Planning
Planning call stations
Analog call station PT2008
8
A6V11899877_en--_b
43 | 46
8.3.2 Power supply PT2008-A1
Fig. 18: Wiring of one PT2008-A1
1
Cerberus PACE Compact cabinet
2
External PT2008-A1
3
Not used
4
Not used
5
Wiring of the 4 button signals to the logic inputs
6
Call station interface of PT2008-A1
7
Fuse 1 A
8
Copper Ethernet cable (CAT5) with RJ45 connector, connecting the call
station interface of PT2008-A1 to the call station PT2008-A1
The figure above displays a wiring example of one PT2008-A1 being connected to
one matrix. This wiring can only be utilized for PT2008-A1 in standard use cases
and is not permitted in evacuation use cases.
The matrix provides DC 10 V. A fuse (7) protects the internal 10 V power supply. A
short circuit outside of the cabinet has no impact on the whole cabinet.
The 10 V power supply, the 4 logic signals and the audio signal are connected to
the call station interface of PT2008-A1.
The PT2008-A1 call station interface provides a RJ45 connector with all the signals,
which facilitates the wiring of the PT2008-A1.
Standard copper Ethernet cables (CAT5) with RJ45 connectors are used for the
wiring (8), connecting the call station interface of PT2008-A1 to the call station
PT2008-A1.
8.3.3 Accessories
The PT2008-A1 call station interface is part of the scope of delivery for PT2008-A1.
PT2008
DC 10 V
Cabinet
11
17
18
CAT5
12
Fuse
16
4x logic
input
1
5
PT2008
interface