Smart Infrastructure
A6V11243351_en--_d
2021-06-30
Call stations
You will find more information and technical data on call stations in the 'Call stations and
extensions' data sheet. You will find the relevant document ID in the 'Product
documentation [▶ 44]' section.
PT2002-A1
'Fire brigade call station (AT)'
● Fire brigade call station with standard-compliant housing and control panel
● Full network participant in a Cerberus PACE system
● Pre-configured for Austrian F3033 standard
● Can be configured for other standards
● Locked with a key to prevent unauthorized operation
● 7 standardized and pre-configured buttons with status indicators
● 3 standardized and pre-configured status indicators
● Removable hand-held microphone with a push-to-talk button
● Microphone off-hook contact to detect that the microphone is in use
● Microphone and line monitoring
● Integrated audio amplifier (1 watt) and speaker
● Integrated industrial micro SD card reader/writer with max. 2 GB card capacity
for alarm messages
● Recording capacity: 255 files with a total duration of approx. 3 hours
● Provision of alarm announcements and alarm tones
● 2x Ethernet LAN interfaces for a redundant 'PACE-Net' network connection
● One additional analog audio input (line) and one additional analog audio
output
● Adapter module PTO2009-A1 for redundant connection to the control panel
PT2003-A1
'Fire brigade call station (485, AT)'
● Fire brigade call station with standard-compliant housing and control panel
● Can be configured for Austrian F3033 standard or other standards
● Locked with a key to prevent unauthorized operation
● 7 standardized and configurable buttons with status indicators
● 3 standardized and configurable status indicators
● Removable hand-held microphone with a push-to-talk button
● Microphone off-hook contact to detect that the microphone is in use
● Microphone and line monitoring
● Symmetrical analog audio transmission, analog
● Analog audio output 0 dB (line volume)
● 'PACE-Bus' (RS485) data transmission
● Connection to control panel via CAT5 cable (max. 500 m)
● Connection to control panel with RJ45 or screw terminal connector
● Adapter module PTO2008-A1 or RS485 module PN2009-A1 for connection to
the control panel
● Addressable via 4-way ID-switch for 'PACE-Bus' connection