Data Sheet for Product
10
Smart Infrastructure
A6V11940275_en--_b
2021-03-12
PACE-Bus
PN1002-A1
'RS485 module (1 port)'
● 1x 'PACE-Bus' (RS485) port
● 2-way optical isolated 'PACE-Bus' (RS485) repeater
● Provides controlled DC 24 V electrically isolated output
● Provides electrically isolated analog audio input
● Provides electrically isolated analog audio output
● Monitoring of the DC 24 V line for ground faults
● Plug-in module for Cerberus PACE Compact digital audio matrix boards
PNA2009-A1
'ICPDAS I-7510 (RS485, isolated)'
● 2-way optical isolated 'PACE-Bus' (RS485) repeater
● 35 mm DIN rail mounting
I/O modules
FDCIO221
'Input/output module FDnet/C-NET'
● Input/output module FDCIO221:
– Control output with potential-free relay contact for activation of alarming
devices, fans, air conditioning systems, lift controls, etc.
– Monitored contact input for reporting technical statuses or activating an
alarm
– Use as a monitored output with a separate power supply, e.g., for operat-
ing acoustic signal transmitters
● LED indicator for input/output statuses and for fault, test and localization
● Power supply and communication via FDnet/C-NET (addressed individually)
● Address automatically issued during commissioning
● Two-wire installation for all cable types