Commissioning Instructions

59 / 188
Siemens Web server OZW772.. V9.0 CE1C5701en
Building Technologies Remote access via Synco IC portal 2018-10-15
Connect with ETS as follows:
1. Select “New connection” menu in ETS
2. Select connection type “KNXnet/IP”
3. Enter the local IP address as per Remote Tool Access (e.g. 127.0.0.1)
4. Confirm with “OK”
3.4 Remote access via OZW gateway
Web server OZW772.. can also be used as a gateway for remote operation of the
M-bus web server WTV676-HB6035 in Climatix IC or Synco IC. Before accessing
the M-bus web server, you must register in Climatix IC or Synco IC and configure
and activate the OZW gateway. You can no longer access the OZW web page via
the portal once the OZW gateway is activated.
Remote operation of the M-bus web server anywhere at any time
Central management of multiple plants (M-bus web server and OZW) over a
common account in Climatix IC or Synco IC
Direct access to the web view of the M-bus web server and the OZW over the
portal
You must register in Climatix IC or Synco IC and configure and activate the OZW
gateway before you can access the M-bus web server.
Additional information configuring and activating the OZW gateway is available
below in this section.
Additional information on Synco IC is also available in the user guide "Synco IC:
Cloud and remote access for OZW772 and OZW672, cloud access for WTV676",
document A6V10500249.
You can access the web page for the M-bus web server in Climatix IC or Synco IC
as soon as the gateway is activated. Go to the "Operation" menu and select a web
server. Open the registration page for the M-bus web server in the menu “Web
access" and log in.