Data Sheet for Product

32
Smart Infrastructure
A6V11243351_en--_d
2021-06-30
PCA2004-A1
'EOL3 (active)'
Monitoring of speaker lines in accordance with EN 54-16
For use with the digital audio matrices PC2001-A1, PC2002-A1 and PC2003-
A1
Monitoring the 100 V speaker line for open lines and short circuits
Addressable: up to 16 different addresses can be configured
Addressing compatible with any tree structure with up to 16 line ends, in
addition to the stub line
Reliable cable break detection in any branch of a speaker line
No other wiring needed; works with standard two-wire speaker line
No need to route line back to control panel
PCA2005-A1
'Loop isolator (100V)'
Monitoring and isolating of speaker line loops in accordance with EN 54-17
For use in 100 V speaker line loops with PC2003-A1
Rapidly detects and isolates short circuits affecting the 100 V speaker line
loops
Monitors the speaker and cables connected to the loop isolator for open lines
and short circuits
Monitoring with speakers from 0.75 W to 12 W
Two-pole standard lines used as cables for the speaker line loop
Optical display of isolator status
Housing 'Spelsberg i 16-L loop isolator Box' PCA2013-A1 required to meet
EN 54-17
PCA2013-A1
'Spelsberg i 16-L loop isolator Box'
Housing for 'Loop isolator (100V)' PCA2005-A1
Required to meet EN 54-17
IP55