Cerberus PACE MP2.1 Public Address and Controlled Evacuation System EN 54-16-certified multi-channel voice alarm control and indicating equipment for demanding digital and network-based public address and evacuation applications.
System overview Fig. 1: System overview Cerberus PACE is a network-based public address and voice alarm (PA/VA) system that complies with the requirements of EN 54-16 and allows for a decentralized and redundant system structure. It is an important feature of the system that the critical risks of single point of failure vulnerabilities are eliminated. A typical Cerberus PACE system is comprised of digital audio matrices, amplifiers, operating terminals, and call stations.
System Applications Cerberus PACE is designed for the following applications: ● Alarm and evacuation – Automatic activation of acoustic alarm and evacuation announcements through a connected hazard detection system, such as a fire detection system – Manual activation of acoustic alarm and evacuation announcements by trained staff – Live announcements made by trained staff ● – Playback of announcements recorded in advance Announcements – Background music – Live announcements, with optional delay feature –
Component Application Digital audio matrices The Cerberus PACE audio matrices process audio signals from the digital network, the internal digital memory (flash), the micro SD card, and the analog audio inputs. The audio matrices automatically digitize analog audio signals so they can be processed further. Each audio signal is assigned to an audio channel. A Cerberus PACE digital audio matrix can manage up to 255 audio channels. Cerberus PACE audio matrices are standard network participants.
Call stations Cerberus PACE offers a range of call stations for various applications. The alarm and standard call station PT2001-A1 is a network based 'PACE-Net' desk call station with 19 buttons and indicators.
Operating terminals The operating terminals display with color-coded LEDs the operating and fault status of the system, and provide color-coded buttons to trigger, reset and silent alarms.
System components Digital audio matrices You will find more information and technical data on the digital audio matrices in the 'Digital audio matrix, Ethernet switches, media converter' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
PC2003-A1 'Digital audio matrix (4/4/16)' ● ● ● ● ● ● ● ● ● ● ● ● ● ● PC2005-A1 'Digital audio matrix no supervision (4/4/0)' ● ● ● ● ● ● ● ● ● ● PC2006-A1 4 analog audio inputs and 4 analog audio outputs 16x 100 V speaker lines 8 logic control inputs and 8 logic control outputs 19'' / 1 HU housing Ethernet-based 100 Mbit/s network interface Serial interface 'PACE-Bus' (RS485) to communicate with internal and external components Integrated micro SD card reader for alarm messages and music Simultaneous
Ethernet switches You will find more information and technical data on the Ethernet switches in the 'Digital audio matrix, Ethernet switches, media converter' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
Media converter You will find more information and technical data on the media converters in the 'Digital audio matrix, Ethernet switches, media converter' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
Call stations You will find more information and technical data on call stations in the 'Call stations and extensions' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
PT2001-A1 'Desk call station (19 buttons)' ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● PTO2001-A1 'Desk call station extension (24 buttons)' ● ● ● ● ● PTO2002-A1 Desk call station with electret condenser microphone and gooseneck 19 configurable buttons and status indicators to control and monitor the Cerberus PACE system by users The buttons are basically freely operable Full network participant in a Cerberus PACE system Insertable labels for custom buttons and indicator identification 2-line text display Moni
PTO2003-A1 'Desk call station extension (Nordic)' ● ● ● ● PTO2004-A1 'ITEC SPM-DM microphone DCS' ● ● ● ● ● ● PTO2005-A1 Optional dynamic gooseneck microphone For 'Desk call station (19 buttons)' PT2001-A1 Supercardioid characteristics Excellent suppression of background noise Highly dynamic performance and wide frequency band with low distortion XLR connection 'Mounting kit DCS (19"/5HU)' ● ● ● ● PT2008-A1 Optional key switch (Nordic) extension For 'Desk call station (19 buttons)' PT2001-A1 Call st
PT2009-A1 'Desk call station (RS485, 8+1)' ● ● ● ● ● ● ● ● ● ● ● ● ● ● PTO2006-A1 'Call station extension (RS485, 8)' ● ● ● ● ● ● PTO2008-A1 Desk call station with electret condenser microphone and gooseneck 8 configurable and illuminated zone buttons plus a talk button to control and monitor the Cerberus PACE system by users Buttons are freely operable Monitored microphone Symmetrical audio transmission, analog 'PACE-Bus' (RS485) data transmission Audio output 0 dB (line level) Connection to control p
PTO2009-A1 'Call station interface (redundant)' ● ● ● ● ● ● ● ● Adapter connecting net-based 'PACE-Net' call stations to a control panel Can be used for PT2001-A1 and PT2002-A1 Provides redundant 'PACE-Net' and 24 V connection Monitors 24 V connection Automatic switch to redundant pair in case of a connection fault 'PACE-Net' interface from screw terminals to RJ45 connector Reports faults with a relay contact 35 mm DIN rail mounting model for an installation in a call station or close by a call station 1
Operating terminals You will find more information and technical data on the operating terminals in the 'Operating terminals' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
PT2004-A1 'System state indicator (19")' ● ● EN 54-16-compliant indicator panel for visual and acoustic status messages Color-coded visual indicators: operation, fault, and alarm – : green – : yellow PT2005-A1 ● ● – : red Fault warning with acoustic warning signal Buttons to acknowledge acoustic warnings and LED test: ● ● – : black Potential-free fault contact Design: 19", 1 HU 'Alarm control panel
Power amplifiers You will find more information and technical data on the power amplifiers in the 'Power amplifiers' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
PV2003-A1 'Power amplifier (4x150W)' ● High efficiency Class-D audio power amplifier ● 10 W in standby mode ● 19'' / 2 HU housing ● Protected against idling, short circuits, overheating, DC Audio power outputs ● 4x 150 W, 100 V or 50 V audio power outputs or ● 2x 300 W (bridged mode), 100 V audio power outputs Inputs ● 1x DC 24 V power supply ● 1x AC 230 V power supply ● 4x analog audio inputs ● 2x analog audio bridge inputs ● 2x logic control inputs: activate channels, activate channels in bridged mode ●
PV2011-A1 'Power amplifier (2x500W)' ● High efficiency transformerless direct output audio power amplifiers ● 2x 10 W in standby mode ● 19'' / 2 HU housing ● Protected against idling, short circuits, overheating, DC Audio power outputs ● 2x 500 W, 100 V audio power outputs Inputs ● 2x DC 24 V power supply ● 1x AC 230 V power supply ● 2x analog audio inputs ● 2x 2 logic control inputs: enable amplifier, power supply off Outputs ● 2x 3 status indicator open collector outputs: AC mains voltage, DC power suppl
Preferred power supplies You will find more information and technical data on power supplies in the 'Power supplies and batteries' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section. NOTICE! These power supplies are to be preferably ordered.
Second source power supplies You will find more information and technical data on power supplies in the 'Power supplies and batteries' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section. NOTICE! Order alternatives only if the preference is not available.
Preferred batteries NOTICE! These batteries are to be preferably ordered. You will find more information and technical data on batteries in the 'Power supplies and batteries' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
Second source batteries NOTICE! Order alternatives only if the preference is not available. You will find more information and technical data on batteries in the 'Power supplies and batteries' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
PA2016-A1 'SunBattery SB12-100HFT Battery' ● ● ● ● ● ● ● ● PA2013-A1 'Triathlon FT-12150 Battery' ● ● ● ● ● ● ● ● PA2017-A1 Maintenance-free lead battery Capacitance: 100 Ah Voltage: 12 V Rechargeable Front terminals Gas-tight Acid-free Second source for PA2008-A1 Maintenance-free lead battery Capacitance: 150 Ah Voltage: 12 V Rechargeable Front terminals Gas-tight Acid-free Second source for PA2009-A1 'SunBattery SB12-150AFT Battery' ● ● ● ● ● ● ● ● Maintenance-free lead battery Capacitance: 150 Ah
Cabinets You will find more information and technical data on the 19" cabinets in the '19" cabinets' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
PH2006-A1 'Rittal (24HU, fix, 80x80)' ● ● ● ● ● ● ● ● ● PH2007-A1 'ERA (40HU, swivel, 80x80)' ● ● ● ● ● ● PH2008-A1 24 HU 19" frame, fixed, with profile rails External dimensions: 800 x 800 mm Active ventilation Aluminum viewing front door, lockable Sheet-steel back door, lockable Roof panel with cable entry points Base with four corner pieces and corresponding orifices Circuit diagram holder, A4 40 HU 19" swivel frame External dimensions: 800 x 800 mm Active ventilation Viewing front door, lockable I
PH2009-A1 'ERA (43HU, fix, 80x80)' ● ● ● ● ● ● PH2010-A1 'ERA (26HU, fix, 80x80)' ● ● ● ● ● ● PH2011-A1 26 HU 19" frame, fixed External dimensions: 800 x 800 mm Active ventilation Viewing front door, lockable Integrated base 'ERA (43HU, fix, 60x60)' ● ● ● ● ● ● PH2012-A1 43 HU 19" frame, fixed External dimensions: 800 x 800 mm Active ventilation Viewing front door, lockable Integrated base 43 HU 19" frame, fixed External dimensions: 600 x 600 mm Active ventilation Viewing front door, lockable Integ
Accessories and options You will find more information and technical data on accessories and options in the 'Accessories and options' data sheet. You will find the relevant document ID in the 'Product documentation [▶ 44]' section.
PCA2018-A1 'MeanWell SD-100B-24 DC/DC Converter (100W)' ● ● ● ● ● ● ● PCA2014-A1 'Backup extension PC2003' ● ● PCIO2001-A1 Extends the digital audio matrix PC2003 with an additional backup amplifier input Allows addition of a backup amplifier with use of all 4 amplifier channels 'Input/Output extension (digital 16)' ● ● ● ● ● ● ● ● PCIO2002-A1 Controlled DC 24 V (100 W) output voltage, electrically isolated Internal 24 V energy supply protected against short circuits on the external 24 V supply line
PCO2002-A1 'Output module (relay, 8)' ● ● ● ● ● ● ● PCO2003-A1 'Output extension (relay, 8)' ● ● ● ● ● ● ● PCA2008-A1 Provides additional relay outputs Extension module for PCIO2002-A1 and PCO2002-A1 Communication via 'PACE-Bus' (RS485) interfaces Extends a digital audio matrix by additional 8 relay outputs The component includes 8 relays with 2-pole changeover contacts The maximum permissible switching current for each changeover contact is 5 A / 100 V 35 mm DIN rail mounting model for the installatio
PCA2004-A1 'EOL3 (active)' ● ● ● ● ● ● ● ● PCA2005-A1 'Loop isolator (100V)' ● ● ● ● ● ● ● ● PCA2013-A1 Monitoring of speaker lines in accordance with EN 54-16 For use with the digital audio matrices PC2001-A1, PC2002-A1 and PC2003A1 Monitoring the 100 V speaker line for open lines and short circuits Addressable: up to 16 different addresses can be configured Addressing compatible with any tree structure with up to 16 line ends, in addition to the stub line Reliable cable break detection in any branch
PNA2007-A1 'Repeater (CAT5)' ● PNA2008-A1 'Camdenboss RJ45 Interface' ● ● PNA2009-A1 2-way optical isolated 'PACE-Bus' (RS485) repeater 35 mm DIN rail mounting model for the installation in a system cabinet 'TAS ULE-614 Dialer' ● ● ● ● ● PCA2016-A1 Interface from RJ45 connector to screw terminals 35 mm DIN rail mounting model 'ICPDAS I-7510 (RS485, isolated)' ● ● PCA2015-A1 Extension of 'PACE-Net' 100 Mbit/sec copper Ethernet cable (CAT5) wiring by additional 100 m Gateway between telephone syst
PCA2019-A1 'ITEC CD/USB/SD-Player' ● ● ● ● ● ● ● ● PCA2020-A1 'Müller Clock FU 30.00 PRO GPS receiver' ● ● ● PCA2021-A1 Optional GPS radio receivers FU 30.00 pro For 'Müller SC 95.47 PRO Clock' PCA2016-A1 Wall mounting with mounting bracket 'Müller Clock FU 20.
FDCIO222 'Input/output module FDnet/C-NET' ● Input/output module FDCIO222: – Four control outputs with potential-free relay contacts for activation of fire doors, fans, air conditioning systems, lift controls, etc.
FDCIO224 'Input/output module FDnet/C-NET' ● Input/output module FDCIO224: – Four control outputs with potential-free relay contacts for activation of fire doors, fans, air conditioning systems, lift controls, etc.
LOGO! DM16 24R 'Siemens LOGO! DM16 24R Digital expansion module' ● ● ● ● PHA2007-A1 Digital expansion modules for 'Siemens LOGO! 12/24RCE Logic module' LOGO! 12/24RCE 8 additional relay outputs 8 additional logic control inputs 35 mm DIN rail mounting model for the installation in a system cabinet 'Battery tray (19")' ● ● ● ● Battery tray For all 80 x 80 Rittal and ERA cabinets Secure fixation of the batteries Holds up to 4x 150 Ah front terminal batteries 37 Smart Infrastructure A6V11243351_en--_d 2
Preferred extras NOTICE! These extras are to be preferably ordered. PCA2002-A1 'ATP AF2GUD-2*** SD 2 GB Card' ● ● ● ● ● ● 2 GB micro SD memory card Up to 256 audio files with a total duration of 3 h For industrial applications Water-tight Dust-tight Guaranteed data storage: >10 years Second-source extras NOTICE! Order alternatives only if the preference is not available.
Order numbers Type Designation Order number PC2001-A1 Digital audio matrix (4/4/4) S54451-B1-A1 PC2002-A1 Digital audio matrix (0/4/4) S54451-B2-A1 PC2003-A1 Digital audio matrix (4/4/16) S54451-B3-A1 PC2005-A1 Dig audio no supervis (4/4/0) S54451-B76-A1 PC2006-A1 Dig audio no supervis (0/4/0) S54451-B77-A1 PN2001-A1 Ethernet switch (2x4/2) S54451-B4-A1 PN2008-A1 Ether.
Type Designation Order number PTO2001-A1 Desk call stat. ext.(24 btn) S54451-B7-A1 PTO2002-A1 Desk call stat. ext. (Kaba) S54451-B8-A1 PTO2003-A1 Desk call stat. ext.(Nordic) S54451-B48-A1 PTO2006-A1 Call station ext. (RS485, 8) S54451-B51-A1 PTO2008-A1 Call stat.
Type Designation Order number PA2006-A1 Merawex MXL 40-12 Battery S54451-B68-A1 PA2007-A1 Merawex MXL 65-12 Battery S54451-B69-A1 PA2008-A1 Merawex MXL 100-12 FT Batt. S54451-B70-A1 PA2009-A1 Merawex MXL 150-12 FT Batt.
Accessories Type Designation Order number ATP AF2GUD-2*** SD 2 GB S54451-B20-A1 Swissbit SFSD2048N1 SD 2 GB S54451-B20-B1 Preferred extras 1 PCA2002-A1 Second source extras 1 PCA2017-A1 Accessories for operating terminals / call stations PN2009-A1 RS485 mod. (1 port, DIN rail) S54451-B87-A1 PCA2001-A1 Ground fault monit.
Type Designation Order number Fire components for connection of a fire detection panel FDCIO221 Input/output module FDnet/C-NET S54312-F2-A1 FDCIO222 Input/output module FDnet/C-NET A5Q00002369 FDCIO223 Input/output module FDnet/C-NET S24218-B102-A1 FDCIO224 Input/output module FDnet/C-NET A5Q00018689 Modules for basic automation and control task LOGO! 12/24RCE Logic module 6ED1052-1MD08-0BA1 LOGO! AM2 Analog expansion module 6ED1055-1MA00-0BA2 LOGO! DM16 24R Digital expansion module
Product documentation You will find more information on the Cerberus PACE system and its components in the following documents: Title Document ID IT security policies Cerberus PACE – IT security policies A6V11439692 System documentation Cerberus PACE – planning A6V11244536 'PACE-Design' – configuration A6V10429097 Cerberus PACE – mounting / installation A6V10430579 Cerberus PACE – operation A6V10430571 Data sheets System data sheet A6V11243351 19" cabinets A6V10429243 Digital audio matrix A
Notes Safety CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. ● Observe national provisions and comply with the appropriate safety regulations. Configuration 'PACE-Design' is a Windows-based software used to configure and monitor the Cerberus PACE system. Large-scale systems become easier to operate because of its comprehensive monitoring and logging features.
Technical data You will find more information and technical data on the system components and accessories in the separate data sheet for the product group in question. You will find more information on the available data sheets and the corresponding document IDs in the section 'Product documentation [▶ 44]'.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID A6V11243351_en--_d Edition 2021-06-30 © Siemens Switzerland Ltd, 2018 Technical specifications and availability subject to change without notice.