User Manual
Siemens Building Technologies CA2N1651E / 11.1998
Landis & Staefa Division 1/4
1
651
PBA
Room operating unit
Room operating unit for individual
room control in HVAC systems.
Used in conjunction with the
PRONTO PRFA.., PRONTO IRC PRU/A,
PRFB.., PRVU, SMART SMVU or
INTEGRAL RS controllers.
• T1 temperature sensor
• ± 3 K setpoint adjuster
• Socket for ZS1 service terminal
(for PRONTO IRC only).
PBA
Technical data
Product data
Operating range 0 ... 50 °C
Sensor element T1 (PTC)
Trimmer range ± 2.5 K
Setpoint adjustment ± 3.0 K, stepless (rotary knob)
Connections
Screw terminals 2.5 mm
2
Service socket FCC 4/4 pin
Weight without unit base
(including packaging) 0.09 kg
Dimensions (w x h x d) 80 x 135 x 37 mm
Colour
Housing NCS 0003-R20B
Operator elements NCS 1005-R20B
Safety
Product safety EN 61010-1
– Contamination level 2 (normal, non-conductive contamination)
Electrical safety SELV
General ambient conditions
Usage For indoor use
Operating temperature 0 ... 50 °C
Storage temperature – 25 ... 70 °C
Ambient humidity Max. 65 %rh annual mean,
non-condensing
Conforms to requirements
Principle of operation
The room temperature is measured with a built-in T1 temperature sensor
(PTC silicon resistance element, see sheet 1713. If a sill-line sensor is used
(such as the PFB-T1), the room temperature sensor must not be connected
(see "Terminal layout", page 2).
The stepless rotary knob on the room operating unit allows the setpoint
defined in the connected controller to be reset locally by ± 3 K.
The measured sensor signal can be recalibrated by ± 2.5 K by use of the
trimmer potentiometer on the underside of the room operating unit
An FCC telephone socket is provided on the underside of the unit for
connection of the ZS1 service terminal, used in conjunction with the
PRONTO IRC controllers for parameter-setting and diagnostics.
Ordering information
The base unit and electronic assembly are
supplied separately and must be ordered
as separate items:
PBA Electronic assembly (without base
unit)
PB1 Base unit with transparent
protective cover
22845 Service cable for ZS1 service
terminal
Ordering example
PBA (Electronic assembly)
PB1 (Base unit)
22845 (Service cable)
50938
FCC socket for ZS1
service terminal
± 2.5 K
trimmer potentiometer
– +