User Manual
1/3
Building Technologies 08-05-905 E
Fire Safety & Security Products
Orifice plate ENGLISH
08-05-905
PED-category: SEP Index Description Date
Fluid group: 2 01.10.09
Product line
Sinorix ™
CX ref. no.
854005
SAP
S54476-B26-A1
Double nipple with filter
PN240
97/23/EG
Usage
H20 Gas 300
®
: 1-n water cylinders, if H2O orifice is drilled < 3.0mm
This part has to be used when the next part in flow direction has a drilling diameter smaller than 3.0mm.
It is installed with HP joints or HP hose. The part has a coaxial hole. The direction of flow is defined and stamped.
On the inlet side a filter is fixed.
Technical data
working pressure 240 bar
test pressure 360 bar
operating temperature range -20°C / +50°C
serial no week/year
material steel EN10027-2: grade 1.4305
orifice diameter range A 7.2 mm
inlet DKOS16
outlet G 1/2
weight 0.20 kg
Safety warning
This product information is exclusively intended for specialized operators with the experience in designing,
mounting, installing, commissioning, maintaining and retrofitting fire extinguishing systems. The user must ensure
that the part is not abused an only used within its design limits and that all danger to life and limb of the operator,
or third parties, is avoided. Moreover, compliance must be ensured with accident prevention regulations and
national regulations. The user must also ensure that all persons the equipment have read and understood these
product information.
direction of flow