Data Sheet for Product

s Industry, Inc.
Building Technologies Division
Specifications (continued)
The switch used for selecting the Candela setting is tamper resistant
When synchronization is required, the appliance is compatible with Siemens’ DSC Sync Modules; the
Siemens 50-point, 252-point and 504-point fire alarm control panels (FACPs), as well as with:
FireFinder® XLS and MXL® FACPs
PAD-3 or PAD-4™ NAC Extenders with built-in sync protocol
The strobes will not drift out of synchronization at any time during operation
The strobes will revert to a non-synchronized flash-rate, if the sync module or Power Supply
should fail to operate (i.e.
contacts remain closed)
The appliance is also designed so that the audible signal may be silenced while maintaining strobe
activation, when used with Siemens synchronization
The Series NHHorn and NSHorn/Strobes of appliances incorporates a Patented Universal Mounting
Plate that will allow mounting to a single-gang, double-gang, 4-inch square (10 cm), European type
backboxes, or the SHBBS Surface Backbox
For use where required, an NATP (Notification Appliance Trim Plate) is provided
All notification appliances are listed for Special Applications:
Strobes are designed to flash at 1-flash-per-second minimum over their “Regulated Input Voltage Range”
Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second, and ADA Guidelines
specify a flash rate of 1-to-3 flashes per second
All Candela ratings represent minimum-effective Strobe intensity, based on UL Standard 1971
The Series NSHorn/Strobe of appliances is UL Listed under UL Standard 1971 for indoor use
with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%)
The Series NH’ Horns of appliances is UL Listed under UL Standard 464 for audible signal appliances (Indoor use only)
Mounting Diagram
Mounting Options
(Shown In Inches)