Commissioning Instructions

59 / 172
Siemens Web server OZW772... V5.2 CE1C5701en
Building Technologies Operate using a web browser 2014-10-15
Procedure:
1. Select System definitions from secondary navigation.
2. Click [ Update ]
3. Select the desired file.
4. Click [ Upload ] to finish.
5. Restart web server with power-down, power-up.
6. You must recreate the devices following a system definition upload.
System definition file transfer is available to administrator and service user
levels.
Uploading and installing make take more than 5 minutes.
System definitions comprise:
Device descriptions.
Text catalogs in each user language.
Units catalog.
The device web pages use the uploaded system definitions to properly display
devices and menus.
You must generate all device web pages following successful uploading. This
applies the new system definitions.
The system definitions must be compatible with the web server's software version.
If incompatible, an associated message is displayed and the old system definitions
remain as is.
Make sure there is at least 60 MB free memory on the web server when uploading.
If not, check the contents via File transfer > Documents.
4.5 Operation with ACS790
The following functions are available with ACS790:
Commissioning with device search.
Popcard.
Plant diagrams:
For standard applications for the Synco devices, web-capable plant diagrams
may be exported from ACS790 and import them to the web server.
Parameterization:
Read and write parameter sets.
(the parameter set of the OZW772 contains the device list of the OZW772, too)
Commissioning protocol.
Offline trend.
For more details, see data sheet N5649.
Upload system
definitions
Notes
System definitions
Note