Configuration Instructions

System configuration
EN 54-16 Specific settings
5
A6V10429097_en--_e
47 | 219
Parameters
Description
'EN5416: Enabled'
Errors are detected within the requested time of 100 s.
Fault state: An error state is indicated until a manual reset and/or another
manual operation at access level 2 or 3 is performed.
LED colors of the 'Desk call stat. (19 buttons)' keypad meet the
specifications of EN 54-16.
'EN5416: Disabled'
LineDetection errors not occurring within the requested time
'Desk call stat. (19 buttons)' LEDs feature a special mode so they can be
detected immediately.
'Remote Triggered'
Deprecated mode for triggering an alarm file 001.wav that may be present
via a remote contact using 'Alarm Start/Stop…'.
'Audible warning'
Option meets the requirements of EN 54-16. Audible indication of the voice
alarm condition.
A buzzer connected on the indication board is enabled for the following
devices:
'Digital audio matrix (4/4/4)'
'Digital audio matrix (0/4/4)'
'Digital audio matrix (4/4/16)'
Cerberus PACE Compact digital audio matrix board
The internal speaker generates this audible warning for a 'Desk call stat. (19
buttons)'.
WARNING! The checkbox 'Acoustic signal' must be checked.
The connected buzzer or connected audible warning can be silenced as
follows:
With the macro 'R' to silence via keypad
With a logic input, specified as 'Test&Quit key'
'DisableZonekeysOnCalls'
Disable functionality to add/remove zones on own triggered calls
'ActiveLineSignaling'
LED on a zonekey signals that a line of this zonekey has been activated by an
alarm.
'SignalLeds_on_VirtKeypad'
(all other Device Types)
-
'SkipLeds_on_Prior0Calls'
-