4 Cerberus PACE Compact Accessories and options PCA20xx-A1, PCIO200x-A1, PCO200x-A1, PNA200x-A1, PN1002-A1, FDCIO22x Accessories and optional components for the EN 54-16-certified Cerberus PACE Compact digital multi-channel audio system.
Use Extras ATP AF2GUD-2*** SD 2 GB Card PCA2002-A1 (Preferred) Swissbit SFSD2048N1 SD 2 GB Card PCA2017-A1 (Second source) The SD cards PCA2002-A1 and PCA2017-A1 are digital micro SD memory cards with a capacity of 2 gigabytes. The cards store up to 3 hours' worth of audio files. The cards can hold up to 256 individual audio files. The SD cards satisfy the industry standard, providing a guaranteed data storage period of over 10 years.
Output module (relay, 8) PCO2002-A1 The 'Output module (relay, 8)' PCO2002-A1 extends the number of digital outputs for each audio matrix by additional 8 electrically isolated relay outputs. Each relay offers 2-pole changeover contacts. All contacts, NC, NO and center are routed to terminals. Further 8 relay outputs can be added by connecting an 'Output extension (relay, 8)' PCO2003-A1 module directly to this module.
EOL modules EOL3 (active) PCA2004-A1 The 'EOL3 (active)' PCA2004-A1 ensures that the speaker lines are monitored without interruption in accordance with EN 54-16. The device is addressable. The 16 addresses are created by DIP switch. Up to 16 PCA2004-A1 can be connected per speaker line and amplifier.
I/O modules Input/output module FDnet/C-NET FDCIO221/FDCIO222/FDCIO223/FDCIO224 The input/output modules FDnet/C-NET FDCIO221/FDCIO222/FDCIO223/FDCIO224 can be used to connect outputs and inputs of the Cerberus PACE Compact system with a Cerberus Pro fire system. The outputs are used to send status and other information to the fire system and the inputs are used to get control information from the fire system. The modules can be mounted in the Cerberus PACE Compact cabinets.
Features and Functions Extras (Preferred) NOTICE! These extras are to be preferably ordered. PCA2002-A1 'ATP AF2GUD-2*** SD 2 GB Card' ● ● ● ● ● ● 2 GB micro SD memory card Up to 256 audio files with a total duration of 3 h For industrial applications Water-tight Dust-tight Guaranteed data storage: >10 years Extras (Second source) NOTICE! Order alternatives only if the preference is not available.
PCA2018-A1 'MeanWell SD-100B-24 DC/DC' ● ● ● ● ● ● Controlled DC 24 V (100 W) output voltage, electrically isolated Internal 24 V energy supply protected against short-circuits on the external 24 V supply line outside the system cabinet Protected against short-circuit, overloading and overvoltage DC 1500 V I/O isolation 100 % full load burn-in test Fixed switch frequency of 83 kHz I/O interfaces PCIO2001-A1 'Input/Output extension (digital 16)' ● ● ● ● ● ● PCIO2002-A1 'Input/output module (digital, 16
Automatic volume control PCA2008-A1 'Automated volume control module' ● ● ● ● ● ● ● ● ● ● PCA2007-A1 Supports automatic volume control to suit levels of background noise Measures the noise level in a designated area Connects up to four microphones PCA2007-A1 Supports microphone and line level Supplies the connected microphones with DC 12 V phantom voltage Monitors the microphone wiring for short, interruption and ground fault Fault message via relay changeover contact (Fault / Okay) Installation in the s
Loop isolators PCA2005-A1 'Loop isolator (100V)' ● ● ● ● ● PCA2013-A1 Isolating element in accordance with EN 54-17 for use in a 100 V speaker line with PC2003-A1, as well as the 'Voice alarm panel Compact 400' PC1001-A3 and the 'Voice alarm panel Compact 1000' PC1002-A3 Rapidly detects and isolates short-circuits affecting the 100 V speaker line Monitors the speaker and cables connected to the loop isolator for open lines and short-circuits Two-pole standard lines used as cables for the speaker loop Op
PACE-Bus PN1002-A1 'RS485 module (1 port)' ● ● ● ● ● ● ● PNA2009-A1 1x 'PACE-Bus' (RS485) port 2-way optical isolated 'PACE-Bus' (RS485) repeater Provides controlled DC 24 V electrically isolated output Provides electrically isolated analog audio input Provides electrically isolated analog audio output Monitoring of the DC 24 V line for ground faults Plug-in module for Cerberus PACE Compact digital audio matrix boards 'ICPDAS I-7510 (RS485, isolated)' ● ● 2-way optical isolated 'PACE-Bus' (RS485) repea
FDCIO222 'Input/output module FDnet/C-NET' ● Input/output module FDCIO222: – Four control outputs with potential-free relay contacts for activation of fire doors, fans, air conditioning systems, lift controls, etc.
Other accessories PCA2015-A1 'TAS ULE-614 Dialer' ● ● ● ● ● PCA2016-A1 'Müller SC 95.47 PRO Clock' ● ● ● ● ● ● ● PCA2019-A1 Gateway between telephone system (VoIP) to analog audio LAN interface 10/100 Base T(x) (VoIP with SIP-Protocol) Analog audio input and output, potential-free 2 remote controlled potential-free digital output contacts 2 digital inputs Masterclock for approximately 200 slave clocks (DC 24 V, 1.
Type Overview Order numbers Type Designation Order number ATP AF2GUD-2*** SD 2 GB S54451-B20-A1 Swissbit SFSD2048N1 SD 2 GB S54451-B20-B1 Preferred extras1 PCA2002-A1 Second source extras1 PCA2017-A1 Accessories for operating terminals / call stations PCA2001-A1 Ground fault monit. (24V) S54451-B19-A1 PCA2011-A1 MeanWell SD-50B-24 DC/DC S54451-B65-A1 PCA2018-A1 MeanWell SD-100B-24 DC/DC S54451-B75-A1 PCIO2001-A1 IN/OUT extent.
Type Designation Order number Fire components for connection of a fire detection panel FDCIO221 Input/output module FDnet/C-NET S54312-F2-A1 FDCIO222 Input/output module FDnet/C-NET A5Q00002369 FDCIO223 Input/output module FDnet/C-NET S24218-B102-A1 FDCIO224 Input/output module FDnet/C-NET A5Q00018689 PCA2015-A1 TAS ULE-614 Dialer S54451-B81-A1 PCA2016-A1 Müller SC 95.
Product documentation You will find more information on the Cerberus PACE Compact system and its components in the following documents: Title Document ID IT security policies Cerberus PACE Compact – IT security policies A6V11439692 System documentation Cerberus PACE Compact – planning A6V11899877 'PACE-Design' – configuration A6V10429097 Cerberus PACE Compact – mounting / installation A6V11899867 Cerberus PACE Compact – operation A6V11899865 Data sheets System data sheet A6V11868429 Voice alar
Notes Safety CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. ● Observe national provisions and comply with the appropriate safety regulations. Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose.
Technical data Extras SD card PCA2002-A1 PCA2017-A1 Preferred Second source 2.7…3.6 V 2.7…3.6 V <50 mA <110 mA 50 Mhz max. 50 Mhz max.
Call stations / operating terminals Ground fault monitoring (24 V) PCA2001-A1 Supply Power supply Current consumption Threshold Relay contact Fault indicator relay DC 24 V (corresponds to the voltage to be monitored) 100 mA 50 kohm (10 kohm if JP1 and JP2 closed) Max.
DC/DC converter PCA2011-A1 PCA2018-A1 Nominal output voltage DC 24 V DC 24 V Maximum output current 2.1 A 4.2 A 50.4 W 100.8 W Residual ripple and noise 150 mVp-p 150 mVp-p Adjustable output voltage range DC 23…30 V DC 23…30 V DC 19…36 V DC 19…36 V Input current 3.0 A / 24 V 4.8 A / 24 V Efficiency 80 % / 24 V 78 % / 24 V 105...150 % nominal output 105...135 % nominal output 31.5...37.5 V / 10 % load 31.5...37.
PCA2011-A1 PCA2018-A1 I/P-O/P: 1.5 kVAC I/P-FG: 1.5 kVAC O/P-FG: 0.5 kVAC I/P-O/P: 1.5 kVAC I/P-FG: 2.0 kVAC O/P-FG: 0.
PCIO2001-A1 PCIO2002-A1 DC 0...10 V DC 0...10 V 8 (max. 15 / matrix) 8 8 bit 8 bit 0.2 mA 0.2 mA Analog control inputs Input voltage range Number Resolution Input current at 10 V Interface RS485 Serial interface to matrices Baud rate 1x RS485 9600, 19200, 56700, 115200 Baud Module connections Up to 4 modules via RS485 Max. cable length 500 m Interface RS232 Baud rate Module connections Max.
Output module PCO2002-A1 PCO2003-A1 Supply Power supply DC 24 V (18 V <36 V) Current consumption 56 mA /200 mA when 8 relays are active Internal power supply DC 12 V Maximum load 100 mA / DC 12 V Digital control outputs Number and type 8 electrically isolated relay outputs with 2-pole changeover contacts Max. voltage AC 100 V, DC 30 V Max. current per output 5A Isolation voltage 10 kV Interfaces Serial interfaces Baud rate Module connection Max.
Automatic volume control Automated volume control module PCA2008-A1 Supply Power supply DC 24 V Current consumption 100 mA Microphone connection Max PCA2007-A1 connected Microphone power supply Microphone input sensitivity selectable 4 DC 12 V phantom power Electrically isolated from the power supply. Line level or microphone level Max. input level (MIC) 12 μV/Pa Max.
Automated volume control microphone PCA2007-A1 Type Electret microphone Supply Power supply Current consumption Cable connection DC 12 V phantom power (up to 48 V possible) 2 mA at 12 V 3-pin terminal: Cable gland PG 9 (cable diameter 2.5…8 mm) Audio properties Frequency band 100 Hz…10 kHz +/-6 dB Outputs: ● Max. output level (MIC) 12 μV/Pa ● Max.
EOL modules EOL3 (active) PCA2004-A1 Supply Power supply AC 8…100 V Power consumption Max. 150 mW Typ. 100 mW Max. line output (corresponds to max. amplifier output on speaker line) Cable connection 500 W Max. 2x 1.5 mm² Maximum number of modules in use Max. number of modules per amplifier 16 Max. number of modules per speaker line 16 Max.
Loop isolators Loop isolator (100V) PCA2005-A1 Supply Operating voltage AC 16…100 V Operating power 75 mW nominal 150 mW in startup Line separating function Pilot tone frequency ● Normal mode ● Alarm mode 20 kHz with configured On/Off-time 21 kHz Line voltage at pilot tone frequency: ● Minimum AC 16 V ● Nominal AC 25 V ● Maximum AC 100 V Voltage at which the 'Loop isolator (100V)' opens: ● Minimum AC 7 V ● Maximum AC 9 V Voltage at which the 'Loop isolator (100V)' closes: ● Minimum
PCA2005-A1 LED connection Recommended color Red Diode bias voltage < 2.
PCA2005-A1 Connections Design Cable diameter Spring type Min.: 0.75 mm² Max.: 2.5 mm² Loudspeaker cable: 2) Maximum cable length per amplifier output Cable types, untwisted only 1000 m FP30/60 NYM, 2 x 1.5 mm² ISTY 2 x 2 x 0.8 mm² Ambient conditions Operating temperature -5…+40 °C Storage temperature -20…+70 °C Operation in humid environments (without moisture condensation) 10...90 % rel. Storage in humid environments (without moisture condensation) 5...90 % rel.
Spelsberg i 16-L Li Box PCA2013-A1 Rated insulation voltage AC 400 V Conductor cross-section Max. 2.5 mm2 Ambient conditions Operating temperature -25…+40 °C Max. operating temperature (24 hours) 35 °C Max. air humidity at 25 °C (short-term) 95 % rel. Max. air humidity at 40 °C 50 % rel.
PACE-Net RJ45 interface PNA2008-A1 Connections Copper Network standards 1 RJ45 connector 9 screw terminals 0.2...4 mm2 Conforms to IEEE 802.3, 100Base-TX, 10Base Ambient conditions Operating temperature -20…+70 °C Storage temperature -20…+70 °C Operation in humid environments (without moisture condensation) 10...90 % rel. Storage in humid environments (without moisture condensation) 5...90 % rel.
PACE-Bus ICPDAS I-7510 (RS485, isolated) PNA2009-A1 Supply Power supply DC 24 V (10…30 V) Power consumption 2.2 W Current consumption 90 mA at 24 V Protection Power reverse Over-voltage Brown-out Interfaces Serial interfaces Transmission speed Max. cable length Asynchronous half-duplex 2-wire RS-485 300...
RS485 module (1 port) PN1002-A1 Supply Power supply DC 24 V (18…28 V) Power consumption 2.2 W Current consumption 25 mA Protection Over-voltage Short circuit Earth fault detection Interfaces Serial interfaces Standard RS485 to 3.
I/O modules Input/output module FDnet/C-NET FDCIO221 Supply Operating voltage DC 12…33 V Operating current (quiescent) Max. 0.4 mA Relay output (ohmic) Line resistance (input) AC 22 V, 2 A, max. 44 VA DC 30 V, 2 A, max. 60 W Max. 20 Ω Communication protocol FDnet/C-NET Connection terminals 0.2…2.5 mm² Ambient conditions Operating temperature -25…+70 °C Storage temperature -30…+75 °C Air humidity (non-condensing) ≤95 % rel.
FDCIO222 FDCIO224 Supply Operating voltage DC 12…33 V Operating current (quiescent) Max. 0.75 mA Relay output Communication protocol AC 250 V / 4 A, max. 1000 VA DC 30 V / 4 A, max. 120 W FDnet/C-NET Connections ● Pluggable connection terminals ● MC link 0.2…1.5 mm² (with 2.5 mm²connection terminal DBZ1190 AB) Plug connection 3.5 mm jack socket Ambient conditions Operating temperature -25…+60 °C Storage temperature -30…+65 °C ≤95 % rel.
FDCIO223 Supply FDnet/C-NET operating voltage DC 12…33 V Operating current Max. 0.75 mA Maximum current connection factor 3 External power supply Input voltage DC 18…32 V Operating current without secondary load at 24V 26 mA (typ.) 60 mA (max.) Operating current with secondary load Max.
FDCIO223 Protection category (IEC 60529) When mounted on a U-rail in a fire control panel IP30 With housing FDCH221 IP65 36 Smart Infrastructure A6V11940275_en--_b 2021-03-12
Other accessories TAS ULE-614 Dialer PCA2015-A1 PCA2015-A1 Supply Operating voltage Operating current (quiescent) DC 24…42 V (1.
Müller SC 95.47 PRO Clock PCA2016-A1 PCA2016-A1 Supply Operating voltage Operating current (quiescent) Receiver Housing type 230 V, 50...60 Hz or DC 24 V with max. 3 A Max. 3 A DCF77 or GPS Self-extinguishing thermoplastic 19" housing (2 HU, 48 DU) Ambient conditions Operating temperature -30…+50 °C Storage temperature -30…+50 °C Humid environments (without moisture condensation) Max. 95 % rel. (non-condensing) Dimensions and weights W x H x D mm Weight 483 x 86 x 203 2.
ITEC CD/USB/SD-Player PCA2019-A1 PCA2019-A1 Supply Operating voltage 230 V / 50 Hz Connection Stereo RCA-jack 775 mV line level output Housing type 19" / 1 HU steel housing Ambient conditions Operating temperature -25…+75 °C Storage temperature -25…+75 °C Humid environments (without moisture condensation) 10...90 % rel. Dimensions and weights W x H x D mm Weight Standards 482 x 315 x 44 4.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID A6V11940275_en--_b Edition 2021-03-12 © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.