Data Sheet for Product
Table Of Contents
5
Smart Infrastructure
A6V11243351_en--_d
2021-06-30
Call stations
Cerberus PACE offers a range of call stations for various applications.
The alarm and standard call station PT2001-A1 is a network based 'PACE-Net' desk call
station with 19 buttons and indicators. This is designed for the following applications:
● Control and monitor the Cerberus PACE system by users
● Selecting speaker circuits
● Selecting an audio source
● Playback of announcements recorded in advance
● Transmitting live announcements via mounted gooseneck microphone
● Allows a redundant system structure
● For other applications, see Call stations [▶ 11]
Up to four additional button modules PTO2001-A1 can be fitted to extend the network-based
desk call station PT2001-A1 to a maximum of 115 buttons.
The call station buttons of PT2001-A1 and PTO2001-A1 are basically freely operable.
An optional key switch module PTO2002-A1 or PTO2003-A1 enables all or individual call
station buttons to be released or locked individually.
The longer PTO2004-A1 can be used here as an alternative to the standard gooseneck
microphone.
The desk call station PT2008-A1 is designed for small standard applications.
The call station buttons of PT2008-A1 are freely operable.
The desk call station PT2008-A1 may only be used for standard applications rather than
alarm applications.
The desk call station PT2009-A1 is designed for small to medium-sized standard
applications. It communicates via the 'PACE-Bus' and a 0 dB symmetrical analog audio
transmission.
Up to three additional button modules PTO2006-A1 can be fitted to extend the desk call
station PT2009-A1 to a maximum of 32 buttons.
The call station buttons of PT2009-A1 and PTO2006-A1 are freely operable.
The PT2002-A1 is a network-based 'PACE-Net' fire brigade call station and allows a
redundant system structure. The fire brigade call station PT2003-A1 communicates via
'PACE-Bus' and 0 dB symmetrical analog audio transmission.
They are designed for use by the fire brigade or trained security personnel. The alarm and
system status can be monitored.
● The integrated hand-held microphone can be used to make live announcements.
● The pre-configured alarm announcement buttons can be used to play stored alarm and
evacuation announcements.
Live announcements or stored alarm and evacuation announcements can be played
throughout the entire building or in single areas (zones). The system interrupts all other
audio outputs throughout the building or in the single areas as soon as:
● an alarm announcement button is pressed or
● hand-held microphone is taken from the hook or
● the push-to-talk button on the hand-held microphone is pressed.