Commissioning Instructions

22 / 172
Siemens Web server OZW772... V5.2 CE1C5701en
Building Technologies Commissioning 2014-10-15
2.5.2 Operating page "Faults current"
Local faults and faults in system are displayed under “Faults current”.
Path: Home > 0.5 OZW672… > Faults current
A description of faults is available in Section 4.3,”Faults
2.5.3 Operating page "Settings"
2.5.3.1 Web server
Path: Home > 0.2.150 OZW772.xx > Settings > Web server
Data point
Explanation, example
Language
Default val: English
Setting val: see example
Web server language: Is used for web server
fault texts, message history, messages and
system reports.
Code
Default val: 01
Setting val: max. 20 charact.
Access code for PC Software ACS790.
Reset admin password *
Default val: No
Setting val: Yes
If you do not know the administrator password
for the web server, setting value "Yes" again
provides access to the web server via the
administrator password "Password"
("Password" = Factory setting for
administrator password).
Setting value "Yes" is a temporary state, i.e.
the setting value automatically goes to "No"
after ca. 2 seconds.
*
*
* with PC software ACS790 only.
2.5.3.2 Time of day/date
Path: Home > 0.2.150 OZW772.xx > Settings > Time of day/date
Data point
Explanation, example
Time zone
Default val: GMT +01:00
Berlin, Rome
Setting val: misc. Time zones
The time zone setting value is based on UTC
(GMT). The time zone also defines daylight
saving time / standard time changeover.
Language and
code number
Time zone