Configuration Instructions

Appendix
Station error state
12
214 | 219
A6V10429097_en--_e
Bit
Name
Description
B0
STATION_NO_RESP
OND
The station is currently not connected via LAN or cannot be seen due to
another reason.
B1
MAINBOARD
_FAILURE
The subsystem failed (internal communication, voltage failure etc.)
B2
MIC_FAILURE
Microphone is not connected or has a short-circuit.
Supervision of microphone must be activated by enabling “Check Mike” in
the Supervision tab of the “Peripherals and supervision” config page.
B3
SD_FAILURE
SD card not present or corrupted sound files. Other possible reasons: Not
accepted cards, or accepted info differs from actual SD card information.
B4
FAULT_CONTACT_
ACTIVE
Logical input check failed.
B5
FLASH_WRITE_FAIL
ED
Some errors occurred while writing to internal flash (error logging).
B6
CODEC_FAILURE
Hardware failure one of the audio codecs reported an error.
B7
LINK_STATE_ILLEG
AL
1) Half duplex or 10 Mbit mode detected these modes are working but
are not allowed.
2) Redundant network: Link is not valid on both ports.
B8
CRC_CHK_FAILED
Cyclic comparison of RAM content failed (64k configuration block).
B9
STATIONS_MISSING
Only valid for the logging station to indicate that at least one station is
missing.
B10
EXT_UART_FAILURE
Used to sign a communication error on external UART Interface.
Appears as of V1.0B21 if a PACE bus device is configured but not
detected. Appears as of V1.2B14 if a safety-related PACE bus participant is
missing.
Also activated if the external UART mode is 'Call Station Keypad Extension'
but no extension was found.
B11
LD_FAILURE
Communication with LineDetection hardware failed.
B12
AMP_FAULT
At least one of connected amplifiers is in faultState
Could be detected by 'Amplifier sense' contact input or LineDetection
B13
ALARM
station is currently in alarm state (active alarm call running)
B14
SYSVAR_FLAGS
To log sysvar stuff
B15
LD_LINE_ERROR
Linedetection reports an error (at least on one line). Further information is
stored in LD_State. Valid as of AVD protocol V1.1
B16
BACKUP_FAULT
Since V1.1B20 following definition is valid:
If backup monitoring of the corresponding line is activated, then this bit
reports a fault on the backup input line.
B17
RUNNING_ON_BATT
The station is running on battery (Mains fault). Valid since FW1.1B30
B18
PACE_BUS_MEMBE
RS_ MISSING
One or more PACE bus participants is missing, valid since FW1.2B14
B19
PACE_BUS_MONITO
RING_FAULT
A monitored bus participant reported a fault, valid since FW1.2B18
B20
NW_RING_FAULT
Indicates a network fault (ERPS ring failure), valid since FW1.2B19.
B21
PWR_OUT_OF_RAN
GE
Internal power supply is out of range, valid since FW1.2B19.