Data Sheet for Product

18
Smart Infrastructure
A6V11940275_en--_b
2021-03-12
Call stations / operating terminals
Ground fault monitoring (24 V)
PCA2001-A1
Supply
Power supply
DC 24 V
(corresponds to the voltage to be monitored)
Current consumption
100 mA
Threshold
50 kohm
(10 kohm if JP1 and JP2 closed)
Relay contact
Max. 48 V / 500 mA
Fault indicator relay
Changeover contact (fault / OK)
Can be switched to a lower sensitivity of
10 kohm for each jumper
Ambient conditions
Operating temperature
-5…+40 °C
Storage temperature
-20…+70 °C
Operation in humid environments
(without moisture condensation)
10...90 % rel.
Storage in humid environments
(without moisture condensation)
5...90 % rel.
Housing type
Open frame design
Mounting
DIN rail mounting (TS35)
Dimensions and weights
W x H x D mm
75 x 70 x 40
Weight
100 g
Standards
EN 54-16