Data Sheet for Product

8
Smart Infrastructure A6V10430563_en--_b
2020-06-30
EOL modules
PCA2004-A1 'EOL3 (active)'
Monitoring the speaker line for open lines and short-circuits
Monitoring in accordance with EN 54-16
Addressable: up to 16 different addresses can be configured
Addressing compatible with any structure with up to 16 line ends, in addition
to the stub line
Reliable cable break detection in any branch of a speaker line
No other wiring needed; works with standard two-wire speaker line
No need to route line back to control panel
Loop isolators
PCA2005-A1 'Loop isolator (100V)'
Isolating element in accordance with EN 54-17 for use in a 100 V speaker line
with PC2003-A1
Rapidly detects and isolates short-circuits affecting the 100 V speaker line
Monitors the speaker and cables connected to the loop isolator for open lines
and short-circuits
Two-pole standard lines used as cables for the speaker loop
Optical display of isolator status
PCA2013-A1 'Spelsberg i 16-L loop isolator Box'
Housing for loop isolator (100 V) PCA2005-A1
IP55