eWON4002™ E t h e r n e t G a t e way Re m o t e A c c e s s S e r ve r ( R A S ) P r o g ra m m a b l e I n d u s t r i a l Rou t e r ( P I R ) Datalogger I n t e g ra t e d I n p u t / O u t p u t 3 s e r i a l Por t s INSTALLATION GUIDE Rev. 2.
eWON4002™ Installation Guide Table Of Contents 1 Product description ............................................................... 1 1.1 1.2 1.3 1.4 Introduction...............................................................................1 General specification of the hardware platform .........................1 Ethernet Gateway ......................................................................1 RAS Modem & PIR ......................................................................2 1.5 1.6 1.7 1.
eWON4002™ Installation Guide Table Of Contents 6.2 By phone line or GSM ...............................................................20 6.2.1 Under Windows 98, NT and 2000.................................................. 20 6.2.2 Under Windows XP ....................................................................... 21 7 IP parameters configuration................................................ 22 8 Technical support ................................................................ 23 8.1 Resets ......
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 1 Product description 1.1 Introduction The eWON4002™ is a compact version from a complete range of Ethernet/Internet gateways also known as “Programmable Industrial Routers” (PIR). See our web site http://www.ewon.biz to get further information about the eWON® range. The eWON® is a terminal that enables access to technical data, whatever their format is. The eWON® is configurable by means of web pages.
eWON4002™ In s ta l l a ti o n G u i d e 1.4 RAS Modem & PIR 1.4.1 Remote Access Server functions • Remote Access Server (RAS) and TCP/IP Server • PAP/CHAP Authentication • Login/password • Remote network access • User access control • Security: Integrated firewall (NAT, IP filtering, …) • Conventional and internet callback 1.4.2 Programmable Industrial Router functions • Automatic routing of protocols • Pre-configured routing tables • Programmable routing from I/O and Tag names (BASIC) 1.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 • cc= Communication: • 01 = NO modem (Ethernet only) • 02 = PSTN modem • 05 = GSM/GPRS modem • /xy = Options: The only option of the eWON4002™ is the modem type. Available Part Numbers for the eWON4002™ platform: Type/Description Part Number eWON4002™/Ethernet EW42201 eWON4002™/PSTN33 (PSTN modem) EW42202 eWON4002™/GSM/GPRS (GSM/GPRS modem) EW42205 Table 1: List of available Part Numbers 1.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 2 Structure of the eWON® technical documentation The eWON® technical documentation is structured in 4 different levels as shown in the table below: Level 1 Title Contents Hardware Installation Guide (the present document) (~40pp) Detailed description of the hardware platform, of its interfaces, available options and accessories. Hardware specifications, conformity to standards. Installation recommendations and connectors pinout.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 3 Housing and markings 3.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 3.2 Markings The identification label of the eWON® stands on the left hand side of the housing. The label is composed of the following fields: Serial number 0504 = year+week 0001 = sequential number 89 = suffix eWON4002™ COM type ../33.6 = PSTN modem at 33.6 kb ..
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 3.4 Equipment information and versions The eWON® hardware and software revisions can be checked via a web browser on the eWON® server (see Communicating with the eWON® on page 20). Once logged onto the eWON®, clicking on the eWON® logo shows these revisions: IP Address Software version Serial Number System Info (I/O, Modem, free memory) Figure 4: eWON® info page details 106 mm 3.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 Spring Bottom slider Figure 6: DIN-rail latch The eWON® must be fastened on a 35mm DIN rail compliant with EN50022. To put the unit in place, insert the bottom slider into the lower part of the rail, with the eWON® tiled around 20°. Then push the eWON® upward to compress the spring, and at the same time, put the unit right by rotating it. The eWON® is now safely fastened. 3.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 3.7 Preparing the installation The recommended free space in the cabinet for the eWON® on the wall for the eWON1002™ should be at least: 80mm wide X 225-mm high X 200-mm deep (terminal block excluded). A piece of rigid DIN-rail profile (flat 35mm wide) of suitable length should be firmly fastened, horizontally, in the middle of the area.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 .
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 5 Communication interfaces and I/Os 5.1 Ethernet Port Specification Value Applicable standard 10/100BaseTX Isolation 1,5 kV Pinout RJ45 connector See label and appendix (RJ45 connector on page 27) Table 5: Ethernet port specification Please refer to the appendix (Direct connection on page 25 and Connection over hub/router on page 26) for information on the different Ethernet connexion modes (straight and crossed cables). 5.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 5.3.1 Recommendations for the GSM/GPRS antenna A dual band GSM/GPRS antenna is available as accessory (ref EW40902).
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 5.4 Serial ports The eWON4002™ is provided with 3 serial ports, 2 of which (port 1 and port 3) are configurable (RS485, RS422, RS232), and one (port 2) is a full RS232 (with all control lines present). 5.4.
eWON4002™ In s ta l l a ti o n G u i d e Positions ve r 2 . 0 4 Mode OFF RS232 ON OFF RS422, RS485 WITHOUT polarisation and termination resistors ON OFF RS422, RS485 WITH polarisation and termination resistors ON Table 10: Serial mode configuration switches Note: the 3 switch configurations shown in the table above are the only configurations giving satisfactory results. Warning: The switch 2 is reserved and must stay OFF.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 5.4.3 Serial port #3 Specification Value Physical modes (configurable) RS232/RS485/RS422 Normal isolation NOT ISOLATED Pinout connector See label and appendix (Relays output on page 30) Termination/polarization Selectable Table 12: Serial port 3 specification The configuration of the physical serial port 3 mode is done by a set of 4 dip switches that are located on the bottom face from the unit.
eWON4002™ In s ta l l a ti o n G u i d e Positions ve r 2 . 0 4 Mode OFF RS232 ON OFF RS422, RS485 WITHOUT polarisation and termination resistors ON OFF RS422, RS485 WITH polarisation and termination resistors ON Table 13: Serial mode configuration switches Note: the 3 switch configurations shown in the table above are the only configurations giving satisfactory results. Warning: The switch 2 is reserved and must stay OFF.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 5.6 Digital Outputs There are 3 Digital Outputs: 1 open collector and 2 relays. 5.6.1 Open collector Digital Output The open collector output is located on the Input/Output connector, which stands beside the power supply connector.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 5.6.2 Relays The 2 relays are on the RL1-RL2 connector. Specification Value Number of outputs 2 Type of output SPST NO relays (Single Pole, Single Throw, Normally Open) Input voltage max 24 VDC/24 VAC Max current (external source) 1A Isolation 1 kV Pinout connector See label and appendix (Input/Outputs on page 28) 5.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 Note: pay attention to the fact that switch 1 configures AI4, switch 2 configures AI3, .... Specification Value Input range 0 to 10 VDC Number of inputs 4 Common points 1 Resolution 12 bits (5 mV) Precision 0.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 6 Communicating with the eWON® 6.1 By Ethernet 1 ) Plug one of the Ethernet cables [see appendix (Direct connection on page 25 and Connection over hub/ router on page 26)] between your eWON® and either your PC (crossed cable) or onto your network (straight cable). 2 ) Configure your Internet browser connection, in order not to use a proxy server (please have a look at your browser help file)..
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 • To configure the Ethernet IP address: , , , • To configure the PPP IP address: , , , 6.2.2 Under Windows XP 1 ) With Windows XP, you first have to go to Start and select Connect to and then Show all connections. Create a new connection appears in the network tasks box (top left corner).
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 7 IP parameters configuration Warning: parameters always have to be defined in full agreement with the network policies applicable within your organisation (ask your network administrator). The Ethernet port of the eWON® is configured in the factory with the following default parameters: • IP Address: 10.0.0.53 • Subnet mask: 255.255.255.0 • Gateway: 0.0.0.0 (none) Note: the default IP address for dial-up access (PPP) is different (202.0.0.240).
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 8 Technical support If you need technical support, simply fill out the form on the Web site http://www.ewon.biz or send an email with the problem description to support@ewon.biz. 8.1 Resets Warning: you should not reset your eWON® unless you have been told to do so by someone of our technical support. The concerned files (differs depending on reset type) are totally lost and unrecoverable after being formatted.
eWON4002™ In s ta l l a ti o n G u i d e 9 Appendix: Pinouts and connections 9.1 Power Supply Power supply connector Pin 2 Pin 1 Figure 14: Power supply mating female connector (included) • Power supply mating female connector (included): Manufacturer Phoenix Contact GmbH http://www.phoenixcontact.com MVSTBW2,5/4-STF-5.08 Part Number • Power supply connector pinout: Pin Description 1 Ground 2 Positive (+) Table 19: Power supply connector pinout page 24 of 35 ve r 2 .
eWON4002™ In s ta l l a ti o n G u i d e 9.2 Ethernet Ethernet connector The eWON® can be accessed by a 10/100BaseTX Ethernet connection. This connection can be made with two different cables (straight or crossed). These cables have 8 copper conductors and are known as UTP Class 5 with RJ45 terminations at both ends. These cables are availbale as spare parts (see External accessories on page 3). The type of cable (straight or crossed) depends on the equipment the eWON® will be connected to.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 When cabling over long distance, you have to take care of the twisted pairs. This means that along with the above cabling conventions, the emission (TX+/TX-) and reception (RX+/RX-) signals have to be connected on the same twisted pair: TX+: pin3, TX-: pin6 Twisted pair 1 RX+: pin1, RX-: pin2 Twisted pair 2 Pins 4, 5, 7 and 8 do not have to be connected. The following picture shows the twisted pair connections: Figure 15: Crossed cable cabling 9.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 9.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 9.4 Input/Outputs 9.4.1 DI / DO connector Digital Input/Output connector Pin 1 Pin 5 Figure 17: Digital Input/Output connector • Digital Input/Output mating female connector (included): Manufacturer: Sauro Part Number: CTF050VT http://www.sauro.
eWON4002™ In s ta l l a ti o n G u i d e 9.4.2 Analog Input Analog Input connector Figure 18: Analog Input connector • Analog Input mating female connector (included): Manufacturer: Phoenix Part Number: http://www.phoenixcontact.com MVSTBW2,5/9-STF-5.
eWON4002™ In s ta l l a ti o n G u i d e 9.4.3 Relays output RL1 RL2 Relay connector Figure 19: Relays Output connector • Relays Output mating female connector (included): Manufacturer: Phoenix Part Number: http://www.phoenixcontact.com MVSTBW2,5/4-STF-5.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 9.4.4 Digital input Top face Front face Back face DI8 DI1 Digital Input connector Figure 20: Digital Input connector • Digital Input mating female connector (included): Manufacturer: Phoenix Part Number: http://www.phoenixcontact.com MVSTBW2,5/10-STF-5.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 9.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 9.5.1 Pinout serial ports 1 and 3 (according to mode): Pin RS232 RS485 RS422 1 - - - 2 RXD - RX+ 3 TXD A+ TX+ 4 - - - 5 GND GND GND 6 - - - 7 RTS - RX- 8 CTS B- TX- 9 - - - Table 27: Serial ports 1 and 3 pinout 9.5.
eWON4002™ In s ta l l a ti o n G u i d e ve r 2 . 0 4 9.6 Unitelway/Modbus serial cable This 2m cable can be delivered as accessory to connect Schneider PLCs; It has a SUBD9 connector at the eWON® side and a MiniDIN connector at the PLC side.
eWON4002™ In s ta l l a ti o n G u i d e 9.7 PSTN phone line connector PSTN phone line connector Figure 23: PSTN phone line connector • PSTN phone line mating male connector (not included): Type RJ11 type "6P2C" without shield Figure 24: PSTN phone line mating male connector type • PSTN phone line mating male connector pinout: Pin Description 1 - 2 - 3 TIP 4 RING 5 - 6 Table 30: PSTN connector pinout page 35 of 35 ve r 2 .