Page 190 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Parameters
The Echo Lock Window is a distance window (units P005) centred on the echo and used
to derive the Reading. When a new measurement is in the window, it is re-centred and
the new Reading calculated. Otherwise, the new measurement is verified by Echo Lock
(P711) before the reading is updated.
When 0 is entered the window is automatically calculated after each measurement. For
slower P003 Maximum Process Speed values the window is narrow, for faster P003
values the window becomes wider.
Transducer Scanning (P726 to P729)
P726 Level System Sync
Enables the System Sync on the terminal block.
Use this if another level measurement system is mounted nearby, and they are wired
together on the Sync terminal.
P727 Scan Delay
The delay, in seconds, between measurements from transducer points (dual point model
only).
This feature may only be used to adjust the delay before the next point is scanned. Enter
the amount of delay in seconds. This value is automatically altered when Maximum
Process Speed (P003) is altered.
Primary Index Global
Values
0not required
1 * synchronize level monitors
Primary Index Global
Values
Range: 0 to 60 seconds
Preset: 5.0
Altered by P003 Maximum Process Speed
Related •P001 Operation