Data Sheet for Product

17 / 26
Siemens Web Server OZW772.. V9.0 CE1N5701en
Building Technologies 2018-10-15
The USB interface directly connects the PC/laptop on site. The required USB cable
type A type Mini-B is delivered with the device.
The router/network is connected to the Ethernet RJ45 plug. The Ethernet interface
features Auto-MDI(X) for crossed and non-crossed Ethernet cables. An Ethernet
category 5 cable is supplied.
The KNX bus is connected to the CE+ and CE connection terminals labeled
"KNX". See data sheet N3127 for more information on the KNX bus.
Web operation via Synco IC takes place through an HTTPS encrypted connection
(Port 443) via TCP/IP. The required certificate is accredited.
Web operation without Synco IC takes place through an HTTPS encrypted con-
nection (Port 443) via TCP/IP. The required certificate is not accredited. The self
signed certificate by Siemens is saved on the web server for a period of 20 years
and cannot be changed.
In addition, an HTTP (Port 80) connection is supported. Port 80 is disabled as de-
livered. The access via http is not secured. The user is responsible for enabling
Port 80.
A RNDIS driver on the PC/laptop is required for USB communication. The RNDIS
driver is already included in the Windows operating systems for web server as of
version 7.0.
Fault messages, consumption data, energy indicator reports, and trend files are
sent in an e-mail via SMTP. The e-mail is encrypted using TLS if supported by the
mail server.
The web server can take its network configuration as client from a DHCP server or
be manually configured.
Interfaces
USB
Ethernet
KNX
Logs
Web operation
Send e-mail
DHCP Client