (P-0 to P-99). The MultiRanger 100/200 parameters number are also sequential; however, some of the parameters are indexed. Parameters are indexed when they apply to more than one input or output.
7ML19981FBO6 MultiRanger 100/200 – INSTRUCTION MANUAL Page 249 0 2365031400 T. ADAM S. NGUYEN PETERBOROUGH R.
DISCRETE INPUTS Page 250 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FBO6 0 2365031400 T. ADAM S. NGUYEN PETERBOROUGH R. CLYSDALE 14/ AUG / 02 ULTRASONICS Product Group CERTIFIED TYCO ELECTRONICS MODULAR JACK 520425-2 (INSTALLED BY SIEMENS MILLTRONICS) CERTIFIED TYCO ELECTRONICS MODULAR PLUG 5-641335 (SUPPLIED BY CUSTOMER) 1.12” RICHCO DUAL LOCKING MINI NYLON STANDOFF (4 PLACES) 1.75”, 6-32 NYLON STANDOFF RPC NONE SN MAIN BOARD POWER SUPPLY BOARD 1.
Appendix H: Software Revision History MultiRanger 100 Software Rev. Date Changes • Pilot Release. 1.01 Sept. 21, 2005 • Internal Release. 1.02 Dec. 12, 2001 • Initial Release. 1.03 Aug. 27, 2002 • Clarified return message for factory RS232 test. Prevent entering of strings with invalid fields in Dolphin Plus. Properly convert ft/sec to m/sec in P654. Eliminated rogue watchdog resets from repeatedly pressing hand programmer enter while in P901-P90. Allow 32 bit read/write as seconds.
Software Rev. Date Changes 1.04 Feb. 11, 2003 • 1.05 Feb. 23, 2003 • • • • • • Appendix H: Software Rev. mmmmm • • • • 1.06 May 27, 2004 • 1.07 Aug. 30, 2004 • • • • • • Page 252 Product enhancements to eliminate relay chatter on software download. Improved functionality of receiver saturation during calibration. Added relay functionality through P118 to coincide with manual. Improved product security with addition of P069. Backup level override behaviour improvement.
Software Rev. 1.08 Date Nov. 11, 2004 Changes • • • • 1.09 Nov. 28, 2005 • • • not released 1.11 Apr. 20, 2006 • • • • 1.12 Aug. 15, 2008 • • • 7ML19981FB06 Software modified to support replacement component. Supports SIMATIC PDM version 6.02. Added support for true First echo processing algorithm Support for 3rd Point Volume has been added on P001 = DPA or DPD. Many parameter ranges improved to match product function and SIMATIC PDM.
MultiRanger 200 Software Rev. Date Changes 1.00 Nov. 09, 2001 • Pilot Release. 1.01 Dec. 02, 2001 • Initial Release. 1.02 Aug. 20, 2002 • P602 functions reduced point limit from 10 to 6. Changed P132 to global. P640 now accepts negative values. Changed access mode of dialer parameters so they cannot be scrolled. Clarified return message for factory RS232 test. Prevent entering strings with invalid fields in Dolphin Plus. Properly convert ft/sec to m/sec in P654.
Software Rev. Date Changes 1.04 Feb. 11, 2003 • 1.05 Feb. 21, 2003 • • • • • • • • • • • 1.07 Aug. 30, 2004 • • • • • • • • • 7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 255 mmmmm May 27, 2004 Appendix H: Software Rev. 1.06 Product enhancements to eliminate relay chatter on software download. Improved functionality of receiver saturation during calibration. Added relay functionality thru P118 to coincide with manual. Improved product security with addition of P069.
Software Rev. 1.08 Date Aug. 30, 2004 Changes • • • • 1.09 Nov. 28, 2005 • Appendix H: Software Rev. mmmmm • • • 1.10 not released 1.11 Apr. 20, 2006 • • • • 1.12 Aug. 01, 2006 • 1.13 Aug. 15, 2008 • • • • Page 256 Improvements made as a result of Siemens systems testing: SIMATIC PDM related: TVT display improvement to prevent it from going negative. MLFB number includes SMPI as well as Siemens numbering. Change of some enumerations in the Device Description.
Programming Charts Parameter # Name Altered Values for Indices/Point Numbers 1 2 3 Security P000 Lock (G) Quickstart P001 Operation P002 Material P003 Max. Process Speed P004 Transducer P005 Units (G) P006 Empty P007 Span Volume P050 Tank Shape P051 Max Volume P052 Tank Dimension A P053 Tank Dimension L P054 Level Breakpoints record values on a separate sheet. P055 Volume Breakpoints record values on a separate sheet.
Parameter # Name Altered Values for Indices/Point Numbers 1 2 3 P113 Relay OFF Setpoint P115 Relay Interval Setpoint [MR 200] P116 Deadband P118 Relay Output Logic P119 Relay Logic Test Pump Setpoint Modifiers P121 Pump by Rate [MR 200] P122 Pump Service Ratio [MR 200] Independent Relay Failsafe P129 Relay Failsafe Advanced Pump Control Modifiers P130 Pump Run-On Interval [MR 200] P131 Pump Run-On Duration [MR 200] P132 Pump Start Delay [MR 200] P133 Pump Power Resumption Delay [MR 200] P136 Wall Cli
Parameter # Name Altered Values for Indices/Point Numbers 1 2 3 P219 mA Output Failsafe[MR 200] mA Input P250 mA Input Range [MR 200] P251 0 to 4 mA Input Level [MR 200] P252 20 mA Input Level [MR 200] P253 Input Filter Time Constant [MR 200] P254 Scaled mA Input Value[MR 200] P260 mA Raw Input [MR 200] Discrete Input Functions P270 Discrete Input Function P275 Scaled Discrete Input Value Record Temperatures P300 Temp, Transducer max P301 Temp, Transducer min P302 Temperature, Sensor max P303 Tempera
Parameter # Name Altered Values for Indices/Point Numbers 1 2 3 P334 Auto Record ON Setpoint P335 Auto Record OFF Setpoint P336 Auto Record Filling/Emptying P337 Auto Record LOE Time Installation Records P340 Date of Manufacture P341 RUN Time P342 Start Ups Open Channel Monitoring P600 Primary Measuring Device [MR 200] P601 Flow Exponent [MR 200] P602 Primary Measuring Device Dimensions [MR200] P603 Maximum Head [MR 200] P604 Maximum Flow [MR 200] P605 Zero Head [MR 200] P606 Time Units [MR 200] P6
Parameter # Name Altered Values for Indices/Point Numbers 1 2 3 Range Calibration P650 Offset Calibration P651 Sound Velocity Calibration P652 Offset Correction P653 Velocity P654 Velocity @ 20° C Temperature Compensation P660 Temp Source P661 Temp Fixed P663 Temp Transducer Allocation P664 Temperature Rate P700 Max Fill Rate P701 Max Empty Rate P702 Filling Indicator P703 Emptying Indicator P704 Rate Filter P705 Rate Update Time P706 Rate Update Distance P707 Rate Value P708 Volume Rate Display [MR 20
Parameter # Name Altered Values for Indices/Point Numbers 1 2 3 P737 Primary Reading [MR 200] P741 Communications Timeout SmartLinx Reserved Communications P770 Port Protocol P771 Network Address P772 Baud Rate P773 Parity P774 Data Bits P775 Stop Bits P778 Modem Available P779 Modem Inactivity Timeout P782 Parameter Index Location SmartLinx Hardware Testing P790 Hardware Error P791 Hardware Error Code P792 Hardware Error Count P794 SmartLinx Module Type P795 SmartLinx Protocol P799 Communications Cont
Parameter # Name Altered Values for Indices/Point Numbers 1 2 3 P824 (reserved) P825 Echo Marker Trigger Advanced TVT Adjustment P830 TVT Type P831 TVT Shaper P832 TVT Shaper Adjust P833 TVT Start Min P834 TVT Start Duration P835 TVT Slope Min P837 Auto-False Echo Suppression P838 Auto-False Echo SuppressionDistance P839 TVT Hover Level Advanced Shot Adjustment P840 Short Shot Number P841 Long Shot Number P842 Short Shot Frequency P843 Long Shot Frequency P844 Short Shot Width P845 Long Shot Width P8
Parameter # Name Altered Values for Indices/Point Numbers 1 2 3 P920 Reading Measurement P921 Material Measurement P922 Space Measurement P923 Distance Measurement P924 Volume Measurement [MR 200] P925 Flow Measurement [MR 200] P926 Head Measurement [MR 200] P927 Distance Measurement Parameter Charts mmmmm P999 Master Reset Page 264 MultiRanger 100/200– INSTRUCTION MANUAL 7ML19981FB06
Index A D accuracy .............................................................4 adding new functions ................................. 245 alarm ................................................................ 54 bounded ................................................. 56 cable fault .............................................. 56 common parameters .......................... 54 emptying rate ....................................... 55 filling rate ...............................................
Leopold Lagco ...................................... 81 Palmer Bowlus ..................................... 77 Parshall ........................................... 80, 84 rectangular ............................................ 76 universal trapezoidal .......................... 84 flush valve ....................................................... 67 format words ................................................ 105 Frequency Input ........................................... 153 G global index method .....
Q quick start ........................................................38 R rake control .....................................................69 randomize setpoints ......................................66 range ...................................................................4 reading volume ....................................................51 recording profiles .........................................160 MultiRanger 100/200 – INSTRUCTION MANUAL Page 267 mmmmm 7ML19981FB06 totalizer .............
register map ................................................... 97 discrete inputs .................................... 100 input/output ........................................... 99 mA output ............................................ 100 map ID .................................................... 98 parameter access ............................. 102 parameter format words ................. 105 point data ............................................... 99 product ID ....................................
characterization chart ........................ 52 dimensions ............................................ 40 readings ................................................. 51 tank shape ............................................. 51 universal example ............................... 52 W wall cling ......................................................... 66 weight .................................................................6 weir Cipolletti ............................................... 167 standard .
Notes.
IQ300IX.
www.siemens.com/processautomation Siemens Milltronics Process Instruments Inc. 1954Technology Drive, P.O. Box 4225 Peterborough, ON, Canada K9J 7B1 Tel: (705) 745-2431 Fax: (705) 741-0466 Email: techpubs.smpi@siemens.com Siemens Milltronics Process Instruments Inc. 2009 Subject to change without prior notice *7ml19981FB06* Printed in Canada Rev. 6.