Configuration Instructions

Hardware specific configuration
'Logic Inputs Connector'
7
A6V10429097_en--_e
149 | 219
DI1
Mains failure
DI2
Battery failure
DI3 and DI4
Use of PT2002 with PTO2009 (2x
DC 24 V feed). Always set 'used for
logging'.
Function
Description
'Test & Quit Key'
Used for indication board. Manual Silencing of faults for audible indication of
faults (buzzer). Also used for silencing the voice alarm condition.
'GP' flag:
If set, then all enabled outputs should be tested
If not set, only specific outputs should be tested
GP_OUT
System Fault
System Fault Buzzer
System Variable with SysVarID=5 (voice alarm)
System Variable with SysVarID=6 (silence alarm)
'Alarm Start'
A positive edge on the corresponding input starts an alarm. Same parameters
as 'Start/Stop'.
'Alarm Stop'
A positive edge on the corresponding input stops an alarm.
'GP' flag:
If set, then all zones are deselected
If not set, then no additional action is taken