Cerberus™ FIT OH110-R1, OP110-R1, HI110-R1, HI112-R1 Automatic Fire Detectors Automatic fire detectors for collective detector lines and conventional detector lines, 110 series ● ● ● ● ● ● A6V10450539_en--_e 2019-01-09 Signal processing with detection algorithms Selectable parameter sets LED indicator, 3 colors Drift compensation Internal error monitoring Error display Building Technologies Control Products and Systems
Properties Features ● Resistant to environmental and interfering influences such as dust, fibers, insects, moisture, extreme temperatures, electromagnetic interference, corrosive vapors, vibration ● Shock resistant, protection against sabotage ● Protected electronics, high-quality components ● Integrated alarm indicator (AI), located centrally, 360° visibility ● Up to 2 external alarm indicators type FDAI91/FDAI92/FDAI93 can be connected per detector ● Signal processing with detection algorithms ● Same dete
OP110-R smoke detector Smoke detector consisting of: ● Point detector ● Detector dust cap to protect the point detector during the construction phase Function: ● Functions according to the scattered light principle with one sensor, optical forward scattering ● Opto-electronic measuring chamber which obstructs disruptive extraneous light but provides excellent detection of smoke particles ● Selectable detection behavior thanks to two parameter sets – Parameter set 1: 'Standard' – Parameter set 2: 'Sensitive'
Type Overview Type Designation Order no. Weight [kg] OH110-R Multi-sensor fire detector (collective) S54372-F11-A2 0,144 OP110-R Smoke detector (collective) S54372-F4-A2 0.138 HI110-R Heat detector (static and differential, collective) S54372-F9-A2 0.130 HI112-R Heat detector (static only, collective) S54372-F10-A2 0.130 DB110 Detector base (collective) S54372-F5-A1 0,052 DB110D Detector base for BS 5839-1 S54372-F6-A1 0.100 DB110R Detector base (collective) S54372-F7-A1 0.
Accessories Detector base DB110 (parameter set 1) Function: ● Universal base for all point detectors of the 110 and OOH740 series ● Selects parameter set 1 within the point detector Use: ● For recess-mounted supply lines ● For surface-mounted supply lines with cables up to max.
Detector base seal RS720 ● ● For achieving a higher IP protection category Mounted between detector base and ceiling Detector locking device LP720 ● ● ● For protection against theft of the point detector Set screw M3 x 12 mm prevents the point detector being unscrewed from the detector base Point detector can only be removed with the appropriate Allen key Base attachment BA720 Function: ● For routing surface-mounted ducts (max. 20 mm) and cable ducts (max.
Designation plate DBZ1193A ● ● For labeling with the location address Can only be used with base attachment wet BA721 Detector heating unit FDBH291 ● ● ● ● For operating point detectors in critical ambient conditions during icy conditions or when there is a danger of moisture condensation. Examples of application: Cold stores, attics, loading ramps, cheese cellars Optimum function is only guaranteed in conjunction with base attachment wet BA721.
Notes Installation ● ● ● ● ● Universal detector base with two break-out points for surface-mounted cable entry at the side. Max. cable diameter: 8 mm. Extra-long mounting slits allow existing drill holes from other systems to be reused. Hole spacing 40…90 mm Connection terminals for conductors up to 2.
Technical data OH110-R OP110-R HI110-R / HI112-R Operating voltage DC 16…28 V DC 16…28 V DC 16…28 V Operating current (quiescent) Max. 100 μA Max. 100 μA Max. 100 μA 2 2 2 Operating temperature -10…50 °C -10…55 °C -10…50 °C (HI110-R) -10…50 °C (HI112-R, A2S) -10…65 °C (HI112-R, B) Storage temperature -30…70 °C -30…70 °C -30…70 °C Air humidity (short-term moisture condensation permitted) < 96 % rel. < 96 % rel. < 96 % rel.
Dimensional drawings OH110-R OP110-R 105 HI110-R / HI112-R 40 51 34 45 105 OH110-R with base OP110-R with base 117 0786 117 62 56 62 117 12 HI110-R / HI112-R with base Siemens Schweiz AG, Theilerstrasse 1a CH-6300 Zug Technical data: see doc. A6V10316298 OH110 - Point type smoke detector for use in fire detection and fire alarm systems installed in buildings.