Data Sheet for Product

Distributed Power Supply NAC Extender (Model PAD-3 series)
3362
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety & Security Products
FACP Accessories
PAD-3 Distributed Power Supply Unit
Notification Appliance Circuit Extender
Models PAD-3, PAD-3R, PAD-3-MB, EN-PAD and E N-PAD-R
Product Overview Specifications
Used with Siemens Fire Safety fire alarm control
panels (FACPs), the Distributed Power Supply Unit
(Model PAD-3 series) is a NAC expander with a built-
in, auxiliary-power output. Each unit is designed to
provide additional power for visual indicators in
buildings that conform to the Americans with
Disabilities Act (ADA).
Each Model PAD-3-series unit provides the following
physical characteristics:
NACs
Unit enclosure
Signal-input circuits
Battery-charging circuit
Trouble relays for remote monitoring
Diagnostic light-emitting diodes (LEDs)
Alternating Current (AC) power connection
The Siemens NACs, which connect with alarm
signaling devices, have been designed to provide the
highest level of reliability and performance.
Each unit provides 6A @ 24VDC power for multiple
uses, and all 6 Amps can be directed to four (4)
NACs. Each NAC is power limited; rated at 3A. Either
one (1) or two (2) inputs can control the four (4)
outputs. These outputs are compatible with all
Siemens
Fire Safety 24VDC notification appliances.
In order to makes the outputs easily programmable,
this version of the Siemens Auxiliary Power Supply
(Model PAD-3)
can be configured in the following
manner:
‘STEADY’ outputs
Synchronized strobe outputs
American National Standards Institute (ANSI) Temporal 3
ARCHITECT AND ENGINEER SPECIFICATIONS
Multi-module mounting in System 3 enclosures
Multiple modules share battery set
Americans with Disabilities Act (ADA) Compliant
UL 864 9
th
Edition Listed, ULC S527-11 Listed;
FM, CSFM & NYC Fire Department Approved
Model EN-PAD
[Black enclosure]
24VDC output voltage
Ground-fault detection
Advanced microprocessor control
Power supply supports NAC power
Up to 6A @ 170W, via Siemens Model PAD-3
3 Amps of auxiliary-power output
‘Form C’ Trouble monitoring dry contact
Four (4), power-limited notification appliance circuits (NACs)
Power supply supports NAC power
Up to 6A @ 170W, via Model PAD-3
Optional built-in strobe synchronization
Supports coded audible signals including
Temporal 3 pattern
Battery supervision and control
Packaged in self-contained, sheet-metal enclosure
Easily capable to house the required 7AH back-up battery set
PAD-3-MB

Summary of content (4 pages)