User's Manual

7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 141
mmmmm
Parameters
Relay Failsafe is only available for the following relay functions (P111) and is not used for
any other relay control function.
To select an independent Relay Failsafe value:
1. Press FUNCTION to display the Auxiliary Function symbol.
2. Press ARROWS to scroll through the failsafe options.
3. Select option and press ENTER .
Advanced Pump Control Modifiers (P130 to P137)
[MR 200]
Please note that these parameters apply to the MultiRanger 200 only.
These parameters only affect relays set to pump operation (P111 = 50 to 56).
P130 Pump Run-On Interval [MR 200]
Sets the number of hours between pump run-on occurrences.
To clear sediment in a pump-down wet well, run the pump after the normal OFF setpoint
is reached to force some solid material through. This parameter sets the time between
such events. Only the last pump running can run-on.
Relay Function (P111) Preset (P129)
1 – level alarm
OFF
2 – in bounds alarm
3 – out of bounds alarm
4 – rate of change alarm
5 – temperature alarm
50 to 56 – all pump controls dE
Primary Index Global
Values Range: 0.000 to 1000
Preset: 0.000
Related Advanced Pump Control Modifiers (P130 to P136)