Commissioning Instructions

9 / 188
Siemens Web server OZW772.. V9.0 CE1C5701en
Building Technologies Overview 2018-10-15
1.2 Web server display and operating elements
Pos
Designation
1 LED Operation, Synco IC portal
connection display and "Energy
indicator"
2
LED
3
No function
4
LED fault
5
LED addressing mode
6
Remote button
7
Addressing mode button
Off No operating voltage DC 24 V
Steady red Web server starts operating system
Flashing red Web server starts application
Steady green Web server operational, "Energy indicator" = "Green
leaf"
Steady orange Web server operational, "Energy indicator" =
"Orange leaf"
Flashing Web server operational, connected to Synco IC portal
green / orange (LED 0.8 s on, 0.2 s off)
Off No bus power
On KNX operational
Flashing Communication on KNX
Dark No function
Off No fault (normal operating state)
On Acknowledged fault
Flashing Unacknowledged fault
Dark KNX addressing mode off
Off KNX addressing mode o
Short (< 2 s) Acknowledges fault message
Long (> 6 s) Sends system report to fault e-mail
Receivers
(not to consumption data and "Energy indicator" Receivers)
Short (< 2 s) Press once: KNX addressing mode on
Press again: KNX addressing mode off
Long (> 6 s) Simultaneously pressing the buttons
and
restores
defaults
All configuration data and settings are reset. The
device list, plant diagrams, and unsent messages are
deleted. History data is not deleted.
Overview
LED displays
1 (red/green/orange)
2 (green)
3 (LED)
4 Fault (red)
5 Addressing mode (red)
Operating buttons
6 Remote button
7 Addressing mode
Button combinations
and