Data Sheet for Product

4
Smart Infrastructure
A6V11940275_en--_b
2021-03-12
EOL modules
EOL3 (active) PCA2004-A1
The 'EOL3 (active)' PCA2004-A1 ensures that the speaker lines are monitored without
interruption in accordance with EN 54-16.
The device is addressable. The 16 addresses are created by DIP switch.
Up to 16 PCA2004-A1 can be connected per speaker line and amplifier. The PCA2004-A1
was specifically developed for use with the digital audio matrices PC2001-A1, PC2002-
A1,PC2003-A1, as well as the 'Voice alarm panel Compact 400' PC1001-A3 and the 'Voice
alarm panel Compact 1000' PC1002-A3.
Loop isolators
Loop isolator (100V) PCA2005-A1
The loop isolator (100 V) PCA2005-A1 is an isolating element in accordance with EN 54-17
for use in a 100 V speaker line. The isolator rapidly detects and isolates short-circuits
affecting the line. It monitors the speaker line connected to the loop isolator for open lines
and short-circuits. The status of the PCA2005-A1 is shown on an optical display.
Two-pole standard wires are used as cables for the speaker loop. Up to 120 loop isolators
can be connected to a speaker line loop (depending on the connected amplifier). The
maximum loop length is 1000 m per amplifier output.
The PCA2005-A1 was specifically developed for use with the digital audio matrix PC2003-
A1, as well as the 'Voice alarm panel Compact 400' PC1001-A3 and the 'Voice alarm panel
Compact 1000' PC1002-A3.
Spelsberg i 16-L loop isolator Box PCA2013-A1
IP55 housing for loop isolator (100 V) PCA2005-A1. It is required for the PCA2005-A1 to
meet the EN 54-17.
PACE-Net
The Cerberus PACE Compact 'PACE-Net' network is based on a standard Ethernet with
100 Mbit/sec and CAT5 copper cables.
Camdenboss RJ45 Interface PNA2008-A1
A standard CAT5 Ethernet cable comes with a standard RJ45 connector. PNA2008-A1 is an
interface from RJ45 connector to screw terminals to connect cables with single wires (e.g.
E30).
PACE-Bus
ICPDAS I-7510 (RS485, isolated) PNA2009-A1
The isolated RS485 repeater PNA2009-A1 is required to electrically isolate 'PACE-Bus'
(RS485) signals exiting the system cabinet from the internal 'PACE-Bus' (RS485). Any short-
circuit that occurs outside the system cabinet will therefore not affect the internal 'PACE-Bus'
(RS485).
The PNA2009-A1 requires a supply voltage of DC 24 V.
RS485 module (1 port) PN1002-A1
The 'RS485 module (1 port)' PN1002-A1 is used for a convenient connection of external
'PACE-Bus' (RS485) components. It provides the following electrically isolated signals:
'PACE-Bus' (RS485) communication
DC 24 V power supply voltage with ground fault detection
Analog audio input
Analog audio output
Any short-circuit on the connected wiring which occurs outside of the system cabinet will
therefore not affect the internal signals.
One PN1002-A1 plug-in module can be mounted on a digital audio matrix board.