Mounting Instructions

Install internal components
Digital audio matrices
6
38 | 173
A6V10430579_en--_b
PC2001-A1
PC2002-A1
PC2003-A1
PC2005-A1
PC2006-A1
Power supply input DC 24 V
1
1
1
1
1
Network, RJ45
2
2
2
2
2
Fault relay output, changeover switch
1
1
1
1
1
Serial interface 'PACE-Bus'
RS485/RS232
1/1
1/1
1/1
1/1
1/1
Analog control inputs
8
8
-
8
8
Logic control inputs
8
8
8
8
8
Logic control outputs, open collector
8
8
8
8
8
Analog audio inputs
4x XLR
-
4
4x XLR
-
Analog audio outputs
4x XLR
4x XLR
4
4x XLR
4x XLR
100 V audio inputs
4
4
4
-
-
100 V speaker line outputs
4
4
16
-
-
NOTICE
PC2005-A1 and PC2006-A1 can not be used in EN 54-16 conform evacuation
systems
The 'Digital audio matrix no supervision (4/4/0)' PC2005-A1 and 'Digital audio
matrix no supervision (0/4/0)' PC2006-A1 do not meet the EN 54-16 requirements
because they have no means to supervise the speaker lines.