Commissioning Instructions

22 / 176
Siemens Web server OZW772... V6.0 CE1C5701en
Building Technologies Commissioning 2015-10-12
The following changes to user defined texts result in outdated device web pages:
· Menu tree names *, e.g. Message receiver 1…4.
· Web Server plant names.
· Plant names for Synco devices (e.g. QAX913).
The impact and restore differ for the three changes mentioned above based on
internal KNX data storage.
Change Device list (device web pages) Texts in sec. navigation Generate/
Update
Delete, Add
Device name Status Menus Device nodes
Menu tree names *, e.g.
Message receiver 1…4
n/a Outdated Outdated n/a Required no
Web Server plant name Current Generate Current Outdated Required no
Plant name for Synco
device(s)
Outdated Generate Current Outdated ** No Required
* Menu tree names are user defined texts displayed in secondary navigation (menu tree)
** Even after generate
· You can update device web pages on user levels "Administrator" and "Service".
· Click "Update" on the service level and "Generate" on the Administrator level to
start updating (see "Create device web pages").
· You can only delete a Synco device on the "Administrator" user level.
When deleting or adding a Synco device (see above for description of workflow),
we recommending copying (select and right-click: Copy) the serial number to the
clipboard prior to deleting.
Update
device web pages
Notes
Tip