EN 54-16 – Specific settings
5
A6V10429097_en--_e
49 | 219
5.4.3 Reset of fault indications
Chapter 8.7 in EN 54-16
8.7.1: 'Indications of faults as required in 8.2 shall be capable of being reset:
● Automatically when faults are no longer recognized
– And/or
● By a manual operation at access level 2.'
Configuring the input accordingly
◈
Enable the desired input, and define it as follows:
– 'EN54-16: System Fault reset'
5.4.4 Configuring PT2004
The 'of Station' field contains the station ID of the module to which the indication
board is connected.
The error logging feature must be enabled. You will find more information in
section Error Logging, EN 54-16 & RSL [➙ 125].
Logic Outputs needed: 4
● LED Betrieb/Operating
● LED Störung/Fault
● LED Sprachalarm/Voice alarm
● Buzzer
Fig. 15: Configuring PT2004: 4 logic outputs
Logic Inputs needed: 2
● Acknowledgment test / Buzzer reset test
● Indication Board Error (ON)
Fig. 16: Configuring PT2004: 2 logic inputs