Data Sheet for Product
15
Smart Infrastructure A6V10430563_en--_b
2020-06-30
Call stations / operating terminals
Ground fault monitoring (24V)
PCA2001-A1
Supply
Power supply DC 24 V
(corresponds to the voltage to be monitored)
Current consumption 100 mA
Threshold 50 kohm
(10 kohm if JP1 and JP2 closed)
Relay contact Max. 48 V / 500 mA
Fault indicator relay Changeover contact (fault / OK)
Can be switched to a lower sensitivity of
10 kohm for each jumper
Ambient conditions
Operating temperature -5…+40 °C
Storage temperature -20…+70 °C
Operation in humid environments
(without moisture condensation)
10...90 % rel.
Storage in humid environments
(without moisture condensation)
5...90 % rel.
Housing type Open frame design
Mounting DIN rail mounting (TS35)
Dimensions and weights
W x H x D mm 75 x 70 x 40
Weight 100 g
Standards EN 54-16