Commissioning Instructions

35 / 188
Siemens Web server OZW772.. V9.0 CE1C5701en
Building Technologies Commissioning 2018-10-15
2.5.3.5 System report
Path: Home > 0.2.150 OZW772.xx > Settings > System report
Enter these settings if the web server is to regularly send an e-mail for a fault.
Data point
Explanation, example
Signal time
Default val: 06:00 hh:mm
Setting val: 00:00...23:59
The setting value corresponds to the time of
day when a system report is sent (once every
24 hours).
Message cycle
Default val: 1 d (day)
Setting val: 0...255 d
The setting value corresponds to the interval
(in days) at which a system report is sent.
The first system report is delivered after
completion of the first message cycle and then
as per the message cycle.
The system report is disabled when the
message cycle = 0.
Priority
Default val: Urgent
Setting val: Urgent /
Not urgent
Filter for sending the system report.
Under the setting urgent, the system report is
sent to all message receivers. Under the
setting not urgent, the message receives are
excluded who have only subscribed to "Urgent
only" messages.
Next report
Default val: 0 d (day)
Setting val: 0...255 d
Waiting period until the next system report is
sent.
Note