5 701 s Web server TM TM For Synco , Synco OZW772... V8.0 living Web server OZW772… allows for remote plant control and monitoring via the web and Smartphone App. Four versions of the web server OZW772... are available: To connect 1, 4, 16, or 250 Synco devices from product ranges Synco 700, room controllers RXB/RXL, RDG/RDF/RDU room thermostats, and the QAX9… Synco living central apartment units. • Operate web browser via PC/laptop or Smartphone.
• Function "Energy indicator" for monitoring data points for energy-technical limit values, so-called “Green limits", and sending them to 2 e-mail recipients • Web services for external applications via Web API (Web Application Programming Interface) • Encrypted with https and TLS for e-mails. • ACS790 functionality. • Secure tunnel connection for ACS and ETS via portal • Time sync via NTP network time server Use Building • • • • Owners/operators • End customers, HVAC and electrical installers.
Web interface The web server interface is the same using the portal or via a direct connection. The portal has, however, additional functions and available settings. User interface portal to open the web server user interface under a new tab and is Click the symbol then the same as the view under a direct connection. The portal symbol and user name.
Primary navigation Primary navigation offers the following functions: Home Energy indicator Faults File transfer User accounts Device web pages Menu-based plant and device operation. Display and operating of "Energy indicator" data points (Displayed only if a controller is connected with an Energy indicator) Display system faults. Create and manage trend functions Download consumption data and message history, upload documents, logos, and system definitions as well as firmware update User administration.
Time The web server has a system clock with adjustable time zone and daylight saving/ standard time changeover. As clock time master, it can send the set system time (date and time) to KNX devices (clock time slave). For the system clock, the NTP network time server can perform the time synchronization and, if used as a time clock master, forward the data to all KNX devices (time clock slaves).
Example Plant web pages for heating plant Example Plant web pages for HVAC and lighting, blinds Download plant diagrams You can download web-capable plant diagrams from the HIT online platform for standard applications on Synco 700 devices, room controllers RXB/ RXL, and room thermostats RDG/RDF/RDU. Create own plant web pages You can freely design plant web pages. As a hybrid form, you can also modify and extend downloaded plant diagrams.
KNX S-Mode Integration of KNX S-Mode data points permits central control of heating, ventilation, air conditioning, and electrical installations. Data points recording by OZW can be used, for example, for trending, to depict the plant diagram or reused for thermal or electrical energy consumption. Number of S-Mode data points Version OZW772.01 supports 7 standard data points for system time and alarm info functions. For version OZW772.
Trend function The trend function can be defined directly in the web server OZW772… as of version 5.0. Any number of data points for connected devices can be logged at a selectable sample rate and queried using the trend function. Data points for devices integrated via KNX S-Mode are also available for the trend function. Trend channels 5 trend channels are available: Each trend channel can include up to 100 data points. The trend channel can be labeled using a plain text name.
Trend graph The data for a trend channel can be graphically displayed on the web user interface. The function is available for OZW772… as of version 6.0. Data transmission per e-mail Up to 2 e-mail recipients can be defined for the trend data. Each trend channel can send its data to one or both e-mail recipients. The send interval can be set individually for each trend. Import/Export Trend definitions can be imported to the web server or exported from the web server.
Consumption data trending The "consumption trend" function is available in web server OZW772… as of version 3.0. The following devices are supported: • Synco 700: RMU7x0B, RMH760B, RMK770 (as of version 2.0), RMS705, RMS705B, RMB795, RMB795B • Synco living: Central apartment unit QAX903, QAX913 OZW772... as of version 5.0 Energy and volume meters that use KNX data points are supported with the integration of KNX S-Mode as of web server version 5.0.
Function "Energy indicator" The "Energy indicator" function is available in web server OZW772… as of version 4.0. The following devices are supported: • Synco 700: RMS705B, RMU7x0B, RMH760B, RMK770 (as of version 2.0), RMB795B Central apartment unit QAX903, QAX913, QAX910 (as of version 3.
Web services The "Web Application Programming Interface" (Web API) is an interface to provide web services client to the web server. All web API functions are started via "http" or encrypted with "https". Each session starts with authentication at the web server. If "Home Control IC” App is installed on a smartphone, the app accesses, using the web services, via web API, data points for devices on the KNX network (Communication connection for smartphone, see page 14).
Equipment combinations The following Synco devices can be connected to the web server OZW772... Synco range Synco devices Universal controllers Heating controllers Boiler sequence controllers Central control units Switching & monitoring units Bus operator unit Room unit Central communication unit RMU7x0, RMU7x0B RMH760, RMH760B RMK770, RMK770 V2 RMB795, RMB795B RMS705, RMS705B RMZ792 QAW740 OZW771, OZW775 Data sheet no.
Technical design Web browser Devices PC/Laptop (1024 x 786) Requirements html5 compatible web browser. Smartphone Specific for device Number of browsers Any number of browsers can be used simultaneously. The maximum data throughput rate is distributed among the browsers. Operation slows down as the number of users increases accordingly. Operation, monitoring, alarming Communication connections for local commissioning (USB) and remote operation, remote monitoring and alarming via Ethernet.
Interfaces USB The USB interface directly connects the PC/laptop on site. The required USB cable type A – type Mini-B is delivered with the device. Ethernet The router/network is connected to the Ethernet RJ45 plug. The Ethernet interface features Auto-MDI(X) for crossed and non-crossed Ethernet cables. An Ethernet category 5 cable is supplied. KNX The KNX bus is connected to the CE+ and CE− connection terminals labeled "KNX". See data sheet N3127 for more information on the KNX bus.
Execution Basic design The web server consists of a housing lower section containing printed circuit boards with interfaces. The upper housing section covers the printed circuit boards. The upper housing section contains the LED displays and one operating button. The connection terminals and additional display and operating elements are located under the removable cover for the upper housing section. All display and operating elements are labeled.
Button combinations and • Long (> 6 s) Simultaneously press and restores default factory settings. All configuration data and settings are reset. The device list, plant diagrams, and unsent messages are deleted. History data is not deleted. Notes Mounting The Web server can be mounted in a panel, distribution box, or on a wall. Include space for wiring when planning. Make sure service can easily access the unit and the unit is ventilated properly.
Commissioning Connections Web-Server is commissioned directly via the portal with a PC/Laptop. A web browser required on the PC/Laptop. The web server can be commissioned locally via USB or with ACS790. The supplied USB cable type A – Type Mini-B connects the web server to the PC/laptop. Additional information is available in the included Mounting instructions M5701 or Installation guide G5701 and Commissioning guide C5701 at the Download Center at http://www.siemens.com/ozw772-manual.
User groups User accounts are created and assigned to specific user groups for customized user operation. End user • Access to end-user data and fault overview. • Operate and monitor via menu tree and plant diagrams. • Administer own user accounts. Service Same as end user. In addition: • Access service data. • Create, download, and manage trend data • Download consumption data and message history. • Upload customized logos and documents. • System definitions update.
Technical data Power cable for web server OZW772... Web server OZW772… Function data KNX bus USB Ethernet Directives and standards Environmental compatibility Degree of protection Operating voltage Rated voltage "Euro plug" AC 230 V ±15 % AC 230 V EN 50075 and VDE 0620-1 Frequency 50 / 60 Hz Power consumption (including web server OZW772...) 3 VA typical Protection class II Output voltage SELV 24 VDC Fusing of supply lines Max.
Degree of protection Degree of protection IP30 to EN 60529. Protection class III as per EN 60950-1. Ambient conditions Operation Climatic conditions Temperature (housing with electronics) Humidity Mechanical conditions IEC 60721-3-3 Class 3K5 0 …50 °C 5…95% r. h. (non-condensing) Class 3M2 Transport Climatic conditions Temperature Humidity Mechanical conditions IEC 60721-3-2 Class 2K3 −25...+70 °C < 95% r.h.
Connection diagrams Connection diagram KNX connection terminals Pin assignment DC 24 V plug 1 2 24 VDC (+) GND (–) Dimensions Published by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd 2018 Delivery and technical specifications subject to change 22 / 22 Siemens Building Technologies Web Server OZW772... V8.