Data Sheet for Product

OSID Imagers
1177
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
VESDA Series
Open-Area Smoke-Imaging Detection (OSID) Imager
Models OSE-HPW, OSE-SP, OSE-SPW, OSI-10, OSI-90,
OSID-INST, OSP-001, OSP-002, and VKT-301
Product Overview Advantages for OSID detection
Open-Area Smoke Imaging Detection (OSID) from
Siemens
Fire Safety is the latest in projected beam /
smoke detection. Basically, OSID is used to replace
the traditional transmitter, receiver (or any
transmitter / receiver combination) and reflector in a
one-for-one arrangement. The most common
application consists of one (1) imager and one (1)
emitter. NFPA 72 rules for beam-detector spacing
also apply to OSID usage.
The OSID series of detectors measures the level of
smoke entering beams of light, projected over an area
of protection. Each OSID imager can detect up to six
(6) emitters, providing a wide coverage area.
Additionally, the OSID series of detectors, through its
use of advanced, dual-wavelength projected beams
and optical-imaging technology, provides a low-cost,
reliable and easy-to-install solution that overcomes
typical beam-detection issues, such as false alarm
incidents and alignment difficulties.
As mentioned, two (2) innovations in smoke
detection technology have been developed for the
OSID series of detectors: dual-wavelength particle
detection and optical imaging.
For dual-wavelength particle detection, the beam
projected from each emitter contains a distinctive
sequence of ultraviolet (UV) and infrared (
IR) pulses
that synchronize with the respective imager, thus
enabling the rejection of any unwanted light sources.
Moreover, the dual-wavelength process allows
each OSID detector to decipher particle sizes, via
the use of two (2) wavelengths of light to detect
particles. The shorter UV wavelength interacts
strongly with small and large particles, while the
longer
IR wavelength is affected only by larger
particles.
ARCHITECT AND ENGINEER SPECIFICATIONS
Conventional alarm interface for precise
integration with Siemens
Fire Safety
fire-alarm control panels (FACPs)
Two (2) model-types available:
Imager for 7° coverage
o {7° has highest detection range: > 450 ft. / 137.2m}
Imager for 80° coverage
High false-alarm immunity
Dust and intrusive solid object rejection
Easy alignment with large adjustment and
viewing angles
Status light-emitting diode (LED) indicators for
Power ON; Alarm / Trouble-event commands
Automatic commissioning of < 10 minutes
Tolerant of alignment drift
No need for precise alignment
DIP switch configuration
Simple, basic maintenance requirements
Three (3) selectable alarm thresholds
UL268 Listed, ULC-S529 Listed