User Manual

1/4
Building Technologies 08-05-930 E
Fire Safety & Security Products
Orifice plate ENGLISH
08-05-930
PED-category: SEP
Pressure reduction device
ORIF-360 G3/4 F
Index Description Date
Fluid group: 2 01.02.09
Product line
Sinorix ™
a usage 01.06.18
CX ref. no.
3854005
G319006
SAP
S54476-B176-A1
97/23/EG
Usage
· Sinorix™ H20 Gas 300:
1-n water cylinders, drilling 0.5-3.0mm
It allows to turn the high pressure of the N2 cylinders (300bar@15°C) into low pressure in order
to squeeze the water stored in the water cylinders.
· Sinorix™ fixed Ar, N2, IG55 and IG541 300 bar high pressure fire extinguishing systems:
1cylinder projects unregulated, drilling 0.5-3.0mm
It allows to turn the high pressure of the inert gas cylinders (300bar@15°C) into low pressure in
order to bring the agent via pipe network to the nozzles.
On the inlet side a filter is fixed.
The direction of flow is defined and stamped.
The drilling has to be according the specific hydraulic calculation.
The drilling diameter is also stamped and good visible from outside
Technical data
working pressure 360 bar
test pressure 540 bar
operating temperature range -20°C / +50°C
serial no week/year
material steel EN10027-2: grade 1.4305
orifice diameter range A 0.5 … 3.0 mm
inlet DKOS20
outlet G 3/4
weight 0.20 kg
direction of flow