Data Sheet for Product

16
Smart Infrastructure
A6V11243351_en--_d
2021-06-30
Operating terminals
You will find more information and technical data on the operating terminals in the
'Operating terminals' data sheet. You will find the relevant document ID in the 'Product
documentation [ 44]' section.
PT2010-A1
'System operating unit (19")'
EN 54-16-compliant indicator panel for visual and acoustic status messages
and control voice alarms
Display of system status
Control of voice alarms
Fault warning with acoustic warning signal
Labeled in English and German
Color-coded visual indicators: operation, fault, and alarm
<System ON / Betrieb>: green
<Fault / Störung>: yellow
<Voice alarm / Sprachalarm>: red
Color-coded control buttons: control of voice alarms, acknowledges
<Start Voice Alarm / Sprachalarm auslösen>: red LED indicator button
<Reset Voice Alarm / Sprachalarm rückstellen>: black button
<Silence Voice Alarm / Sprachalarm ab>: green LED indicator button
<Reset Fault / Störung rückstellen>: black button (acknowledge faults)
<Silence Buzzer/LED Test / Summer aus/LED Test>: black button
(acknowledge acoustic warning and LED lamp test)
8 predefined visual fault indicators: yellow
<Power / Stromversorgung> fault
<Fuse / Sicherung> fault
<Earth / Erdschluss> fault
<Network / Netzwerk> 'PACE-Net' fault
<Bus / Bus> 'PACE-Bus' (RS485) fault
<Amplifier / Verstärker> fault
<Microphone / Mikrofon> fault
<Speaker / Lausprecher> speaker circuit fault
8 user-configurable state indicators: yellow
Extends a digital audio matrix by additional 4 logic control inputs
Extends a digital audio matrix by additional 4 logic control outputs
Service socket
RS485 data transmission ('PACE-Bus')
Addressable via 4-way ID-switch for 'PACE-Bus' connection
Design: 19", 2 HU