Commissioning Instructions

46 / 184
Siemens Web server OZW772... V8.0 CE1C5701en
Building Technologies Commissioning 2018-03-15
2.10 Supply state
The web server can be reset to factory default settings. This is probably a good
idea when using the web server for another plant.
Procedure:
1. Simultaneously press "Long" (> 6 seconds) on the "Remote" button
and "Prog"
The LED "On" turns off. The web server restarts.
2. Wait until the web server is operational (LED "Run" is green).
When restoring default state:
All settings are reset to default state.
Plant diagrams are deleted.
The device list is deleted.
Uploaded files are deleted.
Unsent messages are deleted.
History data is not deleted:
It must be deleted manually (see Section 2.8).
The KNX device addresses and Ethernet IP address are also reset to default state.
Restore default state
Note
Note