Project Name 230900 - 1 BAS AND CONTROL FOR HVAC
Date
SECTION 23 09 00 – BUILDING AUTOMATION SYSTEM
This is supplemental language for a spec. This is not an all inclusive spec. This is language that is
meant to be copied and pasted into an existing spec.
PART 1 - GENERAL
PART 2 - PRODUCTS
2.1 PRESSURE INDEPENDENT CONTROL VALVES (PICV)
A. General
1. All control valves shall be sized by the control vendor. All control valve bodies shall be
suitable for the static and dynamic pressures of the system. Control valve operators shall
be sized to close against a differential pressure equal to the design pump head plus 10
percent.
a. Body pressure rating and connection type construction shall conform to fitting and
valve schedules. Design body pressure shall be determined by the adding the static
pressure due to the height of the system plus the compression tank charge plus the
maximum head of the system pump at cut off. Provide 10% design factor.
2. The valve seat differential pressure rating shall exceed the pump dynamic head design
pressure.
3. All automatic control valves controlled by the BAS shall be furnished by the controls
contractor unless otherwise noted in these documents.
4. All automatic control valves shall be installed by the mechanical trade.
5. The controls contractor shall provide wiring as follows:
a. All line voltage power for electric valve actuators shall be wired by the controls
contractor from the nearest available power panel. Coordinate with electrical
trade.
b. All low voltage wiring between the controller and the valve actuator shall be wired
by the controls contractor.
c. All wiring between safeties and the valve actuator shall be wired by the controls
contractor.
d. All wiring shall comply with code requirements. Segregate high and low voltage
wiring and circuits and segregate the Fire Alarm (FACS) and BAS controls wiring.
B. Manufacturer
1. Siemens 599 series valves bodies, SSD, SAX, SQV Actuators, Series 230, 231, 232, 233,
238, 239, 371, and 373 assemblies
C. Where to use PICVs
1. Provide PICVs where called for in the specifications, sequences of operations, or on the
drawings.
2. If it is not stated elsewhere, PICV valves should be provided to meet the following
guidelines:
a. Provide in direct return, constant speed pumping systems.