Data Sheet for Product
4
Smart Infrastructure A6V10430563_en--_b
2020-06-30
Loop isolators
Loop isolator (100V) PCA2005-A1
The loop isolator (100 V) PCA2005-A1 is an isolating element in accordance with EN 54-17
for use in a 100 V speaker line. The isolator rapidly detects and isolates short-circuits
affecting the line. It monitors the speaker line connected to the loop isolator for open lines
and short-circuits. The status of the PCA2005-A1 is shown on an optical display.
Two-pole standard wires are used as cables for the speaker loop. A speaker loop can
accommodate up to 80 isolators. The maximum loop length is 1000 m per amplifier output.
The PCA2005-A1 was specifically developed for use with the PC2003-A1 digital audio
matrices.
Spelsberg i 16-L loop isolator Box PCA2013-A1
IP55 housing for loop isolator (100 V) PCA2005-A1. It is required for the PCA2005-A1 to
meet the EN 54-17.
PACE-Net
The Cerberus PACE 'PACE-Net' network is based on a standard Ethernet with 100 Mbit/sec
and CAT5 cables.
Repeater (CAT5) PNA2007-A1
A standard Ethernet is usually limited to a length of 100 m. The PNA2007-A1 makes it
possible to extend the CAT5 cable by an extra 100 m.
The PNA2007-A1 requires a line voltage of DC 24 V.
Camdenboss RJ45 Interface PNA2008-A1
A standard CAT5 Ethernet cable comes with a standard RJ45 connector. PNA2008-A1 is an
interface from RJ45 connector to screw terminals to connect cables with single wires (e.g.
E30).
PACE-Bus
ICPDAS I-7510 (RS485, isolated) PNA2009-A1
The isolated RS485 repeater PNA2009-A1 is required to electrically isolate 'PACE-Bus'
signals exiting the system cabinet from the internal 'PACE-Bus'. Any short-circuit that occurs
outside the system cabinet will therefore not affect the internal 'PACE-Bus' .
The PNA2009-A1 requires a supply voltage of DC 24 V.