Planning
Planning call stations
Network call station PT2001, PT2002
8
32 | 46
A6V11899877_en--_b
8.1.2 Power supply
8.1.2.1 Power supply PT2001-A1 and PT2002-A1
PT2001-A1 and PT2002-A1 power supply via separate cable, DC 24 V. 'PACE-Net'
does not support PoE.
Fig. 12: PT2001-A1 and PT2002-A1 power supply
1
Cerberus PACE Compact cabinet
2
External Desk call station (19 buttons) PT2001-A1 with accessories or Fire
brigade call station (AT) PT2002-A1
3
MeanWell SD-50B-24 DC/DC PCA2011-A1 or MeanWell SD-100B-24 DC/DC
PCA2018-A1
4
Ground fault monitoring (24V) PCA2001-A1
5
Fuse 1 A
6
Not used
7
24 V wiring to Desk call station (19 buttons) PT2001-A1 or Fire brigade call
station (AT) PT2002-A1
PCA2011-A1 and PCA2018-A1 (3) provide isolated DC 24 V. A short circuit
outside of the cabinet has no impact on the whole cabinet.
The PCA2001-A1 (4) detects a ground fault on the 24 V wiring to PT2001-A1 and
PT2002-A1.
Each 24 V wiring (7) to PT2001-A1 and PT2002-A1 is installed with a 1 A fuse (5).
It ensures that a short circuit on one 24 V wiring has no impact on the other.
In high reliable life safety systems, use a redundant 24 V power for PT2001-A1 or
PT2002-A1.
Alternative power supply for PT2001-A1, PT2002-A1, and media converter
PN2007-A1 and repeater PNA2007-A1 via the PP2004-A1 power supply, approved
in accordance with EN 54-4.
PT2001
(PT2002)
DC/DC
PCA2011
PCA2018
Ground Fault
PCA2001 Fuse
(PT2001)
PT2002
Fuse
DC 24 V DC 24 V
DC 24 V
Cabinet
1
1
12
13 14
15 17
12
15 17