7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 179
mmmmm
Parameters
P650 Offset Calibration
Calibrates Empty (P006) if the reported level is consistently high or low by a fixed amount.
Before using this feature, verify the following parameters are correct:
•Empty (P006)
Temperature (P664)
Offset Reading (P062)
Zero Head Offset (P605), if using OCM
Offset Calibration
Begin with a steady level.
1. Press TRANSDUCER to display the calculated reading.
2. Repeat Step One at least five times to verify repeatability.
3. Measure the actual reading (use tape measure).
4. Enter the actual value.
The deviation between the entered Empty (P006) value and the calibrated Empty value is
stored in Offset Correction (P652).
P651 Sound Velocity Calibration
Changes the speed of sound constant.
Condition for use of this feature
The acoustic beam atmosphere is other than air
The acoustic beam atmosphere temperature is unknown
The Reading accuracy is acceptable at higher material levels only
For best results, calibrate with the level at a known value near empty.
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values Range: -999 to 9999
Related
P006 Empty
P062 Offset Reading
P605 Zero Head
P652 Offset Correction
P664 Temperature
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values Range: -999 to 9999
Related
P653 Velocity
P654 Velocity at 20°C