Basic Documentation

Table Of Contents
Project Name 230900 - 2 BAS AND CONTROL FOR HVAC
Date
b. Provide in direct return, variable flow water systems where with the system at full
flow the pressure differential between the supply connection and the return
connection is more than double the pressure drop of the circuit or loop at design
flow (including piping, fittings, devices, control valve and coil).
c. Provide in reverse return, constant speed pumping systems where the circuits and
loop pressure drops differ by more than 50%.
d. Provide in reverse return, variable speed pumping systems where the differential
pressure between the systems will vary more than the pressure drop of the circuit
or loop.
e. Provide in systems that have direct return headers and reverse return branch lines
where with the system at full flow the pressure differential between the supply
connection and the return connection is more than double the pressure drop of the
branch at design flow (including piping, fittings, devices, control valve and coil).
D. Piping for circuits with PICVs
1. Systems installed with PICVs shall not require balancing valves.
2. Calibrated balancing valves shall not be required in branches or loops where PICV are
installed.
3. Automatic flow control valves are strictly prohibited in branches or loops where PICVs
are installed.
4. Circuit setters may be required for coils with multiple sections. Follow the piping details.
5. Install pressure ports on either side of the coil for the balancer to test the flow across the
coil at different system flows.
E. Sizing Criteria (Pressure Independent):
1. Two-way modulating service:
a. Determine the design GPM of the actual coil that is selected be used (may be
different than the coil and GPM on the design coil schedule).
b. Select the PICV valve with a GPM rating higher than the GPM required.
c. If more than one valve fits the GPM rating, then pick the valve that matches or is
closest to the line size of the circuit piping.
d. If the maximum GPM of the valve exceeds the design GPM required, then adjust
the Flow Limiter setting on the valve to the GPM required plus 10%.
e. Traditional flow coefficient and pressure drop sizing is not applicable to PICV
valves.
F. Flanged Valves, line size 2 ½” and larger
1. Controlled Media Specific Items
a. The control valve shall be suitable for chilled water to a minimum of 34°F (1°C)
and hot water to a maximum temperature of 248°F (120°C).
b. The control valve shall be suitable for up to 50% ethylene or propylene glycol
solutions, chilled glycol/water solutions to a minimum of 34°F (1°C) and hot
glycol/water solutions to a maximum temperature of 248°F (120°C).
2. General Construction Materials/Applicable
a. Control valve bodies shall be constructed of cast iron and shall meet requirements
of ANSI 125 or ANSI 250 pressure classes.
b. Inlets and outlets shall be clearly marked on the valve bodies.
c. Valves shall be constructed with a single chamber and multiple seats to provide
flow limiting, pressure compensation and flow control.
d. Valves shall contain a mechanical, spring-loaded pressure independent regulator to
maintain a consistent differential pressure across the control port of the valve.