Planning a voice alarm system
Contact for remote triggering
5
A6V11899877_en--_b
25 | 46
5.2 Contact for remote triggering
Transmission for an alarm/evacuation through the VACIE occurs by means of a
contact.
The contact for remote triggering between the FCP and VACIE must be physically
set up and configured in each case.
The FCP must also be configured in such a way that the VACIE confirms that the
alarm/evacuation has been processed successfully following the transmission for
the remote triggering.
If the VACIE fails to confirm that the alarm/evacuation has been processed
successfully following the transmission for the remote triggering, the FCP must
issue the signal for remote triggering again.
WARNING
Alarm not triggered
Personal injury and damage to property in an emergency.
● The FCP must receive and evaluate the 'Alarm active' confirmation once
remote triggering has been transmitted. If this does not happen, the triggering
process must be repeated.