Configuration Instructions
Hardware specific configuration
'Logic Outputs – Connector'
7
A6V10429097_en--_e
153 | 219
Function
Description
'Feed Present'
Used to signal that a dedicated feeding channel is active on the network. The
requested feeding channel (#1-255) is configured via the
'Input/SysVarID/Feed/Level/Led' column.
NOTICE! Use this by 'Feed with triggered signal', otherwise the logic output
is always on, even when the feed is -80 dB.
'AudioOut Active'
a specific audio output of a dedicated station is currently active. Valid parameters
are:
'StationID'
define requested station
'AudioOutputNo'
define requested output (1..4)
'Input/SysVarID/
FeedNo/Level'
used to define a specific feeding channel
'0'
logic output responds if any channel is active on the audio
output
'x(1..254)'
logic output responds if this channel x is active on audio output
'255'
logic output gets active if a priority channel is active on the
audio output.
'AudioOut Level [dB]'
A specific audio output of a dedicated station is currently playing a signal which
level is larger than a given threshold.
Parameters are StationID, Audio Output Number and Level
'AudioIn Level [dB]'
A specific audio input of a dedicated station is currently above the given threshold
level.
Parameters are StationID, Audio Output Number and Level
'Line Detection Fault'
Used to set this logic output if the 'LineDetection' function records a fault. Valid
parameters are:
'1-16'
Selects a specific audio output observed by the 'LineDetection'
function
'0'
Collects all faults of the 'LineDetection' function
'Keypad LED'
Any KeyPad Led in the system could be used to trigger the logic output.
'LedMode 0'
any, the output is activated if any color of the LED is active
'1'
red, only if the red LED is active
'2'
green(only if green LED is active)
'3'
yellow (both LEDs must be active)
'Backup Control'
'Any'
will enable if the current device has switched to an backup
amplifier
'A0'
used to control the line A0 (address line) of the backup mux pcb
'A1'
used to control the line A1
'EN 54-16: Disablement
Condition'
Output is active if one or more local inputs with input mode=Disablement
Condition are active. For detailed information see the EN 54-16 spec.
'EN 54-16: Voice Alarm
Condition'
'0'
Default behavior: Output is active until the voice alarm is
canceled.
'1'
Output is active until 'Alarm manual Reset' is enabled.
For detailed information see chapter 7.7 in EN 54-16 spec.
'EN 54-16: Output to Fire
Alarm devices'
0
Default behavior: Output is active until the voice alarm is
canceled on the corresponding audio output/line.
'1'
Output is active until 'Alarm manual Reset' is enabled.