User Manual
1/5
Building Technologies 08-01-930 E.doc
Fire Safety & Security Products
Orifice plate ENGLISH
08-01-930
PED-category: I
Orifice / restrictor,
2″, 300 bar Sycces
ORIF-360 50
Index Description Date
Fluid group: 2 01.10.06
Product line
Sinorix ™
CX ref. no.
3655099
G306003
SAP
S54476-B65-A4
97/23/EG
75
16
øA
Usage
The orifice plate must be used for pressure reduction in Sinorix ™ extinguishing systems only. It is installed
between orifice plate holders fitted to the end of the manifold to reduce the pressure developed in the distribution
pipework from the cylinder pressure (300 bar) to the calculated pipe pressure (normally 60 bar).
Technical data
working pressure 360bar
bursting pressure 1080bar
operating temperature range -20°C / +50°C
serial no week/year
weight 0.3 kg
material steel EN10027-2: grade 1.4305
Orifice diameter range
orifice holder inlet side orifice holder outlet side orifice diameter range A
2″ 1¼″ 3 … 27.5 mm
2″ 1½″ 3 … 31.5 mm
2″ 2″ 3 … 41.0 mm
2″ 2½″ 3 … 43.5 mm
2″ 3″ 3 … 43.5 mm
direction of flow