Configuration Instructions
System configuration
EN 54-16 – Specific settings
5
48 | 219
A6V10429097_en--_e
5.4.1 Manual silencing of the voice alarm condition (option
with requirements)
EN 54-16, chapter 7.6.2
'It shall be possible to manually silence the voice alarm message from the
↑ VACIE at access level 2. In this case, following manual silencing, it shall be
possible to reactivate the voice alarm message at access level 2.'
Configuring the digital inputs accordingly
1. Enable and assign a name to a desired digital input as follows:
– 'EN54-16: Alarm Manual Silence'
2. Select a '*.wav' file:
– 'Standard: 001.wav'
3. Optional: Press a button on the target station. Standard: 1 <no button>
4. Mandatory: Enter the target station ID.
Configuring the logic outputs accordingly
The station ID corresponds to the station ID of the relevant digital input 'EN 54-
16: Alarm Manual Silence'.
◈
Enable the logic input with the following function:
– 'System Variable(SysVarID)' with SysVarID=6(VASA)
5.4.2 Manual reset of the voice alarm condition (option with
requirements)
EN 54-16, chapter 7.7.2
7.7.2.1: 'It shall be possible to reset the voice alarm condition from the VACIE at
access level 2 by means of a separate manual control. In this case, this control
shall be used only for reset and may be the same as that used for reset from the
fault warning condition.'
7.7.2.2: 'Following a manual reset operation, the indication of the correct functional
condition corresponding to any received signals shall either remain or be re-
established within 20 s.'
Configuring the digital inputs accordingly
◈
Enable the desired input, and define it as follows:
– 'Alarm Stop'