User's Manual

Page 170 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Parameters
P606 Time Units [MR 200]
Determines the units used to display current flow and logging flow values.
This is used when the Primary Measuring Device is Ratiometric (P608=0).
Example
P607 Flowrate Decimal [MR 200]
The maximum number of decimal places to be displayed.
In RUN mode, the number of decimal places displayed is automatically adjusted (if
necessary) to prevent the number of Flowrate digits from exceeding display capabilities.
The maximum number of head decimal places is controlled by Decimal Position (P060).
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
1seconds
2minutes
3hours
4* days
Alters
Altered By P608 Flowrate Units
Conditions Enter
Flowrate display: millions of gallons/day,
Maximum flowrate is 376,500,000 gallons/day
376.5 for Maximum Flow (P604)
•and 4 for Time Units (P606).
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
0 no digits after the decimal point
1 1 digit after the decimal point
2 2 digits after the decimal point
3 3 digits after the decimal point
Altered By P060 Decimal Position