12.3 System Errortypes
SystemError
Value
Remark
Type
UNUSED
0x00
Entry is unused
CLEAN_AFTER_ERR
0x01
Entry after an error
U
SYSVARFLAGS
0x02
Sysvarflag detection – only for debug/logging purposes not
really an error
I
GENERAL_DEBUG
0x03
Used to debug special elements – not really an error
I
DISABLEMENT_CONDITI
ON
0x04
To log changes of one or more speakerlines
Valid since FW1.2B14
I
ALARM_START_SOUND
0x05
To log an “start sound” event (Only warning)
I
ALARM_STOP_SOUND
0x06
To log an “stop sound” event
I
ALARM_ACTIVE
0x07
To log an “alarm active” event
I
ALARM_MAN_SILENCED
0x08
To log manual silencing of activated voice alarms
I
SYSTEM_FAULT_RESET
_
0x09
Manual reset of system fault activated
I
PACE-
BUS_NOTRELEV_MEMB
ERS_ MISSING
0x0A
One or more PACE bus participants is missing. Does not cause
a system error (only for information).
I
0xB-0C
Reserved for future informational entries
I
BACKUP_STATE_CHAN
GED
0x0D
Backup state (SL16)
W
LOGGING_STATION_AB
STIME
0x0E
The logging station is now able to log errors in absolute time
format (received for the first time, entry in relative time format
and one entry in absolute time)
(implemented since V1.1B8)
stationID = ID of the time Provider
U
DEVICEMODE_CHANGE
D
0x0F
The (logging?) station entered/left special modes, e.g., firmware
update
W
MIC_FAULT
0x10
Detected Microphone fault
F
SD_CARD_FAULT
0x11
SD Card not valid/inserted
F
EXT_UART_FAULT-
0x12
External UART reports a fault, valid since FW1.2B23
F
INT_FLASH_WRITE
0x13
Internal flash write error
F
CODEC_FAILED
0x14
Codec failure
F
LINK_ILLEGAL
0x15
Established LAN connection is not permitted for PACE-Net
devices
F
CFG_MEM_FAULT
0x16
An unallowed change of config data occurred
F
MAINBOARD_FAULT
0x17
The mainboard reported a failure
F
PACE-BUS
MONITORING FAULT
0x18
A monitored bus participant reported a fault
F
NW-RING_FAULT
0x19
Indicates a network fault (ERPS ring failure) valid since
FW1.2B20
F
PWR_OUT_OF_RANGE
0x1A
An internal power supply is out of range valid since FW1.2B20
F
SENS_OUT_OF_RANGE
0x1B
Any sensor (temperature, etc.) is out of range, valid since
FW1.2B20
F
PACE-
0x1C
A safety-relevant PACE bus participant is missing
F